NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings

D3

Part D3 Construction of exits

Part D3 Construction of exits

VIC D3D26 Operation of latch2019: D2.21

Insert VIC subclause D3D26(6) in clause D3D26 as follows:

(6) For the purposes of (1), an exit door from a children’s service which does not open to an outdoor space enclosed in accordance with G1D4, must have the device located between 1.5 m and 1.65 m above the floor and the door must be self-closing.