Part F7 Sound transmission and insulation
Introduction to this Part
This Part is intended to reduce the likelihood of illness or loss of amenity as result of undue noise transmission between different parts of a building or adjoining buildings. This Part contains minimum requirements for sound insulation for walls, floors and penetrations through walls and floors for services such as pipework.
Objectives
F7O1
Objective
FO5
The Objective of this Part is to safeguard occupants from illness or loss of amenity as a result of undue sound being transmitted—
- between adjoining sole-occupancy units; and
- from common spaces to sole-occupancy units; and
- from parts of different classifications to sole-occupancy units.
Applications
F7O1 only applies to a Class 2 or 3 building or a Class 9c building.
Functional Statements
F7F1
Sound transmission and insulation
2019: FF5.1
A part of a building that separates—
- sole-occupancy units; or
- a sole-occupancy unit from a part of another classification in the building; or
- a sole-occupancy unit from a common space,
is to be constructed to prevent undue sound transmission.
Applications
F7F1 only applies to a Class 2 or 3 building or a Class 9c building.
Performance Requirements
F7P1
Sound transmission through floors
2019: FP5.1
A floor separating sole-occupancy units or a sole-occupancy unit from a plant room, lift shaft, stairway, public corridor, public lobby, or the like, or parts of a different classification, must minimise the transmission of airborne and impact generated sound such that the separating floor, including the effect of services and their penetrations, has—
- a weighted standardised level difference with spectrum adaptation term (DnT,w + Ctr) not less than 45 for airborne sound; and
- a weighted standardised impact sound pressure level (LnT,w) not more than 62 for impact generated sound.
Applications
F7P1 only applies to a Class 2 or 3 building.
F7P2
Sound transmission through walls
2019: FP5.2
A wall, including services and their penetrations, must minimise the transmission of sound such that—
- for airborne sound—
- a wall separating sole-occupancy units has a weighted standardised level difference with spectrum adaptation term (DnT,w + Ctr) not less than 45; and
- a wall separating a sole-occupancy unit from a plant room, lift shaft, stairway, public corridor, public lobby, or the like, or parts of a different classification, has a weighted standardised level difference (DnT,w) not less than 45; and
- any door assembly located in a wall that separates a sole-occupancy unit from a stairway, public corridor, public lobby, or the like, has a weighted standardised level difference (DnT,w) not less than 25; and
- for impact generated sound, a wall must have sufficient sound insulation to prevent illness or loss of amenity to the occupants if the wall separates—
- a bathroom, sanitary compartment, laundry or kitchen in one sole-occupancy unit from a habitable room (other than a kitchen) in an adjoining sole-occupancy unit; or
- a sole-occupancy unit from a plant room or lift shaft.
Applications
F7P2 only applies to a Class 2 or 3 building.
F7P3
Sound transmission through floors in a residential care building
2019: FP5.4
A floor separating sole-occupancy units must minimise the transmission of airborne and impact generated sound such that the separating floor, including the effect of services and their penetrations, has—
- a weighted standardised level difference (DnT,w) not less than 40 for airborne sound; and
- a weighted standardised impact sound pressure level (LnT,w) not more than 62 for impact generated sound.
Applications
F7P3 only applies to a Class 9c building.
F7P4
Sound transmission through walls in a residential care building
2019: FP5.5
- airborne sound such that the wall has a weighted standardised level difference (DnT,w) not less than 40; and
- impact generated sound, if the wall separates a sole-occupancy unit from a kitchen or laundry.
Applications
F7P4 only applies to a Class 9c building.
Verification Methods
F7V1
Sound transmission through floors [F7P1]
2019: FV5.1
Compliance with F7P1 to avoid the transmission of airborne and impact generated sound through floors is verified when it is measured in-situ that the separating floor has—
- airborne: a weighted standardised level difference with spectrum adaptation term (DnT,w + Ctr) not less than 45 when determined under AS/NZS ISO 717.1; and
- impact: a weighted standardised impact sound pressure level (LnT,w) not more than 62 when determined under AS ISO 717.2.
