NCC 2019 Volume One
Search the National Construction Code editions
Part C1 Fire resistance and stability
Where a Deemed-to-Satisfy Solution is proposed, Performance RequirementsCP1 to CP9 are satisfied by complying with—
C1.1 to C1.14, C2.1 to C2.14 and C3.1 to C3.17; and
for a building containing an occupiable outdoor area, Part G6; and
for additional requirement for Class 9b buildings, Part H1; and
for farm sheds, Part H3.
Where a Performance Solution is proposed, the relevant Performance Requirements must be determined in accordance with A2.2(3) and A2.4(3) as applicable.
To clarify that the requirements of CP1 to CP9 will be satisfied if a building complies with Parts C1, C2 and C3, and Parts G3and G6, H1 and H3, if applicable.
Where a solution is proposed to comply with the Deemed-to-Satisfy Provisions, C1.0 clarifies that for most buildings compliance with Parts C1, C2 and C3 will achieve compliance with CP1 to CP9. The exceptions to this general rule are as follows:
Where a Performance Solution is proposed, the relevant Performance Requirements must be determined in accordance with A2.2(3) and A2.4(3) as applicable. (See commentary on Part A2).
The minimum Type of fire-resisting construction of a building must be determined in accordance with Table C1.1, except as allowed for—
certain Class 2, 3 or 9c buildings in C1.5; and
open spectator stands and indoor sports stadiums in C1.7.
SA C1.1(a)(iv) and (v)
Each building element must comply with Specification C1.1 as applicable.
Rise in storeys |
Class of building 2, 3, 9 |
Class of building 5, 6, 7, 8 |
---|---|---|
4 or more | A | A |
3 | A | B |
2 | B | C |
1 | C | C |
SA C1.1(c) and (d)
To establish the minimum fire-resisting construction required for Class 2–9 buildings.
C1.1(a) sets out the minimum type of fire-resisting construction required by the Deemed-to-Satisfy Provisions for all Class 2–9 buildings.
Type A construction is the most fire-resistant type of construction, Type C construction is the least fire-resistant and Type B construction falls between these two.
C1.1(b) requires building elements to comply with Specification C1.1 for the appropriate type of construction.
Table C1.1 explains that the required type of construction of a building depends on risk levels as indicated by the Class of building and the building’s height as indicated by the rise in storeys. Note that there could be other factors that need to be considered. For example, C2.2 and Table C2.2 examine the maximum permissible size of fire compartments or atriums in buildings for specific types of construction.
The Class of building is a measure of the building’s likely:
Research indicates that if a fire occurs while a person is asleep, the smell of the smoke will not wake them. Response times in residential buildings are longer than in other types of buildings. The BCA thus requires a higher type of construction in residential buildings. See Table C1.1.
The height (rise in storeys) of the building is relevant as a measure of likely evacuation times and evacuation difficulty.
When using a Performance Solution, Part C1 does not apply and there is no need to refer to the types of construction. Nonetheless, if building proponents using Performance Solutions wish to use Part C1 as part of the solution, they can.
The rise in storeys is the sum of the greatest number of storeys at any part of the external walls of the building and any storeys within the roof space—
above the finished ground next to that part; or
if part of the external wall is on the boundary of the allotment, above the natural ground level at the relevant part of the boundary.
A storey is not counted if—
it is situated at the top of the building and contains only heating, ventilating or lift equipment, water tanks, or similar service units or equipment; or
it is situated partly below the finished ground and the underside of the ceiling is not more than 1 m above the average finished level of the ground at the external wall, or if the external wall is more than 12 m long, the average for the 12 m part where the ground is lowest.
For the purposes of calculating the rise in storeys of a building—
a mezzanine is regarded as a storey in that part of the building in which it is situated if its floor area is more than 200 m2 or more than 1/3 of the floor area of the room, whichever is the lesser; and
two or more mezzanines are regarded as a storey in that part of the building in which they are situated if they are at or near the same level and have an aggregate floor area more than 200 m2 or more than 1/3 of the floor area of the room, whichever is the lesser.
To establish a method for the calculation of the rise in storeys of a building, as a means of helping determine a building’s required type of construction.
