13.7
Part 13.7 ServicesPart 13.7 Services
13.7.1
Application of Part 13.7
2019: 3.12.5
13.7.1
Application of Part 13.7
2019: 3.12.5
- a Class 1 building; and
- a Class 10a building.
Application of Part 13.7
- a Class 1 building; and
- a Class 10a building; and
- a Class 10b swimming pool associated with a Class 1 or 10a building.
13.7.2
Insulation of services
2019: 3.12.5.1
13.7.2
Insulation of services
2019: 3.12.5.1
Explanatory information
The central heating water piping provisions apply to systems designed to heat the building via water, such as a hydronic heating system.
13.7.3
Central heating water piping
2019: 3.12.5.2
13.7.3
Central heating water piping
2019: 3.12.5.2
- flow and return piping that is—
- within an unventilated wall space; or
- within an internal floor between storeys; or
- between ceiling insulation and a ceiling; and
- heated water piping encased within a concrete floor slab (except that which is part of a floor heating system),
must, in all climate zones, have a minimum material R-Value of 0.4.
- flow and return piping; and
- cold water supply piping within 500 mm of the connection to the central water heating system; and
- relief valve piping within 500 mm of the connection to the central water heating system,
must have a minimum material R-Value in accordance with (5).
- flow and return piping; and
- cold water supply piping within 500 mm of the connection to the central water heating system; and
- relief valve piping within 500 mm of the connection to the central water heating system,
must have a minimum material R-Value in accordance with (6).
- in climate zones 1, 2, 3 and 5 — 0.6; and
- in climate zones 4, 6 and 7 — 0.9; and
- in climate zone 8 — 1.3.
- in climate zones 1, 2, 3 and 5 — 0.6; and
- in climate zones 4, 6 and 7 — 1.3; and
- in climate zone 8 — 1.3.
Explanatory information
- The insulation levels in Explanatory Table 13.7.3 are typical examples of materials that can be used to insulate central heating water piping calculated in accordance with AS/NZS 4859.1.
- The R-Value is that of the insulation and not the Total R-Value of the pipe, air film and insulation. Where piping has a significant inherent R-Value it may be subtracted from the material R-Value required. However, the inherent R-Value of most piping is not sufficient to satisfy the requirements of 13.7.3.
- Piping within a timber member, such as that passing through a wall stud, is considered to have sufficient insulation for the purposes of 13.7.3.
- Explanatory Table 13.7.3 provides examples for the R-Value of the insulation used for smaller diameter piping.
Insulation | R-Value |
---|---|
9 mm of closed cell polymer | 0.4 |
13 mm of closed cell polymer | 0.6 |
19 mm of closed cell polymer | 0.9 |
25 mm of closed cell polymer | 1.3 |
25 mm of glasswool | 1.3 |
13.7.4
Heating and cooling ductwork
2019: 3.12.5.3
13.7.4
Heating and cooling ductwork
2019: 3.12.5.3
- achieve the material R-Value in (4); and
- be sealed against air loss—
- by closing all openings in the surface, joints and seams of ductwork with adhesives, mastics, sealants or gaskets in accordance with AS 4254.1 and AS 4254.2 for a Class C seal; or
- for flexible ductwork, with a draw band in conjunction with a sealant or adhesive tape.
- abut adjoining duct insulation to form a continuous barrier; and
- be installed so that it maintains its position and thickness, other than at flanges and supports; and
- where located outside the building, under a suspended floor, in an attached Class 10a building or in a roof space—
- be protected by an outer sleeve of protective sheeting to prevent the insulation becoming damp; and
- have the outer protective sleeve sealed with adhesive tape not less than 48 mm wide creating an airtight and waterproof seal.
- In a heating-only system or cooling-only system including an evaporative cooling system—
- ductwork must have a minimum material R-Value of—
- in climate zones 1 to 7 — 1.0; and
- in climate zone 8 — 1.5; and
- fittings must have a minimum material R-Value of 0.4.
