Part F8 Condensation management
Introduction to this Part
This Part is intended to reduce the risk of illness or loss of amenity due to the occurrence of condensation inside a building. It does this by requiring features that enable moisture-laden air to be removed from inside the building and the building structure.
Notes
From 1 May 2023 to 30 September 2023 Part F6 of NCC 2019 Volume One Amendment 1 may apply instead of Part F8 of NCC 2022 Volume One. From 1 October 2023 Part F8 of NCC 2022 Volume One applies.
Objectives
F8O1
Objective
2019: FO6
The Objective of this Part is to safeguard occupants from illness or loss of amenity as a result of excessive internal moisture.
Applications
F8O1 only applies to a sole-occupancy unit of a Class 2 building or Class 4 part of a building.
Functional Statements
F8F1
Condensation
2019: FF6.1
A building is to be constructed to avoid the likelihood of excessive internal moisture accumulating within the building structure.
Applications
F8F1 only applies to a sole-occupancy unit of a Class 2 building or Class 4 part of a building.
Performance Requirements
F8P1
Condensation and water vapour management
2019: FP6.1
In a sole-occupancy unit of a Class 2 building or a Class 4 part of a building, risks associated with water vapour and condensation must be managed to minimise their impact on the health of occupants.
Notes
- Refer to the guidance in the “Condensation in Buildings Tasmanian Designers’ Guide” – current version available at www.cbos.tas.gov.au. This Guide must be read in conjunction with the NCC.
- The strategies listed in the Guide exceed the NCC requirements for condensation management, however are strongly recommended to assist in minimising condensation in cool climates like Tasmania.
Condensation and water vapour management
Risks associated with water vapour and condensation must be managed to minimise their impact on the health of occupants.
Applications
F8P1 only applies to a sole-occupancy unit of a Class 2 building or Class 4 part of a building.
Verification Methods
F8V1
Condensation management
2019: FV6
- the interior surface of the water control layer; or
- the surfaces of building fabric components interior to the water control layer.
- input assumptions in accordance with AIRAH DA07; and
- the intermediate method for calculating indoor design humidity in Section 4.3.2 of AIRAH DA07.
Deemed-to-Satisfy Provisions
F8D1
Deemed-to-Satisfy Provisions
2019: F6.0
Explanatory information
The intent of these requirements is to assist in the mitigation of condensation within a building. The implementation of a condensation management strategy may not prevent condensation from occurring.
F8D2
Application of Part
2019: F6.1
The Deemed-to-Satisfy Provisions of this Part only apply to a sole-occupancy unit of a Class 2 building and a Class 4 part of a building.
F8D3
External wall construction
2019: F6.2
- comply with AS 4200.1; and
- be installed in accordance with AS 4200.2; and
- be located on the exterior side of the primary insulation layer of wall assemblies that form the external envelope of a building.
- in climate zones 4 and 5, 0.143 µg/N.s; and
- in climate zones 6, 7 and 8, 1.14 µg/N.s.
Explanatory information
F8D3(2) requires some wall materials on the external side of the primary insulation layer to have a minimum level of vapour permeance. Vapour permeance is measured in µg/N.s (micrograms per newton-second).
Class 3 and 4 vapour control membranes (as defined by clause 5.3.4 of AS 4200.1) meet the vapour permeance requirements of F8D3(2)(a), while Class 4 vapour control membranes meet the vapour permeance requirements of F8D3(2)(b).
Open-cell insulation, such as mineral wool or fibreglass, typically has a high vapour permeance, while closed-cell insulation such as polystyrene typically has a low vapour permeance. Many foil-faced insulation products have a low vapour permeance.
F8D4
Exhaust systems
2019: F6.3
- 25 L/s for a bathroom or sanitary compartment; and
- 40 L/s for a kitchen or laundry.
- be interlocked with the room’s light switch; and
- include a run-on timer so that the exhaust system continues to operate for 10 minutes after the light switch is turned off.
Explanatory information
A range hood installed in a kitchen must comply with F8D4(2).
Part F6 includes other ventilation requirements which must be met, including a requirement for make-up air to be provided to mechanically ventilated rooms in accordance with AS 1668.2.
F8D5
Ventilation of roof spaces
2019: F6.4
- is located—
- immediately above the primary insulation layer; or
- immediately above sarking with a vapour permeance of not less than 1.14 μg/N.s, which is immediately above the primary insulation layer; or
- immediately above ceiling insulation which meets the requirements of J3D7(3) and J3D7(4); and
- has a height of not less than 20 mm; and
- is either—
- ventilated to outdoor air through evenly distributed openings in accordance with Table F8D5; or
- located immediately underneath roof tiles of an unsarked tiled roof.
- concrete roof; or
- roof that is made of structural insulated panels; or
- roof that is subject to Bushfire Attack Level FZ requirements in accordance with AS 3959.
Roof pitch | Ventilation openings |
---|---|
<10° | 25,000 mm2/m provided at each of two opposing ends |
≥10° and <15° | 25,000 mm2/m provided at the eaves and 5,000 mm2/m at high level |
≥15° and <75° | 7,000 mm2/m provided at the eaves and 5,000 mm2/m at high level, plus an additional 18,000 mm2/m at the eaves if the roof has a cathedral ceiling |
Table Notes
- Ventilation openings are specified as a minimum free open area per metre length of the longest horizontal dimension of the roof.
- For the purposes of this table, high level openings are openings provided at the ridge or not more than 900 mm below the ridge or highest point of the roof space, measured vertically.