Section H Special use buildings

Section H Special use buildings

Part H1 Class 9b buildings

Delete H1.1 and insert NSW H1.1 as follows:

NSW H1.1 Application of Part

(a)

For a Class 9b building or part of a building that is not an entertainment venue

(i)

The Deemed-to-Satisfy Provisions of Part H1 apply to every enclosed Class 9b building or part of a building which—

(A)

is a school assembly, church or community hall with a stage and any backstage area with a total floor area of more than 300m2; or

(B)

otherwise, has a stage and any backstage area with a total floor area of more than 200m2; or

(C)

has a stage with an associated rigging loft.

(ii)

Notwithstanding (a)(i)

(A)

H1.4 applies to every open or enclosed Class 9b building; and

(B)

H1.7 applies to every enclosed Class 9b building.

(b)

For a Class 9b building that is an entertainment venue, NSW Part H101, as follows, applies in replacement of Part H1: