Qld Part G5 Construction in bushfire prone areas

Qld Part G5 Construction in bushfire prone areas

Delete GP5.1 and insert Qld GP5.1 as follows:

Qld GP5.1

A building that is constructed in a designated bushfire prone area must be designed and constructed to reduce the risk of ignition from a bushfire while the fire front passes.

Application

Application

Qld GP5.1 only applies to—

  1. a Class 2 or 3 building; or
  2. a Class 10a building or deck associated with a Class 2 or 3 building,

located in a designated bushfire prone area , but does not apply when the classified vegetation is Group F rainforest (excluding wet sclerophyll forest types), mangrove communities and grasslands under 300 mm high.

Delete G5.1 and insert Qld G5.1 as follows:

Qld G5.1

The Deemed-to-Satisfy Provisions of this Part apply to—

(a)

a Class 2 or 3 building; or

(b)

a Class 10a building or deck associated with a Class 2 or 3 building,

located in a designated bushfire prone area , but does not apply when the classified vegetation is Group F rainforest (excluding wet sclerophyll forest types), mangrove communities and grasslands under 300 mm high.