NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings
Filter
I12
TAS Part I12 Premises for manufacture or processing of glass reinforced plasticsTAS Part I12 Premises for manufacture or processing of glass reinforced plastics
Introduction to this Part
This Part contains additional requirements for premises used for the manufacture or processing of glass reinforced plastics.
Deemed-to-Satisfy Provisions
NCC Blurbs
- provide for the safety and comfort or workers; and
- be constructed in a manner that will avoid the spread of fire within the building and to other buildings.
NCC Title
Application of Part
NCC State
TAS
NCC SPTC Current
Application of Part
Building Classes
1a,1b,10a,10b,10c
NCC Blurbs
A building for the manufacture or processing of glass reinforced plastics must be—
- separated from other buildings or parts of an occupancy by means of impervious walls with FRL at least 120/120/120; or
- separated from all other buildings by a clear space of not less than 6 m.
NCC Title
Separation from other buildings
NCC State
TAS
NCC SPTC Current
Separation from other buildings
Building Classes
1a,1b,10a,10b,10c
NCC Blurbs
The building must be of single storey construction.
NCC Title
Rise in storeys
NCC State
TAS
NCC SPTC Current
Rise in storeys
Building Classes
1a,1b,10a,10a,10c
NCC Blurbs
The floor area of any building or fire-separated section must not exceed the relevant maximum floor area set out in Table TAS I12D4.
Insert TAS table (I12D4) I12D4 as follows:
Type A building construction | Type B building construction | Type C building construction |
---|---|---|
Not sprinklered: 1500 m2 | Not sprinklered: 1200 m2 | Not sprinklered: 1000 m2 |
Sprinklered: 6000 m2 | Sprinklered: 5000 m2 | Sprinklered: 3000 m2 |
NCC Title
Maximum floor areas
NCC State
TAS
NCC SPTC Current
Maximum floor areas
Building Classes
1b,1a,10a,10b,10c
NCC Blurbs
NCC Title
Required exits
NCC State
TAS
NCC SPTC Current
Required exits
Building Classes
1a,1b,10a,10b,10c
NCC Blurbs
The walls and floors of areas to be used for hand laminating and spray depositing must be constructed of non-combustible materials.
NCC Title
Hand laminating and spray depositing
NCC State
TAS
NCC SPTC Current
Hand laminating and spray depositing
Building Classes
1a,1b,10a,10b,10c
NCC Blurbs
- produce a negative pressure within any exhaust ducting within the work place so that a leak in the ducting will not vent exhaust air back in to the work place; and
- vent the exhaust air to the atmosphere so as to prevent recirculation of that exhaust air.
NCC Title
Ventilation
NCC State
TAS
NCC SPTC Current
Ventilation
Building Classes
1a,1b,10a,10b,10c
NCC Blurbs
Each fire-separated section must be provided with automatic smoke and heat roof vents.
NCC Title
Smoke and heat roof vents
NCC State
TAS
NCC SPTC Current
Smoke and heat roof vents
Building Classes
1a,1b,10a,10b,10c