Part C2 Fire resistance and stability
NSW C2D11 Fire hazard properties2019: C1.10 and NSW C1.10
Delete clause C2D11 and insert NSW C2D11 as follows:
- Floor linings and floor coverings.
- Wall linings and ceiling linings.
- Air-handling ductwork.
- Lift cars.
- In Class 9b buildings used as—
- an entertainment venue, a material used to cover closed back upholstered seats; and
- a public hall or the like, a proscenium curtain required by Specification 32.
- Escalators, moving walkways and non-required non fire-isolated stairways or pedestrian ramps subject to Specification 14.
- Sarking-type materials.
- Attachments to floors, ceilings, internal walls, common walls, fire walls and to internal linings of external walls.
- Other materials including insulation materials other than sarking-type materials.
- plaster, cement render, concrete, terrazzo, ceramic tile or the like; or
- a fire-protective covering; or
- a timber-framed window; or
- a solid timber handrail or skirting; or
- a timber-faced door; or
- an electrical switch, socket-outlet, cover plate or the like; or
- a material used for—
- a roof insulating material applied in continuous contact with a substrate; or
- an adhesive; or
- a damp-proof course, flashing, caulking, sealing, ground moisture barrier, or the like; or
- a paint, varnish, lacquer or similar finish, other than nitro-cellulose lacquer; or
- a clear or translucent roof light of glass fibre-reinforced polyester if—
- the roof in which it is installed forms part of a single storey building required to be Type C construction; and
- the material is used as part of the roof covering; and
- it is not closer than 1.5 m from another roof light of the same type; and
- each roof light is not more than 14 m2 in area; and
- the area of the roof lights per 70 m2 of roof surface is not more than 14 m2; or
- a face plate or neck adaptor of supply and return air outlets of an air handling system; or
- a face plate or diffuser plate of light fitting and emergency exit signs and associated electrical wiring and electrical components; or
- a joinery unit, cupboard, shelving, or the like; or
- an attached non-building fixture and fitting such as—
- a curtain, blind, or similar decor, other than—
- a proscenium curtain required by Specification 32; or
- in a Class 9b building used as an entertainment venue, a material regulated under NSW Table S7C7; and
- a whiteboard, window treatment or the like; or
- a curtain, blind, or similar decor, other than—
- timber treads, risers, landings and associated supporting framework installed in accordance with D3D30 where the Spread-of-Flame Index and the Smoke-Developed Index of the timber does not exceed 9 and 8 respectively; or
- any other material that does not significantly increase the hazards of fire.