Part B1 Cold water services
Introduction to this Part
This Part sets out the requirements for any part of a cold water service of a property that is connected to a drinking water supply. It covers from the point of connection to the points of discharge.
This part also applies to a cold water service connected to an alternative water source and residential fire sprinklers installed in accordance with FPAA101D Automatic Fire Sprinkler System Design and Installation - Drinking Water Supply.
Objectives
B1O1
Objective
2019: BO1
The Objective of this Part is to—
- safeguard people from illness, injury or loss (including loss of amenity) due to the failure of a cold water installation; and
- ensure that a cold water installation is suitable; and
- conserve water and energy; and
- safeguard the environment; and
- safeguard public and private infrastructure; and
- ensure that a cold water installation is designed and is capable of being maintained so that throughout its serviceable life it will continue to satisfy Objectives (a) to (e).
Functional Statements
B1F1
Cold water supply
2019: BF1.1
Sanitary fixtures, sanitary appliances and supply outlets providing drinking water must have a safe and adequate piped cold water supply.
B1F2
Cold water service
2019: BF1.2
The cold water service must be conveyed through plumbing installations in a way that minimises any adverse impact on building occupants, the Network Utility Operator’s infrastructure, property and the environment.
B1F3
Fire sprinkler systems
New for 2022
Residential fire sprinkler equipment must be provided with adequate water supply and pressure for its intended purpose.
Performance Requirements
B1P1
Cold water supply
2019: BP1.1
A cold water service must be connected to a drinking water supply.
Applications
- B1P1 applies to cold water supplied for human consumption, food preparation, food utensil washing or personal hygiene.
- B1P1 applies to automatic fire sprinkler systems when installed in accordance with FPAA101D Automatic Fire Sprinkler System Design and Installation - Drinking Water Supply.
Explanatory information: Unintentional heating of cold water services
- Where installed in a location subjected to extreme summer temperatures (such as the roof space of a building), cold water services have the potential to become unintentionally heated. This can pose a hazard as the cold water supply may reach temperatures in excess of 45° Celsius, increasing the potential for scalding.
- To reduce the likelihood of unintentional heating of cold water services, consideration should be given to—
- avoiding long runs of pipework in locations exposed to solar heat gain; or
- applying insulation, either directly to the pipework, or by using additional ceiling insulation material between the pipework and the solar heat source.
- Avoidance of unintentional heating of cold water services in known areas of extreme summer temperatures may also assist in reducing water usage through drawing off of water which has become excessively heated.
B1P2
Velocity
2019: BP1.2
Cold water service pipework must ensure that the pipework water velocity does not exceed 3 metres per second for more than 1% of the time that water is required during the annual peak hour.
Explanatory information
During the hour of heaviest usage expected to occur in a year, cold water service velocity of 3 metres per second must not be exceeded for 99% of the time downstream fixtures are in use.
B1P3
Access and isolation
2019: BP1.2
B1P4
Water efficiency
2019: BP1.2
A cold water service must ensure the efficient use of drinking water by—
- limiting water usage from—
- a tap or outlet for a shower, basin, kitchen sink or laundry trough, to a flow rate of not more than 9 l/m; and
- a cistern or flushing device for a urinal, to a flush volume of not more than 2.5 litres for each—
- single urinal stall; or
- 600 mm length of a continuous urinal wall; and
- a dual flush cistern or flushing valve that is connected to a water closet pan to a flush volume of not more than—
- 6 and 3 litres; or
- 4.5 and 3 litres; or
- water saving measures equivalent to or greater than those described in (a).
Applications
The flush volumes of B1P4 may be within a tolerance of—
- ±0.5 litres for the full flush of a 6/3 litre cistern; or
- +0.5 litres for the reduced flush of a 6/3 litre cistern; or
- ±0.2 litres for a 4.5/3 litre cistern.
Exemptions
The requirements of B1P4 do not apply to a vacuum drainage system.
B1P5
Pressure
2019: BP1.2
The points of discharge for a cold water service must—
- have—
- a working pressure of not less than 50 kPa; and
- a static pressure within the building of not more than 500 kPa; or
- have water pressures suitable for the correct functioning of the fixture or appliance where water pressures outside of (a)(i) and (a)(ii) are required.
Exemptions
B1P5(a)(i) and B1P5(a)(ii) do not apply to existing low-pressure gravity only water services.
Pressure
The points of discharge for a cold water service must—
- have—
- a working pressure of not less than 50 kPa; and
- a static pressure within the building of not more than 500 kPa; or
- have water pressures suitable for the correct functioning of the fixture or appliance where water pressures outside of (a)(i) and (a)(ii) are required.
B1P6
Uncontrolled discharge
2019: BP1.2
A cold water service must avoid failure or uncontrolled discharge.