Under C1.2(a), the rise in storeys is the sum of the greatest number of storeys at any part of the external walls of a building above ground level and any storeys within the roof space. The reason for the inclusion of any storey within the roof space is that the storey may not have any external walls such as occur with a hip roof.
C1.2(a)(i) and (ii) distinguish between the situation where the part of the external walls is within the allotment (in which case it is calculated above finished ground level—C1.2(a)(i)), or on the allotment boundary (in which case it is calculated above natural ground level at that point—C1.2(a)(ii)).
The rise in storeys is the criteria used to determine the type of construction. This is because the rise in storeys has an impact on:
“Storey” is defined in Schedule 3. It is advisable to refer to this definition before calculating the rise in storeys of a building.
The calculation of the rise in storeys includes larger mezzanines (see C1.2(d)(i)) and situations where two or more mezzanines can create a similar impact to larger mezzanines (see C1.2(d)(ii)) because of their potential fire load.
The calculation excludes machinery or similar plant rooms at the top of the building because they do not add significantly to the building’s fire load (see C1.2(b)(i)) and storeys below ground level in particular circumstances outlined in Figure C1.2(1). This is because basements are not exposed to radiant heat from a fire in another building, nor do they emit any significant heat horizontally.
C1.2(b)(ii) describes when storeys partly below ground level are not included in the calculation of the rise in storeys, i.e. when they are treated as basement storeys as described above. Whether a storey is to be excluded from the calculation of the rise in storeys is determined by measuring the extent of the storey above the average ground level at the external wall. If the wall is more than 12 m long, consider only the 12 m length of the wall where the average ground level is lowest. If any wall of a storey is more than 1 m above the average ground level, the storey is included in the calculation of the rise in storeys.
The height of a ceiling in a storey above the average ground level adjacent to the external wall can be determined by calculating the area between the ground level and the ceiling for the length of the wall under consideration (the actual length of the wall or 12 metres, whichever is the lesser) and dividing the area obtained by that length (see Figure C1.2(3)).
Under C1.2(c), a Class 7 or Class 8 building with more than one storey above ground level (see C1.2(c)(i)) and which has an internal storey height of 6 metres or more is, from the point of view of potential fire load, considered to be the equivalent to 2 storeys (see C1.2(c)(ii)).
Figure C1.2(2) illustrates some examples of calculating the rise in storeys of a building.
Note: if the wall is more than 12 m long, consider only the 12 m length of the wall where the average finished ground level is lowest (see Figure C1.2(1)).
In a building of multiple classifications, the Type of construction required for the building is the most fire-resisting Type resulting from the application of Table C1.1 on the basis that the classification applying to the top storey applies to all storeys.
To establish the type of construction required for a building that contains more than one Class.
In a building comprising multiple classifications, the type of construction applicable to the classification of the top storey applies to all the storeys below it. Figure C1.3(1) illustrates this. This method is used to determine the type of construction only, and not the FRLs required for the different classifications.
To determine the type of construction required when a Class 4 part of a building occupies the whole of the top storey, the class of the next highest storey must be applied to the top storey (see C1.3(b)(i)). When a Class 4 part of a building occupies only part of the top storey, the required type of construction is determined by the class of the other part of the top storey (see C1.3(b)(ii)).
C1.6 must be used to determine the appropriate FRLs for the building elements in the Class 4 part of the building.
In a 3 storey building with the lower 2 storeys of Class 5 and the top storey entirely of Class 4 the Class 5 classification would be applied to the top storey as shown in Figure C1.3(2). Thus the required type of construction by the use of Table C1.1 would be at least Type B construction.
A building may be of mixed Types of construction where it is separated in accordance with C2.7 and the Type of construction is determined in accordance with C1.1 or C1.3.
To specify the circumstances in which a building may be of more than one type of construction.
The only circumstance in which the Deemed-to-Satisfy Provisions allow a building to be of different types of construction is when the types are separated from one another by a fire wall as described in C2.7(b).
In no case do the Deemed-to-Satisfy Provisions allow different types of construction to be above one another.
