Specification 7 Fire hazard properties
S7C1
Scope
2019: Spec C1.10: 1
This Specification sets out requirements in relation to the fire hazard properties of linings, materials and assemblies in Class 2 to 9 buildings as set out in Table S7C2.
S7C2
Application
2019: Spec C1.10: 2
Linings, materials and assemblies must comply with the appropriate requirement described in Table S7C2.
Lining, material or assembly | Requirement |
---|---|
Floor linings and floor coverings | S7C3 |
Wall linings and ceiling linings | S7C4 |
Air-handling ductwork | S7C5 |
Lift cars | S7C6 |
In fire control rooms subject to Specification 6 and fire isolated exits | S7C7 |
In Class 9b buildings used as a theatre, public hall or the like — fixed seating in the audience area or auditorium; and a proscenium curtain required by Specification 32 | S7C7 |
Escalators, moving walkways and non-required non-fire-isolated stairways or pedestrian ramps subject to Specification 14 | S7C7 |
Sarking-type material | S7C7 |
Attachments to internal floors, walls and ceilings | S7C7 |
Other materials including insulation | S7C7 |
S7C3
Floor linings and floor coverings
2019: Spec C1.10: 3
A floor lining or floor covering must have—
- a critical radiant flux not less than that listed in Table S7C3; and
- in a building not protected by a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17, a maximum smoke development rate of 750 percent-minutes; and
- a group number complying with S7C6(b), for any portion of the floor covering that is continued more than 150 mm up a wall.
Class of building | Building not fitted with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 | Building fitted with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 | Fire-isolated exits and fire control rooms |
---|---|---|---|
Class 2, 3, 5, 6, 7, 8 or 9b, excluding Class 3 accommodation for the aged and Class 9b as specified below | 2.2 kW/m2 | 1.2 kW/m2 | 2.2 kW/m2 |
Class 3 accommodation for the aged | 4.5 kW/m2 | 2.2 kW/m2 | 4.5 kW/m2 |
Class 9a patient care areas | 4.5 kW/m2 | 2.2 kW/m2 | 4.5 kW/m2 |
Class 9a areas other than patient care areas | 2.2 kW/m2 | 1.2 kW/m2 | 4.5 kW/m2 |
Class 9b auditorium or audience seating area used mainly for indoor swimming or ice skating | 1.2 kW/m2 | 1.2 kW/m2 | 2.2 kW/m2 |
Class 9b auditorium or audience seating area used mainly for other sports or multi-purpose functions | 2.2 kW/m2 | 1.2 kW/m2 | 2.2 kW/m2 |
Class 9c resident use area | N/A | 2.2 kW/m2 | 4.5 kW/m2 |
Class 9c areas other than resident use areas | N/A | 1.2 kW/m2 | 4.5 kW/m2 |
S7C4
Wall and ceiling linings
2019: Spec C1.10: 4
- a smoke growth rate index not more than 100; or
- an average specific extinction area less than 250 m2/kg.
Class of building | Fire-isolated exits and fire control rooms | Public corridors | Specific areas | Other areas |
---|---|---|---|---|
Class 2 or 3, unsprinklered, excluding accommodation for the aged, people with disabilities and children | Walls: 1 | Walls: 1, 2 | Walls: 1, 2, 3 | Walls: 1, 2, 3 |
Ceilings: 1 | Ceilings: 1, 2 | Ceilings: 1, 2, 3 | Ceilings: 1, 2, 3 | |
Class 2 or 3, sprinklered, excluding accommodation for the aged, people with disabilities and children | Walls: 1 | Walls: 1, 2, 3 | Walls: 1, 2, 3 | Walls: 1, 2, 3 |
Ceilings: 1 | Ceilings: 1, 2, 3 | Ceilings: 1, 2, 3 | Ceilings: 1, 2, 3 | |
Class 3 or 9a, unsprinklered, accommodation for the aged, people with a disability, children and health-care buildings | Walls: 1 | Walls: 1 | Walls: 1, 2 | Walls: 1, 2, 3 |
Ceilings: 1 | Ceilings: 1 | Ceilings: 1, 2 | Ceilings: 1, 2, 3 | |
Class 3 or 9a, sprinklered, accommodation for the aged, people with a disability, children and health-care buildings | Walls: 1 | Walls: 1, 2 | Walls: 1, 2, 3 | Walls: 1, 2, 3 |