- ductwork must have a minimum material R-Value of—
- In a combined heating and refrigerated cooling system—
- ductwork must have a minimum material R-Value of—
- in climate zones 1, 3, 4, 6 and 7 — 1.5; and
- in climate zones 2 and 5 — 1.0; and
- in climate zone 8 — 1.5; and
- fittings must have a minimum material R-Value of 0.4.
- ductwork must have a minimum material R-Value of—
- For the purposes of (b)(i), the minimum material R-Value required for ductwork may be reduced by 0.5 for combined heating and refrigerated cooling systems in climate zones 1, 3, 4, 6 and 7 if the ducts are—
- under a suspended floor with an enclosed perimeter; or
- in a roof space that has an insulation of greater than or equal to R0.5 directly beneath the roofing.
Explanatory information
- Ductwork within a fully insulated building may still benefit from insulation particularly when the system is only operating for short periods.
- In some climate zones condensation may create problems with uninsulated ductwork, in which case insulation should still be considered.
- An enclosed perimeter treatment means that the airspace under the floor is enclosed between ground and floor level by walls which have only the required subfloor vents.
- Insulation for refrigerated cooling ductwork should have a vapour barrier to prevent possible damage by condensation.
- The insulation levels in the Explanatory Tables 13.7.4a, 13.7.4b and 13.7.4c are typical examples of materials that can be used to insulate ductwork and the R-Values they contribute. Other methods are available for meeting the minimum material R-Value required by 13.7.4(4). These values do not take into account all issues that may reduce the effectiveness of insulation. AS/NZS 4859.1 should be used to confirm in-situ values.
- For fittings, 11 mm polyurethane typically provides an R-Value of 0.4.
- Any flexible ductwork used for the transfer of products, initiating from a heat source that contains a flame, must also have the fire hazard properties required by H3D2(2).
Insulating material and thickness | R-Value |
---|---|
45 mm glasswool (11 kg/m3) | 1.0 |
70 mm polyester (6.4 kg/m3) | 1.0 |
63 mm glasswool (11 kg/m3) | 1.5 |
90 mm polyester (8.9 kg/m3) | 1.5 |
85 mm glasswool (11 kg/m3) | 2.0 |
Insulating material and thickness | R-Value |
---|---|
38 mm glasswool (22 kg/m3) | 1.0 |
50 mm polyester (20 kg/m3) | 1.1 |
50 mm glasswool (22 kg/m3) | 1.5 |
75 mm polyester (20 kg/m3) | 1.7 |
Insulating material and thickness | R-Value |
---|---|
38 mm glasswool (32 kg/m3) | 1.0 |
50 mm polyester (32 kg/m3) | 1.3 |
50 mm glasswool (32 kg/m3) | 1.5 |
13.7.5
Electric resistance space heating
2019: 3.12.5.4
13.7.5
Electric resistance space heating
2019: 3.12.5.4
Electric resistance space heating
13.7.5 does not apply in NSW.
An electric resistance space heating system that serves more than one room must have—
- separate isolating switches for each room; and
- a separate temperature controller and time switch for each group of rooms with common heating needs; and
- power loads of not more than 110 W/m2 for living areas, and 150 W/m2 for bathrooms.
13.7.6
Artificial lighting
2019: 3.12.5.5
13.7.6
Artificial lighting
2019: 3.12.5.5
Artificial lighting
13.7.6 does not apply in NSW.
- 5 W/m2 in a Class 1 building; and
- 4 W/m2 on a verandah, balcony or the like attached to a Class 1 building; and
- 3 W/m2 in a Class 10a building associated with a Class 1 building.
- be controlled by a daylight sensor; or
- have an average light source efficacy of not less than 40 Lumens/W.
- Lighting timer for corridor lighting: 0.7.
- Motion detector —
- 0.9, where —
- at least 75% of the area of a space is controlled by one or more motion detectors; or
- an area of less than 200 m2 is switched as a block by one or more motion detectors; and
- 0.7, where up to 6 lights are switched as a block by one or more detectors; and
- 0.55, where up to 2 lights are switched as a block by one or more detectors.
- 0.9, where —
- Manual dimming system where not less than 75% of the area of a space is controlled by manually operated dimmers: 0.85.