Deemed-to-Satisfy Provisions
B1D1
Deemed-to-Satisfy Provisions
2019: B1.1
- the Network Utility Operator’s drinking water supply; or
- an alternative drinking water supply.
B1D2
Water efficiency
2019: B1.2
- have a dual flushing mechanism; and
- be a minimum 3 Star WELS rating discharging not more than 6 litres or 4.5 litres for a full flush.
QLD B1D2 Water efficiency2019: B1.2
- have a dual flushing mechanism; and
- be a minimum 4 Star WELS rating discharging not more than 4.5 litres for a full flush; and
- are compatible with the size of the toilet bowl to allow for proper functioning of the toilet.
For all other installations, cisterns or flushing devices for water closets must—
- have a dual flushing mechanism; and
- be a minimum 3 Star WELS rating discharging not more than 6 litres or 4.5 litres for a full flush.
- be a minimum 2 Star WELS rating discharging a volume of not more than 2.5 litres for each—
- single urinal stall; or
- 600 mm length of continuous urinal wall; and
- not be set-cycled or activated by any method other than manual or use activation.
Applications
- B1D2(1) applies to outlets that provide cold water only. The Deemed-to-Satisfy Provision for outlets that deliver a combination of cold water and heated water is B2D4.
- The flush volumes of B1D2(2) and B1D2(3) may be within a tolerance of—
- ±0.5 litres for the full flush of a 6/3 litre cistern; or
- +0.5 litres for the reduced flush of a 6/3 litre cistern; or
- ±0.2 litres for a 4.5/3 litre cistern.
Exemptions
- The requirements of B1D2(1) do not apply to a shower intended to provide rapid drenching of a person for emergency purposes, such as chemical removal.
- The requirements of B1D2(2) and B1D2(3) do not apply to a vacuum drainage system.
- The requirements of B1D2(3)(b) do not apply to a programmed solenoid operated flushing system if programmed to shut down during extended periods of non-occupancy of a building.
Explanatory information
Prior to installing a programmed solenoid operated flushing system, further advice should be sought from the authority having jurisdiction.
Where sensor control is used for urinal flushing, sensors should be located to avoid unnecessary ‘nuisance’ flushing triggered by pedestrian traffic.
AS/NZS 6400 Water Efficient Products - Rating and labelling, provides the basis for the rating and labelling of a range of products under the mandatory Water Efficiency Labelling and Standards (WELS) Scheme.
B1D2 outlines the minimum level of water efficiency for certain plumbing products and fixtures, however the adoption of products and technologies of greater efficiency should be considered.
B1D3
General requirements
2019: B1.4
General requirements
Exemptions
B1D3(1) does not apply to existing low-pressure gravity only water supply systems.
General requirements
A cold water service must be in accordance with AS/NZS 3500.1, with the following additions to clause 5.4.2: (l) Where valves are located below ground within the property boundary, they shall be provided with a surface box and riser. The box lid shall be permanently marked with a “W”.
General requirements
A cold water service must be in accordance with AS/NZS 3500.1.
B1D4
Bushfire prone areas
New for 2022
A cold water service in a designated bushfire prone area must be in accordance with AS 3959.
B1D5
Cold water fire sprinkler systems
2019:B4.2
A cold water service used for fire-fighting must be in accordance with—
- the requirements of E1 of Volume One, where applicable; and
- FPAA 101D when installed in a Class 2 or Class 3 building with an effective height of not more than 25 m and a rise in storeys of 4; and
- AS/NZS 3500.1.
Exemptions
B1D5(b) does not apply to a residential care building.
Explanatory information
For all other fire-fighting water services, see Part B4.
B1D6
Top-up lines
2019: B6.3
A cold water service used to top up a rainwater tank must be in accordance with AS/NZS 3500.1.
Installation of cold-water storage tanks used to supply water to a drinking water service must comply with B1D7.
For connection of cold water tanks where reticulated supply is available refer to Sections 8 and 15 of AS/NZS 3500.1.
- AS 2070 Plastics materials for food contact use
- AS 3600 Concrete structures
- AS 3735 Concrete structures retaining liquids
- AS/NZS 2179.1 Specifications for rainwater goods, accessories and fasteners – Metal shape or sheet rainwater goods, and metal accessories and fasteners
- AS/NZS 3500.0 Plumbing and drainage
- AS/NZS 3500.1 Water services
- AS/NZ 3500.3 Stormwater drainage
- AS/NZS 4020 Testing of products in contact with drinking water
- AS/NZS 4130 Polyethylene (PE) pipes for pressure applications
- AS/NZS 4766 Polyethylene storage tanks for water and chemicals
- ABCB Procedures for the Certification of Plumbing and Drainage Products Section B Water services Tasmania
- NCC 2019 Volume Three - Plumbing Code of Australia Page 134
- The followings references are for information only— HB 230 Rainwater Tank Design and Installation Handbook and the enHealth Guidance on the use of rainwater tanks
- the nature and source of the water;
- the risk of corrosion and tank contamination;
- the nature of the environment;
- the physical and chemical characteristics of the materials and products;
- compatibility of materials and products; and
- accessibility for monitoring and maintenance.