Ceilings: 1 | Ceilings: 1, 2 | Ceilings: 1, 2, 3 | Ceilings: 1, 2, 3 | |
Class 5, 6, 7, 8 or 9b schools, unsprinklered | Walls: 1 | Walls: 1, 2 | Walls: 1, 2, 3 | Walls: 1, 2, 3 |
Ceilings: 1 | Ceilings: 1, 2 | Ceilings: 1, 2 | Ceilings: 1, 2, 3 | |
Class 5, 6, 7, 8 or 9b schools, sprinklered | Walls: 1 | Walls: 1, 2, 3 | Walls: 1, 2, 3 | Walls: 1, 2, 3 |
Ceilings: 1 | Ceilings: 1, 2, 3 | Ceilings: 1, 2, 3 | Ceilings: 1 ,2, 3 | |
Class 9b other than schools, unsprinklered | Walls: 1 | Walls: 1 | Walls: 1, 2 | Walls: 1, 2, 3 |
Ceilings: 1 | Ceilings: 1 | Ceilings: 1, 2 | Ceilings: 1, 2, 3 | |
Class 9b other than schools, sprinklered | Walls: 1 | Walls: 1, 2 | Walls: 1, 2, 3 | Walls: 1, 2, 3 |
Ceilings: 1 | Ceilings: 1, 2 | Ceilings: 1, 2, 3 | Ceilings: 1, 2, 3 | |
Class 9c, sprinklered | Walls: 1 | Walls: 1, 2 | Walls: 1, 2, 3 | Walls: 1, 2, 3 |
Ceilings: 1 | Ceilings: 1, 2 | Ceilings: 1, 2, 3 | Ceilings: 1, 2, 3 |
Table Notes
- ”Sprinklered” means a building fitted with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.
- ”Specific areas” means within—
- for Class 2 and 3 buildings, a sole-occupancy unit; and
- for Class 5 buildings, open plan offices with a minimum floor dimension/floor to ceiling height ratio > 5; and
- for Class 6 buildings, shops or other building with a minimum floor dimension/floor to ceiling height ratio > 5; and
- for Class 9a health-care buildings, patient care areas; and
- for Class 9b theatres and halls, etc, an auditorium; and
- for Class 9b schools, a classroom; and
- for Class 9c buildings, resident use area.
S7C5
Air-handling ductwork
2019: Spec C1.10: 5
Rigid and flexible ductwork in a Class 2 to 9 building must comply with the fire hazard properties set out in AS 4254.1 and AS 4254.2.
S7C6
Lift cars
2019: Spec C1.10: 6
Materials used as—
- floor linings and floor coverings must have a critical radiant flux not less than 2.2; and
- wall and ceiling linings must be a Group 1 material or a Group 2 material in accordance with AS 5637.1.
S7C7
Other materials
2019: Spec C1.10: 7
Materials and assemblies not included in S7C3, S7C4, S7C5 or S7C6 must not exceed the indices set out in Table S7C7.
Material or assembly location | Flammability Index | Spread-of-Flame Index | Smoke-Developed Index |
---|---|---|---|
Fire control rooms subject to Specification 19 and fire-isolated exits, other than a sarking-type material used in a ceiling or used as an attachment or part of an attachment to a building element. Note 1 | N/A | 0 | 2 |
Class 9b buildings used as a theatre, public hall or the like: Any part of fixed seating in the audience area or auditorium. | N/A | 0 | 5 |
Class 9b buildings used as a theatre, public hall or the like: A proscenium curtain required by Specification 32. | N/A | 0 | 3 |
Escalators, moving walkways or non-required non fire-isolated stairway or pedestrian ramps subject to Specification 14. | N/A | 0 | 5 |
Sarking-type materials: In a fire control room subject to Specification 19 or a fire-isolated exit or fire control room used in the form of an exposed wall or ceiling. | 0 | N/A | N/A |
Sarking-type materials: In other locations. Note 2 | 5 | N/A | N/A |
Other materials or locations and insulation materials other than sarking-type material. Notes 2 and 3 | N/A | 9 | 8 if the Spread-of-Flame Index is more than 5 |
Table Notes
- In a fire control room or fire-isolated stairway, a material used as an attachment or part of an attachment to a building element must, if combustible, be attached directly to a non-combustible substrate and not exceed 1 mm finished thickness.