A building having a rise in storeys of 2 may be of Type C construction if—
it is a Class 2 or 3 building or a mixture of these classes and each sole-occupancy unit has—
access to at least 2 exits; or
its own direct access to a road or open space; or
it is a Class 9c building protected throughout with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification E1.5 and complies with the maximum compartment size specified in Table C2.2 for Type C construction.
To grant concessions for:
The concession for Class 2 and Class 3 buildings is made on the basis that the level of risk to occupants does not warrant the full application of the type of construction requirements.
The circumstances outlined in C1.5(a) and (b) are alternative options. They do not have to both exist to bring the C1.5 concession into operation.
The concession also applies to a building containing a mixture of Class 2 and Class 3.
Figure C1.5 illustrates an example of the use of the concession allowed by C1.5.
The concession for Class 9c buildings recognises the benefits of sprinkler systems and differences between Types A, B and C construction. It must be remembered that the Class 9c building must comply with all the other BCA provisions, including the floor area limitations contained in Table C2.2.
For the Type of construction required by C1.3, a Class 4 part of a building requires the same FRL for building elements and the same construction separating the Class 4 part from the remainder of the building as a Class 2 part in the same Type of construction.
To specify that Class 4 parts of buildings are subject to the same requirements for fire-resistance levels (FRLs) and separation as would apply to Class 2 parts in similar circumstances.
The reason for requiring the same FRL for a Class 4 as a Class 2 building is because the two different classifications have similar fire loads. It should be noted that the Type of construction required for a Class 4 part is determined in accordance with C1.3.
In a building fire, the people most at risk include those who are sleeping. It is therefore important that the residential part of the building be fire separated from the other parts. The fire-resistance levels (FRLs) required for structural elements in a Class 4 part of a building are identified in Tables 3, 4 or 5 of Specification C1.1.
An open spectator stand or indoor sports stadium may be of Type C construction and need not comply with the other provisions of this Part if it contains not more than 1 tier of seating, is of non-combustible construction, and has only changing rooms, sanitary facilities or the like below the tiered seating.
In (a), one tier of seating means numerous rows of tiered seating incorporating cross-overs but within one viewing level.
To grant a concession for open spectator stands and indoor sports stadiums.
Under specified circumstances (see C1.7(a)), an indoor sports stadium may be of Type C construction.
The reason for this concession is that although an indoor sports stadium may have a high population, particularly during an event, it generally has a lower fire load than other Class 9b buildings. For example, in most stadiums:
Under specified circumstances (see C1.7(a)), an open spectator stand may be of Type C construction. The reason for this concession is that an open spectator stand generally has a low fire load, even though it may have a high population, particularly during an event; and is open at the front thereby not allowing the build up of smoke and heat.
C1.7(b) refers to a “tier of seating”. This describes the levels of seating in an open spectator stand. Figure C1.7 illustrates a single tiered open spectator stand, and a two tiered open spectator stand.
Lightweight construction must comply with Specification C1.8 if it is used in a wall system—
that is required to have an FRL; or
for a lift shaft, stair shaft or service shaft or an external wall bounding a public corridor including a non fire-isolated passageway or non fire-isolated ramp, in a spectator stand, sports stadium, cinema or theatre, railway station, bus station or airport terminal.
If lightweight construction is used for the fire-resisting covering of a steel column or the like, and if—
the covering is not in continuous contact with the column, then the void must be filled solid, to a height of not less than 1.2 m above the floor to prevent indenting; and
the column is liable to be damaged from the movement of vehicles, materials or equipment, then the covering must be protected by steel or other suitable material.
To specify the requirements for the use of lightweight construction in:
Refer to Schedule 3 for the definition of “lightweight construction”.
Lightweight construction needs protection to preserve its integrity from mechanical damage in a fire or other situation where it may be particularly subject to risk of damage. This is because it is generally more susceptible to damage than other forms of wall construction, such as concrete (which does not contain soft materials) and masonry thicker than 70 mm.
To make sure lightweight construction performs correctly, C1.8 states that it must comply with Specification C1.8. This Specification sets down tests which such construction must satisfy.
