Filter
10.2
Part 10.2 Wet area waterproofingPart 10.2 Wet area waterproofing
10.2.1
Wet areas
2019: 3.8.1.2
10.2.1
Wet areas
2019: 3.8.1.2
Building elements in wet areas within a building must—
- be waterproof or water resistant in accordance with 10.2.2 to 10.2.6, except that—
- in any room containing a washing machine, the wall area from finished floor level to a minimum of 75 mm above and 75 mm each side of the washing machine tap outlets must be water resistant; and
- where a vessel is inset into a bench top in a kitchen, bar area, kitchenette or domestic food and beverage preparation area—
- wall junctions and joints within 150 mm above the vessel must be water resistant for the extent of the vessel; and
- the perimeter edges of the vessel must be water resistant for the extent of the vessel (see SA Figures 10.2.1a, 10.2.1b and 10.2.1c); and
- penetrations in horizontal surfaces for tap and spout outlets in kitchens, bar areas, kitchenettes or domestic food and beverage preparation areas, must be waterproof; and
- comply with AS 3740; and
- have floor wastes provided in accordance with SA 10.2.33; and
- where floor wastes are provided for drainage of floors in bathrooms and laundries, the floors, floor/wall junction and penetration must be waterproof.
Wet areas
10.2.2
Shower area (enclosed and unenclosed)
2019: Table 3.8.1.1
10.2.2
Shower area (enclosed and unenclosed)
2019: Table 3.8.1.1
- The floor of the shower area must be waterproof, including any hob or step-down (see Figure 10.2.2); and
- The walls of the shower area must be waterproof not less than 1800 mm above the floor substrate (see Figure 10.2.2).
- Wall junctions and joints within the shower area must be waterproof not less than 40 mm either side of the junction (see Figure 10.2.2).
- Wall/floor junctions within the shower area must be waterproof (see Figure 10.2.2).
- Penetrations within the shower area must be waterproof.
Notes
Where a shower is above a bath or spa, use requirements for shower.
10.2.3
Area outside shower area
2019: Table 3.8.1.1
10.2.3
Area outside shower area
2019: Table 3.8.1.1
- waterproof; and
- where a flashing is used, the horizontal leg must be not less than 40 mm.
10.2.4
Areas adjacent to baths and spas without showers
2019: Table 3.8.1.1
10.2.4
Areas adjacent to baths and spas without showers
2019: Table 3.8.1.1
- For concrete, compressed fibre-cement and fibre-cement sheet flooring, the floor of the room must be water resistant.
- For timber floors including particleboard, plywood and other timber based flooring materials, the floor of the room must be waterproof.
- Tap and spout penetrations must be waterproof where they occur in horizontal surfaces.
- Walls must be water resistant (see Figure 10.2.4a and Figure 10.2.4b)—
- Wall junctions and joints must be water resistant within 150 mm above a vessel for the extent of the vessel.
- Wall/floor junctions must be waterproof for the extent of the vessel (see Figure 10.2.4a and Figure 10.2.4b).
- For floors and horizontal surfaces:
- Any shelf area adjoining the bath or spa must be waterproof and include a waterstop under the vessel lip.
- There are no requirements for the floor under a bath or spa.
- For walls:
- Waterproof to not less than 150 mm above the lip of a bath or spa.
- There are no requirements for the floor under a bath or spa.
- For wall junctions and joints, the following applies:
- Waterproof junctions within 150 mm of a bath or spa.
- There are no requirements for junctions and joints in walls beneath the lip of a bath or spa.
- Tap and spout penetrations must be waterproof where they occur in horizontal surfaces.
10.2.5
Other areas
2019: Table 3.8.1.1
10.2.5
Other areas
2019: Table 3.8.1.1
- Walls must be water resistant to a height of not less than 150 mm above the vessel, for the extent of the vessel, where the vessel is within 75 mm of a wall (see Figure 10.2.5).
- Waterproof wall junctions where a vessel is fixed to a wall.
- Waterproof tap and spout penetrations where they occur in surfaces required to be waterproof or water resistant.
- The floor of the room must be water resistant.
- Wall/floor junctions must be water resistant, and where a flashing is used, the horizontal leg must not be less than 40 mm.
- The floor of the room must be waterproof.
- Walls must be—
- waterproof in WC area within a 900 mm radius from the wall connection of the handheld bidet spray device to a height of not less than 150 mm above the floor substrate; and
- water resistant in WC area within a 900 mm radius from the wall connection of the handheld bidet device to not less than 1200 mm above the finished floor level of the WC.