- Manufacturer’s name, brand or trademark, and
- The Standard which the tank is manufactured to, and
- The date of manufacture.
Explanatory information
Information on some of the above items listed in the materials above may be obtainable from the manufacturer or supplier of the product or materials.
Rainwater for drinking purposes should not be collected from recently painted roofs (until after the first few rainfalls), timber roofs preserved with chemicals, roofs coated with lead flashings, lead-based paints or tar-based coatings, or parts of roofs near flues from solid fuel heaters. Rainwater for drinking water purposes may be collected from roof types other than those identified above provided the roof and associated gutters are kept clean of leaves, animal remains, dust and other debris. Gutters must be kept clean by installing screens or leaf diverters between the roof and the water tank. The system should incorporate a ‘first flush system’ or other diversion system that will prevent the first flush of water from entering the tank.
Tanks should be regularly maintained by cleaning out accumulated sludge from the base every 2 - 3 years. For detailed advice on desludging and maintaining tanks refer to the enHealth Guide – Guidance on the use of rainwater tanks; or HB 230 Rainwater tank design and installation handbook
For ongoing maintenance of water quality one or more of the following water quality treatment methods should be adopted: Chlorinating: To commission the tank sufficient chlorine should be added to provide a free chlorine residual of 0.5 mg/L after 30 minutes. To satisfy chlorinating requirements an initial dose of 5 mg/L of chlorine may be necessary. For every kL of water in the tank, add either: 40 mL of liquid pol chlorine (sodium hypochlorite - 12.5% available chlorine); or 8 grams of granular pool chlorine (calcium hypochlorite - 65% available chlorine). To calculate the tank volume in kL for a cylindrical tank the volume in of water in kL = D x D x H x 0.785. Where D = diameter of the tank, and H = depth of water in the tank in metres. To verify this calculation, compare this volume with the maximum capacity of the tank. The chlorine residual may be tested with a swimming pool test kit or dip strips. Water after chlorinating should not be used for 24 hours to enable any harmful microorganisms to be killed off. Filtration: If filters are used in drinking water installations they are to be certified to the relevant Australian Standard under the WaterMark Certification Scheme and should be maintained by following the manufacturer’s maintenance instructions. Ultraviolet Disinfection: Filtration may be required to address water turbidity to enable adequate UV disinfection. Ultraviolet treatment is affected by the levels of turbidity, organic content from suspended solids, pH, hardness and UV transmissivity of the water. The intensity of the UV light and the build-up of suspended solids on the quartz tube affect the disinfection performance. Regular monitoring of the quartz tubes is critical. Lamps also need to be replaced regularly in accordance with the manufacturer’s instructions.
Cold water storage tanks
Explanatory information: Cross-volume considerations
NCC Volumes One and Two deal with a number of areas of on-site construction which are relevant to cold water services. These include, but may not be limited to, those listed in Table B1.
Item | NCC Volume One Class 2 to 9 buildings | NCC Volume Two Class 1 and 10 buildings |
---|---|---|
Excavations for pipework adjacent to a building and footings | B1 Structural provisions | H1 Structure |
Termite management for attachments to buildings and penetrations through a slab | B1 Structural provisions | H1 Structure |
Penetrations for pipework through a vapour barrier | B1 Structural provisions | H1 Structure |
Pipework in timber bearers and joists of solid timber or engineered wood products | B1 Structural provisions | H1 Structure |
Fittings, fixtures and pipework installations in steel framed construction | B1 Structural provisions | H1 Structure |
Penetrations through a fire-resisting wall or floor | C1 Fire resistance Performance Requirements and C4 Protection of openings | H3 Fire safety |
Fixtures and fittings in a wet area | F2 Wet areas and overflow protection | H4 Health and amenity |
Service pipework external to the building and penetrations through roof cladding in a bushfire prone area | G5 Construction in bushfire prone areas | H7 Ancillary provisions and additional construction requirements |
Pipework sound insulation | F7 Sound transmission and insulation | H4 Health and amenity |
Flues, chimneys, pipes, gas storage, domestic fuel tanks, cooling or heating appliances or other services | C4 Protection of openings | H3 Fire safety |
Power supply to boiling and/or chilled water storage units | J7 Artificial lighting and power | Not applicable |