Lightweight construction used in any wall system required to have a FRL must comply with Specification C1.8 (see C1.8(a)(i)).
Lightweight construction must also comply with Specification C1.8 if it is used in a wall system which is not required to have a FRL, but is specifically listed in C1.8(a)(ii) or in a building specifically listed in C1.8(a)(ii).
There is no requirement to comply with Specification C1.8 where lightweight construction is used for walls which:
C1.8(b) sets out the circumstances under which lightweight construction is permitted to be used as a fire-resisting covering for steel columns and the like.
In a building required to be of Type A or B construction, the following building elements and their components must be non-combustible:
External walls and common walls, including all components incorporated in them including the facade covering, framing and insulation.
The flooring and floor framing of lift pits.
Non-loadbearing internal walls where they are required to be fire-resisting.
A shaft, being a lift, ventilating, pipe, garbage, or similar shaft that is not for the discharge of hot products of combustion, that is non-loadbearing, must be of non-combustible construction in—
a building required to be of Type A construction; and
A loadbearing internal wall and a loadbearing fire wall, including those that are part of a loadbearing shaft, must comply with Specification C1.1.
The following materials may be used wherever a non-combustiblematerial is required:
Plasterboard.
Perforated gypsum lath with a normal paper finish.
Fibrous-plaster sheet.
Fibre-reinforced cement sheeting.
Pre-finished metal sheeting having a combustible surface finish not exceeding 1 mm thickness and where the Spread-of-Flame Index of the product is not greater than 0.
Sarking-type materials that do not exceed 1 mm in thickness and have a Flammability Index not greater than 5.
Bonded laminated materials where—
each lamina, including any core, is non-combustible; and
each adhesive layer does not exceed 1 mm in thickness and the total thickness of the adhesive layers does not exceed 2 mm; and
the Spread-of-Flame Index and the Smoke-Developed Index of the bonded laminated material as a whole do not exceed 0 and 3 respectively.
To specify the non-combustibility for building elements and to permit the use of certain materials that are known to provide acceptable levels of fire safety where an element is required to be non-combustible.
The following table lists building elements required to be non-combustible, concrete, or masonry in a building of Type A construction.
Building element
Type A construction
External wall
Non-combustible
Common wall
Non-combustible
Floor and floor framing of lift pit
Non-combustible
All loadbearing internal walls (including those of shafts)
Concrete, masonry or fire-protected timber
Loadbearing fire walls
Concrete, masonry or fire-protected timber
Non-loadbearing walls required to be fire-resistant
Non-combustible
Non-loadbearing lift, ventilation, pipe, garbage and like shafts which do not discharge hot products of combustion
Non-combustible
The following table lists building elements required to be non-combustible, concrete, masonry or fire-protected timber in a building of Type B construction.
Building element
Type B construction
External wall
Non-combustible
Common wall
Non-combustible
Floor and floor framing of lift pit
Non-combustible
All loadbearing internal walls (including those of shafts)
Concrete, masonry or fire-protected timber
Loadbearing fire walls
Concrete, masonry or fire-protected timber
Non-loadbearing walls required to be fire-resistant
Non-combustible
Non-loadbearing lift, ventilation, pipe, garbage and like shafts which do not discharge hot products of combustion
Non-combustible (subject to conditions outlined in C1.9(b))
It should be noted that Parts C1, C2 and C3 and the associated Specifications contain some further non-combustibility requirements for certain building elements.
Note also that C1.9 and other Deemed-to-Satisfy Provisions contain a number of concessions from non-combustibility. For example, C1.13 allows fire-protected timber to be used where an element is required to be non-combustible.
C1.9(d) allows a concession from the requirement for non-combustibility for minor ancillary items forming part of an external wall. These minor ancillary items include gaskets, caulking, sealants and damp-proof courses. They may be used wherever a material is required to be non-combustible. In some instances the material may contain combustible components.
C1.9(e) lists materials deemed to be non-combustible. These materials may be used wherever a material is required to be non-combustible. In some instances the material may contain combustible components. The materials listed are not intended to apply to fire place hearths (see G2.3).
The fire hazard properties of the following internal linings, materials and assemblies within a Class 2 to 9 building must comply with Specification C1.10:
Floor linings and floor coverings.
