Specification 27 Accessible adult change facilities
S27C1
Scope
2019: Spec F2.9: 1
This Specification contains the requirements for accessible adult change facilities.
S27C2
General requirements
2019: Spec F2.9: 2
- be constructed so that all required equipment and fixtures are contained within the same room; and
- if it is a unisex facility, be located such that it can be entered without crossing an area reserved for one sex only.
- A hoist complying with S27C3.
- A toilet pan, seat, backrest and grabrails complying with S27C4.
- A washbasin and tap complying with S27C5.
- Fixtures and fittings as specified in S27C6.
- A change table complying with S27C7.
- Changing rails complying with S27C8.
- An automated sliding entrance door complying with S27C9.
- Signage complying with S27C10.
- Operating instructions for the hoist and change table in accordance with S27C11.
- Circulation spaces complying with Figures S27C2a, S27C2b and S27C2c.
- The Roman numerals shown in Figures S27C2a, S27C2b and S27C2c indicate the following required circulation spaces:
- Turning space: a full circle of 1125 mm radius.
- Each side of the pan: 900 mm (measured from each edge of the pan).
- In front of the pan: 2350 mm (measured from the wall behind the pan, and therefore includes the pan itself).
- For a washbasin: the width of the basin (450 mm) increasing to a width of 1350 mm measured at a distance of 750 mm out from the wall against which the washbasin is mounted then continuing at that width for a further 800 mm (to a total of 1550 mm out from the wall).
- For changing rails: the width of the rails increasing to a width of 1350 mm at a distance of 750 mm out from the wall to which the rails are fixed then continuing at that width for a further 800 mm (to a total of 1550 mm out from the wall).
- All required circulation spaces must extend for a minimum height of 2000 mm above finished floor level.
- Required circulation spaces may be overlapped.
S27C3
Hoist
2019: Spec F2.9: 3
The hoist must—
- provide a constant charge in-line room coverage hoist system (also known as an “XY” system or gantry) including 2 parallel fixed rails and a moving traverse rail; and
- provide coverage over the entire room; and
- have a maximum safe working load of not less than 180 kg; and
- be capable of sustaining a static load of not less than 1.5 times the rated load; and
- have a minimum lifting height of 2100 mm.
S27C4
Toilet pan, seat, backrest and grabrails
2019: Spec F2.9: 4
- the front edge of the pan is 800 mm (±10 mm) from the rear wall; and
- the top of the seat is between 460 mm and 480 mm above finished floor level; and
- there is a minimum clearance of 900 mm, measured horizontally, between each side of the pan and any adjacent wall or privacy screen.
- be of the full-round type (not open-fronted) with minimal contours to the top surface; and
- be securely fixed in position when in use; and
- have seat fixings that provide lateral stability to the seat when the seat is in use; and
- be load-rated to 150 kg; and
- have a minimum luminance contrast of 30% against the pan, wall or floor; and
- remain in the fully upright position when raised.
- be located on the centreline of the toilet, at a height above finished floor level of—
- not less than 600 mm; and
- not more than 1100 mm; and
- not be located within the area required for any grabrails or backrest; and
- have the button mounted so that it is proud of the wall surface, and activates the flushing operation before the button becomes level with the surrounding surface.
- be capable of withstanding a force, in any direction, of not less than 1100 N; and
- have a minimum height, between the lower edge of the backrest and the top of the seat, of between 120 mm and 150 mm; and
- have a vertical height, between the upper and lower edges of the backrest, of between 150 mm and 200 mm; and
- have a width of between 350 mm and 400 mm; and
- be positioned such that the face of the backrest achieves an angle of between 95° and 100° back from the seat, when the seat is in use.
- of the drop-down type; and
- located such that—
- the top of each rail is between 800 mm and 810 mm above finished floor level; and
- the rails are between 750 mm and 770 mm apart, measured centre-to-centre, and equidistant to the centreline of the pan; and
- at least 850 mm long; and
- with a diameter of between 30 mm and 40 mm; and
- securely fixed to withstand a force, in any direction, of not less than 1100 N; and
- provided with a toilet paper dispenser on one side; and
- capable of being lifted up or swung away when not in use, so as to allow unimpeded access to the toilet pan.
S27C5
Washbasin and tap
2019: Spec F2.9: 5
S27C6
Fixtures and fittings
2019: Spec F2.9: 6
- is not less than 600 mm wide; and
- has its bottom edge not more than 900 mm above finished floor level; and
- has its top edge not less than 1850 mm above finished floor level.
- is not less than 600 mm wide; and
- has its bottom edge not less than 600 mm above finished floor level; and
- has its top edge not less than 1850 mm above finished floor level.
- between 900 mm and 1100 mm above finished floor level; and
- not less than 500 mm from any internal corner.
- at a height of between 1200 mm and 1350 mm above finished floor level; and
- adjacent to the washbasin; and
- not less than 500 mm from any internal corner.
- A sanitary disposal bin in the corner adjacent to the toilet pan.
- An incontinence pad disposal bin in the corner adjacent to the change table.
Explanatory information
The purpose of the sling hook is to store the sling when it is not in use.
S27C7
Change table
2019: Spec F2.9: 7
- permanently installed, with one of the long edges up against a wall and with a retractable safety rail on the opposite side; and
- motorised for the purposes of height adjustment; and
- height adjustable between 450 mm and 900 mm above finished floor level; and
- not less than 700 mm wide; and
- not less than 1800 mm long.
S27C8
Changing rails
2019: Spec F2.9: 8
Changing rails must be installed as two horizontal and parallel rails fixed to a wall, not less than 800 mm long, each with a diameter between 30 mm and 40 mm, and—
- the lower rail must be installed between 800 mm and 810 mm above finished floor level; and
- the upper rail must be installed between 1000 mm and 1010 mm above finished floor level; and
- the rails must be able to withstand a force of not less than 1100 N in any direction.
S27C9
Door and door controls
2019: Spec F2.9: 9
The entrance door and associated door controls must be automated and must comply with the following:
- The threshold must incorporate a smooth transition without a step or lip.
- The minimum clear opening width must be—
- 1100 mm in locations where beach wheelchairs are likely to be used; or
- 950 mm in all other locations.
- The doorway must achieve a luminance contrast of at least 30% between—
- door leaf and door jamb; or
- door leaf and adjacent wall; or
- architraves (where used) and adjacent wall; or
- door leaf and architrave (where used); or
- door jamb and adjacent wall.
- The operation of the door must be calibrated such that—
- it has a gentle opening and closing movement; and
- there is sufficient dwell time for a user to safely travel through the doorway.
- The door must be fitted with a fail-safe opening mechanism that opens the door if an obstruction is detected during its closing movement.
- Door controls must be located internally and externally—
- between 900 mm and 1200 mm above finished floor level; and
- not less than 500 mm from any internal corner.
- Door control buttons must—
- have a minimum diameter of 25 mm; and
- be proud of the surrounding surface; and
- activate the door operation before the button becomes level with the surrounding surface; and
- be of a contrasting colour to the surrounding plate.
- The surrounding plates of both internal and external door controls must include the words “Push to Open”.
- The following indicator lights must be provided:
- “Occupied” and “Vacant” on the external plate.
- “Locked” and “Unlocked” on the internal plate.
- Braille and tactile signage complying with Specification 15 must identify the door controls.
S27C10
Signage
2019: Spec F2.9: 10
- the symbol shown in Figure S27C10; and
- the words “Accessible Adult Change Facility”.
S27C11
Operating instructions
2019: Spec F2.9: 11
Signage provided within the facility must include the following information for the hoist and change table:
- Operating instructions.
- Safe working load limits.