TAS Table I12D4: Maximum floor area of buildings for manufacture or processing of glass reinforced plastics or isocyanates
Type A building construction
Type B building construction
Type C building construction
Not sprinklered: 1500 m2
Not sprinklered: 1200 m2
Not sprinklered: 1000 m2
Sprinklered: 6000 m2
Sprinklered: 5000 m2
Sprinklered: 3000 m2
NCC Title
Maximum floor areas
NCC State
TAS
NCC SPTC Current
Maximum floor areas
NCC ID
_a0b48e44-9dfd-4421-b4d2-af11649dd46e
Building Classes
1b,1a,10a,10b,10c
NCC Blurbs
(1) Each fire-separated section of a building which is a work place must have at least two exits for escape purposes and the number and location of exits must be such that any point on the floor is not further than 20 m from one of the exits.
(2) Only exits with vertically hinged swinging doors may be considered as exits for the purposes of this clause.
NCC Title
Required exits
NCC State
TAS
NCC SPTC Current
Required exits
NCC ID
_d71a9cd2-d7f8-46fe-9c55-29094b04e664
Building Classes
1a,1b,10a,10b,10c
NCC Blurbs
The walls and floors of areas to be used for hand laminating and spray depositing must be constructed of non-combustible materials.
NCC Title
Hand laminating and spray depositing
NCC State
TAS
NCC SPTC Current
Hand laminating and spray depositing
NCC ID
_0da9ca9a-609b-45ad-803b-8863bfe5c0e7
Building Classes
1a,1b,10a,10b,10c
NCC Blurbs
(1) Mechanical or natural ventilation must be via low-level, exhaust ducting in a wall and a fixed, open, floor-level, fresh-air inlet ducting in the opposite wall such as to ensure a cross flow of the ventilation over the complete working area.
(2) Mechanical ventilation must provide not less than 6 air changes per hour.
(3) The ventilation fan and exhaust ducting must be arranged in such a manner as to—
produce a negative pressure within any exhaust ducting within the work place so that a leak in the ducting will not vent exhaust air back in to the work place; and
vent the exhaust air to the atmosphere so as to prevent recirculation of that exhaust air.
NCC Title
Ventilation
NCC State
TAS
NCC SPTC Current
Ventilation
NCC ID
_646a2e49-f938-4615-b319-64074bc3813a
Building Classes
1a,1b,10a,10b,10c
NCC Blurbs
Each fire-separated section must be provided with automatic smoke and heat roof vents.