Wall linings and ceiling linings.
Air-handling ductwork.
Lift cars.
In Class 9b buildings used as a theatre, public hall or the like—
fixed seating in the audience area or auditorium; and
a proscenium curtain required by Specification H1.3.
Escalators, moving walkways and non-required non fire-isolated stairways or pedestrian ramps subject to Specification D1.12.
Attachments to floors, ceilings, internal walls, common walls, fire walls and to internal linings of external walls.
Other materials including insulation materials other than sarking-type materials.
Paint or fire-retardant coatings must not be used to achieve compliance with the required fire hazard properties.
The requirements of (a) do not apply to a material or assembly if it is—
plaster, cement render, concrete, terrazzo, ceramic tile or the like; or
a fire-protective covering; or
a timber-framed window; or
a solid timber handrail or skirting; or
a timber-faced door; or
an electrical switch, socket-outlet, cover plate or the like; or
a material used for—
a roof insulating material applied in continuous contact with a substrate; or
an adhesive; or
a damp-proof course, flashing, caulking, sealing, ground moisture barrier, or the like; or
a paint, varnish, lacquer or similar finish, other than nitro-cellulose lacquer; or
a clear or translucent roof light of glass fibre-reinforced polyester if—
the material is used as part of the roof covering; and
it is not closer than 1.5 m from another roof light of the same type; and
each roof light is not more than 14 m2 in area; and
the area of the roof lights per 70 m2 of roof surface is not more than 14 m2; or
a face plate or neck adaptor of supply and return air outlets of an air handling system; or
a face plate or diffuser plate of light fitting and emergency exit signs and associated electrical wiring and electrical components; or
a joinery unit, cupboard, shelving, or the like; or
an attached non-building fixture and fitting such as—
a curtain, blind, or similar decor, other than a proscenium curtain required by Specification H1.3; and
a whiteboard, window treatment or the like; or
timber treads, risers, landings and associated supporting framework installed in accordance with D2.25 where the Spread-of-Flame Index and the Smoke-Developed Index of the timber does not exceed 9 and 8 respectively; or
any other material that does not significantly increase the hazards of fire.
To stipulate the minimum fire hazard properties of materials inside a building susceptible to the effects of flame or heat.
It is important that the spread of fire and the development of smoke be limited during a fire until building occupants have had time to evacuate. See CP4.
C1.10(a) lists the internal linings, materials and assemblies that must comply with Specification C1.10.
C1.10(c)(i) and (ii) list materials that are not required to comply with C1.10(a). These materials are deemed to comply and accordingly no tests are required to prove that these materials meet the requirements of C1.10(a).
Some paints have been designed to reduce flame spread on combustible materials. These paints, usually referred to as “fire retardant paint”, cannot be used to achieve any of the required fire hazard properties.
This material is unable to be used because of its susceptibility to damage.
C1.10(b) does not prohibit the use of suitable impregnated materials that achieve the relevant fire hazard properties.
C1.10(c)(iii) to (xv) is a practical recognition that a number of building components and materials are unlikely to significantly contribute to the spread of fire and smoke, because of their size, construction, location and so on. The listed components and materials need not comply with C1.10(a).
C1.10(c)(ix) grants an exemption to permit the use of glass reinforced polyester (GRP) in single storey buildings required to be of Type C construction.
The material is limited to GRP because it does not droop or drip when alight. Furthermore, C1.10(c)(ix) limits the disposition and quantity of the GRP for use in the roof. This restriction is to reduce the likelihood of the rapid horizontal spread of fire over large sections of roofing.
Accordingly, for the exemption to be used there must be:
GRP does not have the Spread-of-Flame Index and Smoke-Developed Index required by the Specification. However, the C1.10(c)(ix) concession is provided because if GRP is installed in the prescribed manner, its use in single storey buildings of Type C construction will not materially increase the risk of spread of fire and smoke.