- Programmable dimming system where not less than 75% of the area of a space is controlled by programmable dimmers: 0.85.
- Dynamic dimming system, with automatic compensation for lumen depreciation, the design lumen depreciation factor is not less than —
- 0.9 for fluorescent lights; or
- 0.8 for high pressure discharge lights.
- Fixed dimming where at least 75% of the area is controlled by fixed dimmers that reduce the overall lighting level and the power consumption of the lighting — equal to the % of full power to which the dimmer is set divided by 0.95.
- Daylight sensor and dynamic lighting control device, with dimmed or stepped switching of lights adjacent to windows:
- Lights within the space adjacent to windows other than roof lights for a distance from the window equal to the depth of the floor at window head height: 0.5.
- Lights within the space adjacent to roof lights: 0.6.
Explanatory information
- There are two approaches available for achieving compliance with (1) in Class 1 and associated Class 10a buildings. These are through the determination of the lamp power density or the illumination power density.
- The first step in achieving compliance is to determine the relevant lamp power density or illumination power density allowance. Generally, the lamp power density or illumination power density is the relevant value in (1)(a), (b) or (c), however the illumination power density allowance can be increased in accordance with (2) if a control device is used.
- When illumination power density and one or more control devices are used, the adjustment factor is only applied to the space(s) served by the control device. The adjusted allowance for this space is then combined with the allowances for the remaining spaces using an area weighted average, which subsequently increases the allowance provided in (1)(a), (b) or (c).
- Where no control device is used the adjustment factor is equal to 1.
- The second step in achieving compliance is to assess the overall lamp power density or overall illumination power density of the building.
- The overall lamp power density is calculated by adding the maximum power ratings of all of the permanently wired lamps in a space and dividing this sum by the area of the space.
- The overall illumination power density is calculated by adding the illumination power load for each space and dividing this sum by the area of the space.
- Control device factors in (2) are only applied to the illumination power density, not the overall illumination power density.
- To comply with (1), the overall lamp power density or overall illumination power density must be less than or equal to the allowance.
- Trading of allowances between (1)(a), (b) and (c) is not permitted.
- (1)(b) includes outdoor living spaces such as verandahs, balconies, patios, alfresco spaces or the like that are attached to a Class 1 building.
- The artificial lighting requirements in 13.7.6 are to be read in conjunction with the artificial lighting requirements in 10.5.2.
- The artificial lighting around the perimeter of a building does not need to comply to a maximum power density as neither the lighting required or the area of the space can be easily defined. Instead, external lights are required to be controlled by daylight sensors or to be efficient.
- In (4), separate switching is required for halogen lamps to facilitate less frequent usage. This is because they are significantly less energy efficient that fluorescent lamps.
13.7.7
Water heater in a heated water supply system
2019: 3.12.5.6
13.7.7
Water heater in a heated water supply system
2019: 3.12.5.6
Water heater in a heated water supply system
13.7.7 does not apply in NSW.
A water heater in a heated water supply system must be designed and installed in accordance with Part B2 of NCC Volume Three — Plumbing Code of Australia.
13.7.8
Swimming pool heating and pumping
2019: 3.12.5.7
13.7.8
Swimming pool heating and pumping
2019: 3.12.5.7
Swimming pool heating and pumping
13.7.8 does not apply in NSW.
- a solar heater not boosted by electric resistance heating; or
- a heater using reclaimed energy; or
- a gas heater; or
- a heat pump; or
- a combination of (a) to (d).
- a cover with a minimum R-Value of 0.05, unless located in a conditioned space; and
- a time switch to control the operation of the heater.
13.7.9
Spa pool heating and pumping
2019: 3.12.5.8
13.7.9
Spa pool heating and pumping
2019: 3.12.5.8
Spa pool heating and pumping
13.7.9 does not apply in NSW.
- a solar heater; or
- a heater using reclaimed energy; or
- a gas heater; or
- a heat pump; or
- a combination of (a) to (d).
- a cover; and
- a push button and a time switch to control the operation of the heater.