- Wall junctions within the WC area within 900 mm radius from the wall connection of the handheld bidet spray device must be waterproof.
- Wall/floor junctions within the WC area within 1000 mm radius from the wall connection of the handheld bidet spray device must be waterproof.
- Penetrations in the WC area must be waterproof.
10.2.6
Waterproofing systems
New for 2022
10.2.6
Waterproofing systems
New for 2022
- waterproof, if it complies with (2); or
- water resistant, if it complies with (3).
10.2.7
Materials
New for 2022
10.2.7
Materials
New for 2022
Where required to be installed in accordance with 10.2.2 to 10.2.6, materials used in wet areas forming a waterproofing system must be either waterproof or water resistant in accordance with 10.2.8 and 10.2.9.
10.2.8
Materials — waterproof
New for 2022
10.2.8
Materials — waterproof
New for 2022
The following materials used in waterproofing systems are deemed to be waterproof:
- Stainless steel.
- Flexible waterproof sheet flooring material with waterproof joints.
- Membranes complying with AS/NZS 4858.
- Waterproof sealant.
10.2.9
Materials — water resistant substrates
New for 2022
10.2.9
Materials — water resistant substrates
New for 2022
The following materials are deemed to be water resistant:
- For walls:
- Concrete complying with AS 3600, treated to resist moisture movement.
- Cement render, treated to resist moisture movement.
- Compressed fibre-cement sheeting manufactured in accordance with AS/NZS 2908.2.
- Water resistant plasterboard sheeting.
- Masonry in accordance with AS 3700, treated to resist moisture movement.
- For floors:
- Concrete complying with AS 3600.
- Concrete slabs complying with AS 2870.
- Compressed fibre-cement sheeting manufactured in accordance with AS/NZS 2908.2 and supported on a structural floor.
10.2.10
Materials — water resistant surface materials
New for 2022
10.2.10
Materials — water resistant surface materials
New for 2022
The following surface materials are deemed to be water resistant:
- For walls:
- Thermosetting laminate.
- Pre-decorated compressed fibre-cement sheeting manufactured in accordance with AS/NZS 2908.2.
- Tiles when used in conjunction with a substrate listed in 10.2.9.
- Water resistant flexible sheet wall material with sealed joints when used in conjunction with a substrate listed in 10.2.9.
- Sanitary grade acrylic linings.
- For floors, when used in conjunction with a substrate listed in 10.2.9:
- Tiles.
- Water resistant flexible sheet flooring material with sealed joints.
- Concrete treated to resist moisture movement.
Explanatory information
Sheet vinyl or linoleum would satisfy the requirements of this clause.
10.2.11
Construction of wet areas — wall and floor substrate materials
New for 2022
10.2.11
Construction of wet areas — wall and floor substrate materials
New for 2022
For the purposes of this Part, materials used in wall and floor substrates must comply with 10.2.9.
10.2.12
Construction of wet area floors — falls
New for 2022
10.2.12
Construction of wet area floors — falls
New for 2022
Where a floor waste is installed—
- the minimum continuous fall of a floor plane to the waste must be 1:80; and
- the maximum continuous fall of a floor plane to the waste must be 1:50.
10.2.13
Construction of wet areas — wall and floor surface materials
New for 2022
10.2.13
Construction of wet areas — wall and floor surface materials
New for 2022
For the purposes of this Part, wall and floor surface materials must comply with 10.2.10.
10.2.14
Shower area requirements
New for 2022
10.2.14
Shower area requirements
New for 2022
Shower areas must be designed as either enclosed or unenclosed—
10.2.15
Stepdown showers
New for 2022
10.2.15
Stepdown showers
New for 2022
For stepdown showers, the highest finished floor level of the shower area must be stepped down a minimum of 25 mm lower than the finished floor level outside the shower (see Figures 10.2.15a, 10.2.15b, 10.2.15c and 10.2.15d).
10.2.16
Hob construction
New for 2022
10.2.16
Hob construction
New for 2022
- masonry; or
- concrete; or
- autoclaved aerated concrete; or
- extruded polyurethane foam,
in accordance with Figure 10.2.16.
10.2.17
Enclosed showers with level threshold (without hob or set down)
New for 2022
10.2.17
Enclosed showers with level threshold (without hob or set down)
New for 2022
For enclosed showers without a stepdown or a hob, at the extremity of the shower area, a waterstop must be positioned so that its vertical leg finishes—
- where a shower screen is to be installed, not less than 5 mm above the finished floor level (see Figure 10.2.17); and
- where the waterstop intersects with a wall or has a joint, the junction must be waterproof.