C1.10(c)(xii) refers to elements within buildings such as joinery units, cupboards, shelving and the like which are typically attached to the building structure, however do not form part of the building structure. These elements are exempt as they do not form part of the structure and typically are not included within building works approval. Notwithstanding that these elements are often fixed to the building structure for stability, they are generally of low hazard and may be likened to any building furniture which is not subject to the fire hazard properties provisions.
Likewise, C1.10(c)(xiii) exempts certain types of non-building fixtures such as whiteboards, curtains and blinds, etc. Again, these elements are exempt as they do not form part of the structure and typically are not included within building works approval. It should be noted that not all such fixtures are exempt and reference needs to be made to C1.10(a) to determine which elements must comply.
Concrete external walls that could collapse as complete panels (e.g. tilt-up and pre-cast concrete), in a building having a rise in storeys of not more than 2, must comply with Specification C1.11.
To minimise the risk of any concrete external wall collapsing outwards as a complete panel during a fire.
See the comments on CP5 for the reasons for C1.11; and why C1.11 only applies to a building having a rise in storeys of 1 or 2.
Specification C1.11 contains:
This clause has deliberately been left blank.
Fire-protected timber may be used wherever an element is required to be non-combustible, provided—
the building is—
a separate building; or
a part of a building—
which is located above or below a part not containing fire-protected timber and the floor between the adjoining parts is provided with an FRL not less than that prescribed for a fire wall for the lower storey; and
the building has an effective height of not more than 25 m; and
the building has a sprinkler system (other than a FPAA101D or FPAA101H system) throughout complying with Specification E1.5; and
any insulation installed in the cavity of the timber building element required to have an FRL is non-combustible; and
cavity barriers are provided in accordance with Specification C1.13.
To permit fire-protected timber to be used where an element is required to be non-combustible.
C1.13 provides requirements for when fire-protected timber can be used where an element is required to be non-combustible.
Limitations of the building
C1.13(a) to (c) has specific limitations for a building to use the concession for fire-protected timber.
C1.13(a) requires a building to be a separate building, or a part of building to be separated from the remainder of the building. This includes separation via a fire wall where the part of the building only occupies part of a storey. Where the part of the building is below or above another classification, floor separation must be provided. A fire wall or floor required to have an FRL under C1.13(a)(ii) cannot consist of fire-protected timber.
To use the concession, a height limitation in C1.13(b) requires the building to have an effective height of not more than 25 m. C1.13(c) also requires the building to be sprinkler protected in compliance with Specification E1.5 (other than by a FPAA 101D or FPAA101H system). This is for the purpose of the C1.13 concession and is in addition to the sprinkler requirements of E1.5.
Construction requirements
C1.13(d) and (e) have specific construction requirements as part of the concession. Under (d), where insulation is installed in a fire-protected timber system, the insulation must be non-combustible.
C1.13(e) requires cavity barriers for fire-protected timber to be provided in accordance with Specification C1.13. A cavity barrier referred to in C1.13(e) is a barrier/enclosure within, around or adjacent to the fire-protected timber to limit the spread of fire, smoke and hot gases in the event of a fire.
An ancillary element must not be fixed, installed or attached to the internal parts or external face of an external wall that is required to be non-combustible unless it is one of the following:
An ancillary element that is non-combustible.
A gutter, downpipe or other plumbing fixture or fitting.
A flashing.
A grate or grille not more than 2 m2 in area associated with a building service.
An electrical switch, socket-outlet, cover plate or the like.
A light fitting.
A required sign.
A sign other than one provided under (a) or (g) that—
achieves a group number of 1 or 2; and
does not extend beyond one storey; and
does not extend beyond one fire compartment; and
An awning, sunshade, canopy, blind or shading hood other than one provided under (a) that—
meets the relevant requirements of Table 4 of Specification C1.10 as for an internal element; and
A part of a security, intercom or announcement system.
Wiring.
A paint, lacquer or a similar finish.
To permit certain building components that may contain a limited amount of combustible material to be attached to an external wall required to be non-combustible.
C1.14 prescribes certain allowable ancillary elements that may form part of or be attached to an external wall required to be non-combustible, subject to certain limitations or conditions. These conditions include the ancillary element being constructed of materials meeting certain fire properties, and limitations on its potential extent of coverage of the wall.