- A material, other than one located within a fire-isolated exit or fire control room, may be covered on all faces by concrete or masonry not less than 50 mm thick, as an alternative to meeting the specified indices.
- In the case of a composite member or assembly, the member or assembly must be constructed so that when assembled as proposed in a building—
- any material which does not comply with this Table is protected on all sides and edges from exposure to the air; and
- the member or assembly, when tested in accordance with Specification 3, has Spread-of-Flame Index and Smoke-Developed Index not exceeding those prescribed in this Table; and
- the member or assembly retains the protection in position so that it prevents ignition of the material and continues to screen it from access to free air for a period of not less than 10 minutes.
Material or assembly location | Flammability Index | Spread-of-Flame Index | Smoke-Developed Index |
---|---|---|---|
Fire control rooms subject to Specification 19 and fire-isolated exits, other than a sarking-type material used in a ceiling or used as an attachment or part of an attachment to a building element. Note 1 | N/A | 0 | 2 |
Class 9b buildings used as an entertainment venue, a material used to cover closed back upholstered seats in any part available to the public—where smoking is permitted; or flame is exposed in connection with the preparation of meals Note 4 | N/A | 6 | 5 |
Class 9b buildings used as an entertainment venue, a material used as a curtain, blind or similar decor in any part available to the public. Notes 4 and 5 | 6 | N/A | N/A |
Class 9b buildings used as an entertainment venue, a material used to form a cinematograph screen. Notes 4, 5 and 6 | 12 | 0 | 7 |
Class 9b buildings used as a public hall or the like: A proscenium curtain required by Specification 32. | N/A | 0 | 3 |
Escalators, moving walkways or non-required non fire-isolated stairways or pedestrian ramps subject to Specification 14. | N/A | 0 | 5 |
Sarking-type materials: In a fire control room subject to Specification 19 or a fire-isolated exit used in the form of an exposed wall or ceiling. | 0 | N/A | N/A |
Sarking-type materials other than in a fire control room subject to Specification 19 or a fire-isolated exit used in the form of an exposed wall or ceiling. Note 2 | 5 | N/A | N/A |
Other materials or locations and insulation materials other than Sarking-type materials. Notes 2 and 3 | N/A | 9 | 8 if the Spread-of-Flame Index is more than 5 |
Note
- In a fire control room or fire-isolated stairway, a material used as an attachment or part of an attachment to a building element must, if combustible, be attached directly to a non-combustible substrate and not exceed 1 mm finished thickness.
- A material, other than one located within a fire-isolated exit or fire control room, may be covered on all faces by concrete or masonry not less than 50 mm thick, as an alternative to meeting the specified indices.
- In the case of a composite member or assembly, the member or assembly must be constructed so that when assembled as proposed in a building—
- any material which does not comply with this Table is protected on all sides and edges from exposure to the air; and
- the member or assembly, when tested in accordance with Specification 3, has a Spread-of-Flame Index and Smoke-Developed Index not exceeding those prescribed in this Table; and
- the member or assembly retains the protection in position so that it prevents ignition of the material and continues to screen it from access to free air for a period of not less than 10 minutes.
- Any fire-retardant coating used in an entertainment venue to make a material comply with a required Flammability Index, Spread-of-Flame Index or Smoke-Developed Index must be certified by—
- its manufacturer or distributor—
- as approved for use with the fabric to achieve the required indices; and
- to retain its retardancy effect after a minimum of 5 commercial dry cleaning or laundering operations carried out in accordance with AS 2001.5.4, Procedure 7A, using non-phosphate ECE reference detergent A (without optical brightener); and
- the applicator as having been carried out in accordance with the manufacturer’s specification.
- its manufacturer or distributor—
- Materials used in an entertainment venue must have a label affixed to a representative sample of each different material indicating, in legible characters—
- name of manufacturer; and
- trade name and description of material’s composition; and
- retardant treatment (if any), name of applicator and date of application; and
- AS 1530 Part 2 and/or AS/NZS 1530 Part 3 test number and its Flammability Index, Spread-of-Flame Index and Smoke-Developed Index; and
- approved methods of cleaning.
- A cinematograph screen must have a supporting frame of metal construction.