NCC 2022 Volume One - Building Code of Australia Class 2 to 9 buildings

E1

Part E1 Fire fighting equipment

Part E1 Fire fighting equipment

NT E1D10 Where sprinklers are required: Class 9a and 9c buildings2019: NT Table E1.5

Delete clause E1D10 and insert NT E1D10 as follows:

(1) In a Class 9a health-care building used as a residential care building, sprinklers are required throughout the building and in any fire compartment containing a Class 9a part used for residential care.

(2) In a Class 9a building, other than as described in (1), sprinklers are required if the building has more than one storey.

(3)  In a Class 9c building, sprinklers are required throughout the building and in any fire compartment containing a Class 9c part.