Specification J1.6 Sub-floor thermal performance

Specification J1.6 Sub-floor thermal performance

1. Scope

This Specification describes the thermal performance of sub-floor spaces and soil in direct contact with a floor for the purposes of calculating the Total R-Value of a floor.
Intent

To provide the R-Values considered to be achieved by sub-floor spaces and soil in direct contact with a floor.

The R-Values provided are intended to assist in determining whether and how much additional insulation is required to achieve the minimum Total R-Values in Table J1.6. This is provided as an alternative to carrying out a more detailed calculation using Section 3.5 of CIBSE Guide A.

2. Sub-floor thermal performance

(a)

Table 2a details the R-Values considered to be achieved by enclosed sub-floor spaces that are—

(i)

mechanically ventilated by not more than 1.5 air changes per hour; or

(ii)

provided with not more than 150% of the aggregate sub-floor ventilation area required by Part F1 and are not mechanically ventilated.

Table 2a R-Value of sub-floor spaces
Ratio of floor area to floor perimeter (m) Sub-floor space R-Value
1.0 0.10
1.5 0.15
2.0 0.20
2.5 0.25
3.0 0.30
3.5 0.35
4.0 0.40
4.5 0.45
5.0 0.50
5.5 0.55
6.0 0.60
6.5 0.65
7.0 0.70

Note to Table 2a

Note to Table 2aWhere the ratio of floor area to floor perimeter is between the values stated, interpolation may be used to determine the sub-floor space R-Values.

(b)

Table 2b details the R-Values considered to be achieved by the soil for floors that are in direct contact with the ground.

Table 2b R-Value of soil in contact with a floor
Ratio of floor area to floor perimeter (m) Wall thickness of 50 mm Wall thickness of 100 mm Wall thickness of 150 mm Wall thickness of 200 mm Wall thickness of 250 mm Wall thickness of 300 mm
1.0 0.4 0.5 0.5 0.6 0.7 0.8
1.5 0.6 0.7 0.7 0.8 0.9 1.0
2.0 0.7

0.8

0.9 1.0 1.1 1.3
2.5 0.9 1.0 1.1 1.2 1.3 1.5
3.0 1.0 1.2 1.3 1.4 1.5 1.7
3.5 1.2 1.3 1.5 1.6 1.7 1.9
4.0 1.3 1.5 1.6 1.7 1.9 2.2
4.5 1.5 1.7 1.8 1.9 2.1 2.4
5.0 1.6 1.8 2.0 2.1 2.3 2.6
5.5 1.8 2.0 2.1 2.2 2.4 2.8
6.0 1.9 2.1 2.3 2.4 2.6 2.9
6.5 2.0 2.3 2.4 2.6 2.8 3.1
7.0 2.2 2.4 2.6 2.7 3.0 3.3

Note to Table 2b

Note to Table 2bWhere a wall thickness or ratio of floor area to floor perimeter is between the values stated, interpolation may be used to determine the soil R-Value.

Intent

To detail the thermal performance achieved by sub-floor spaces and soil in direct contact with a floor.