F7V2
Sound transmission through walls [F7P2(a)]
2019: FV5.2
Compliance with F7P2(a) to avoid the transmission of airborne sound through walls is verified when it is measured in-situ that—
- a wall separating sole-occupancy units has a weighted standardised level difference with spectrum adaptation term (DnT,w + Ctr) not less than 45 when determined under AS/NZS ISO 717.1; or
- a wall separating a sole-occupancy unit from a plant room, lift shaft, stairway, public corridor, public lobby, or the like, or parts of a different classification, has a weighted standardised level difference (DnT,w) not less than 45 when determined under AS/NZS ISO 717.1; or
- any door assembly located in a wall that separates a sole-occupancy unit from a stairway, public corridor, public lobby, or the like, has a weighted standardised level difference (DnT,w) not less than 25 when determined under AS/NZS ISO 717.1.
F7V3
Sound transmission through floors [F7P3]
2019: FV5.3
Compliance with F7P3 to avoid the transmission of airborne and impact generated sound through floors is verified when it is measured in-situ that the separating floor has—
- airborne: a weighted standardised level difference (DnT,w) not less than 40 when determined under AS/NZS ISO 717.1; and
- impact: a weighted standardised impact sound pressure level (LnT,w) not more than 62 when determined under AS ISO 717.2.
F7V4
Sound transmission through walls [F7P4(1)(a) and (2)]
2019: FV5.4
Compliance with F7P4(1)(a) and (2) to avoid the transmission of airborne sound through walls is verified when it is measured in-situ that—
- a wall separating sole-occupancy units has a weighted standardised level difference (DnT,w) not less than 40 when determined under AS/NZS ISO 717.1; or
- a wall separating a sole-occupancy unit from a kitchen, bathroom, sanitary compartment (not being an associated ensuite), laundry, plant room or utilities room has a weighted standardised level difference (DnT,w) not less than 40 when determined under AS/NZS ISO 717.1.
Deemed-to-Satisfy Provisions
F7D1
Deemed-to-Satisfy Provisions
2019: F5.0
F7D2
Application of Part
2019: F5.1
The Deemed-to-Satisfy Provisions of this Part apply to Class 2 and 3 buildings and Class 9c buildings.
F7D3
Determination of airborne sound insulation ratings
2019: F5.2
A form of construction required to have an airborne sound insulation rating must—
- have the required value for weighted sound reduction index (Rw) or weighted sound reduction index with spectrum adaptation term (Rw + Ctr) determined in accordance with AS/NZS ISO 717.1 using results from laboratory measurements; or
- comply with Specification 28.
F7D4
Determination of impact sound insulation ratings
2019: F5.3
- have the required value for weighted normalised impact sound pressure level (Ln,w) determined in accordance with AS ISO 717.2 using results from laboratory measurements; or
- comply with Specification 28.
- for a Class 2 or 3 building be of discontinuous construction and
- for a Class 9c building, must—
- for other than masonry, be two or more separate leaves without rigid mechanical connection except at the periphery; or
- be identical with a prototype that is no less resistant to the transmission of impact sound when tested in accordance with Specification 29 than a wall listed in S28C4 to S28C7.
- for masonry, where wall ties are required to connect leaves, the ties are of the resilient type; and
- for other than masonry, there is no mechanical linkage between leaves except at the periphery.
F7D5
Sound insulation rating of floors
2019: F5.4
- sole-occupancy units; or
- a sole-occupancy unit from a plant room, lift shaft, stairway, public corridor, public lobby or the like, or parts of a different classification.
F7D6
Sound insulation rating of walls
2019: F5.5
- have an Rw + Ctr (airborne) not less than 50, if it separates sole-occupancy units; and
- have an Rw (airborne) not less than 50, if it separates a sole-occupancy unit from a plant room, lift shaft, stairway, public corridor, public lobby or the like, or parts of a different classification; and
- comply with F7D4(2) if it separates—
- a bathroom, sanitary compartment, laundry or kitchen in one sole-occupancy unit from a habitable room (other than a kitchen) in an adjoining unit; or
- a sole-occupancy unit from a plant room or lift shaft.
- sole-occupancy units; or
- a sole-occupancy unit from a kitchen, bathroom, sanitary compartment (not being an associated ensuite), laundry, plant room or utilities room.
F7D7
Sound insulation rating of internal services
2019: F5.6
- 40 if the adjacent room is a habitable room (other than a kitchen); or
- 25 if the adjacent room is a kitchen or non-habitable room.
F7D8
Sound isolation of pumps
2019: F5.7
A flexible coupling must be used at the point of connection between the service pipes in a building and any circulating or other pump.