Happy Holidays! We wish you a happy and safe holiday season. Please note that the ABCB office will be closed from 24 December 2024 until 2 January 2025.
Part 9.3 Fire protection of separating walls and floors
Part 9.3 Fire protection of separating walls and floors
9.3.1
Separating walls
2019: 3.7.3.2
(1) A separating wall between Class 1 buildings, or a wall that separates a Class 1 building from a Class 10a building which is not associated with the Class 1 building must—
be constructed—
having an FRL of not less than 60/60/60; or
of masonry not less than 90 mm thick; and
commence at the footings or ground slab (see Figure 9.3.1a), except for horizontal projections to which 9.3.4 applies (see Figure 9.3.4); and
must not be crossed by timber or other combustible building elements except for roof battens with dimensions of 75 x 50 mm or less, or roof sarking; and
must have any gap between the top of the wall and the underside of the roof covering packed with mineral fibre or other suitable fire-resisting material.
(4) Where a building has a masonry veneer external wall, any gap between the separating wall and the external masonry veneer must be—
not more than 50 mm; and
packed with a mineral fibre or other suitable fire-resisting material with the packing arranged to maintain any weatherproofing requirements of H2D4.
(5) Eaves, verandahs and similar spaces that are open to the roof space and are common to more than one Class 1 dwelling must be separated by a non-combustible vertical lining (see Figure 9.3.1c).
(1) Any service opening, other than those listed in (2), (3) and (4), in a separating wall must have construction with an FRL of not less than -/60/60.
(2) If an electrical wire or cable penetrates a separating wall—
the service and building element at the penetration must—
be identical with a prototype assembly that has been tested in accordance with AS 4072.1 and AS 1530.4 and achieve an FRL of not less than -/60/60; or
differ from a prototype assembly of the service and building element in accordance with AS 4072.1; or
the service must be installed so that—
the opening is neatly formed, cut or drilled and no closer than 50 mm to any other service; and
the opening is no larger in cross-section than—
2000 mm2 if only a single cable is accommodated and the gap between the cable and the wall is no wider than 15 mm; or
500 mm2 in any other case; and
any gap between the service and the wall is packed with mineral fibre or other suitable fire-resisting material.
(3) If an electrical switch, outlet, socket or the like is accommodated in a separating wall—
the service and building element at the penetration must—
be identical with a prototype assembly which has been tested in accordance with AS 4072.1 and AS 1530.4 and achieve an FRL of not less than -/60/60; or
differ from a prototype assembly of the service and building element in accordance with AS 4072.1; or
the service must be installed so that—
the opening or recess—
is not located opposite any point within 300 mm horizontally or 600 mm vertically of any opening or recess on the opposite side of the wall; or
does not extend beyond half the thickness of the wall; and
any gap between the service and the wall is packed with mineral fibre or other suitable fire-resisting material.
(4) Other than where a tested system is used in accordance with (3)(a), if an electrical switch, socket, outlet or the like is accommodated in a hollow separating wall, the cavity immediately behind the service must be framed and packed with mineral fibre or other suitable fire-resisting material (see Figure 9.3.2).
Explanatory information
For the purposes of 9.3.2 and 10.7.2, a reference to a separating wall includes a wall that separates a Class 1 building from a Class 10a building that is not associated with the Class 1 building.
It is important that any opening in a separating wall between Class 1 buildings does not allow the free passage of fire between buildings. Many designs would require the installation of openings for electrical cables and outlets in these walls. 9.3.2 therefore allows such openings provided they comply with the requirements of that provision.
A reference to a hollow separating wall in 9.3.2(4) may include a stud wall, masonry cavity wall or a wall of hollow blockwork.
Part 10.7 (sound insulation) also contains requirements relevant to separating walls, in addition to the provisions of this Part. This includes installation requirements for walls and services to achieve appropriate levels of sound insulation.
be a floor/ceiling or floor/soffit system incorporating a ceiling or soffit which has a resistance to the incipient spread of fire to the space above itself of not less than 60 minutes; or
have an FRL not less than 30/30/30 when tested from the underside; or
(2) The part of the separating wall that projects outwards horizontally must—
extend to the underside of the floor/ceiling or floor/soffit system complying with (1); and
not be crossed by timber or other combustible building elements except for framing members with dimensions of 75 x 50 mm or less, or sarking; and
have any gap between the bottom of the wall and the underside of the floor/ceiling or floor/soffit system packed with mineral fibre or other suitable fire-resisting material.
(3) Where a floor subject to (1)(b) depends on direct vertical or lateral support from another part to maintain its FRL, that supporting part must have an FRL of not less than 30/-/-.
(4) Where a service passes through a floor referred to in (1), the penetration must not reduce the fire performance of the floor or covering.