10.2.18
Unenclosed showers
New for 2022
10.2.18
Unenclosed showers
New for 2022
- A waterstop must be installed a minimum horizontal distance of 1500 mm from the shower rose.
- The vertical leg of the waterstop must finish—
- flush with the top surface of the floor (see Figure 10.2.18); and
- where the waterstop intersects with a wall or is joined—
- the junction must be waterproof; or
- the whole wet area floor must be waterproofed and drained to a floor waste as for the shower area.
10.2.19
Preformed shower bases
New for 2022
10.2.19
Preformed shower bases
New for 2022
Preformed shower bases must—
- have an upturn lip (see Figure 10.2.19a and Figure 10.2.19b); and
- be recessed into the wall to allow the water resistant surface materials and substrate materials to pass down inside the perimeter upturn lip of the shower base (see Figure 10.2.19a and Figure 10.2.19b); and
- be supported to prevent distortion or cracking.
10.2.20
Baths and spas
New for 2022
10.2.20
Baths and spas
New for 2022
Baths and spas, except freestanding baths and spas, must—
- have an upturn lip; and
- be recessed into the wall (see Figure 10.2.20); and
- have the water resistant substrate materials of the wall pass down inside the upturn lip (see Figure 10.2.20).
10.2.21
Membrane installation for screed
New for 2022
10.2.21
Membrane installation for screed
New for 2022
Where a screed is used in conjunction with a waterproof membrane, the waterproof membrane can be installed either above or below the tile bed or screed.
10.2.22
Substrate surface preparation for application of membrane
New for 2022
10.2.22
Substrate surface preparation for application of membrane
New for 2022
The substrate surface area where a membrane is to be applied must—
- be clean and dust free; and
- free of indentations and imperfections.
10.2.23
Penetrations
New for 2022
10.2.23
Penetrations
New for 2022
Penetrations within shower areas must comply with the following:
- Penetrations for taps, shower nozzles and the like must be waterproofed by sealing with—
- sealants; or
- proprietary flange systems; or
- a combination of (i) and (ii).
- The spindle housing of the tap body must be able to be removed to enable replacement of the washer without damaging the seal.
- The following must be waterproofed:
- All penetrations due to mechanical fixings or fastenings of substrate materials.
- Any penetration of the surface materials due to mechanical fixings or fastenings.
- Recessed soap holders (niches) and the like.
- Tap and spout penetrations on horizontal surfaces surrounding baths and spas must be waterproofed by—
- sealing the tap body to the substrate with sealants; or
- proprietary flange systems.
10.2.24
Flashings/junctions
New for 2022
10.2.24
Flashings/junctions
New for 2022
Flashings must be installed in accordance with 10.2.2 to 10.2.5 and the following:
- Perimeter flashing to wall/floor junctions must have a—
- vertical leg that extends a minimum of 25 mm above the finished floor level, except across doorways; and
- horizontal leg that has a minimum width of not less than 50 mm.
- Where a water resistant substrate is used in conjunction with a water resistant surface material, a waterproof sealant must be installed at the substrate junction at the wall/floor junction.
- Perimeter flashings at a floor level opening must comply with the following:
- Where the whole wet area floor is waterproof, at floor level openings, a waterstop must be installed that has a vertical leg finishing flush with the top of the finished floor level with the floor membrane being terminated to create a waterproof seal to the waterstop and to the perimeter flashing (see Figure 10.2.24).
- In any other case, at a floor level opening a waterstop must be installed that has a vertical leg finishing flush with the top of the finished floor level and waterproofed to the perimeter flashing.
- A vertical flashing, either external to the wet area or internal, must extend a minimum of 1800 mm above the finished floor level.
Explanatory information
Vertical flashing may be used as follows:
- External vertical flashing may be used with external membrane systems and installed behind the wall sheeting or render. They must have legs of sufficient width to allow the wall sheeting or render to overlap by not less than 32 mm.
- Internal vertical flashing may be used with both external and internal membrane systems provided each leg has a minimum overlap of 40 mm to the wall sheeting or render and where used with—
- internal membrane, must extend vertically from the shower tray; and
- external membranes, must overlap the top edge of the floor waterproofing system by not less than 20 mm; and
- preformed shower bases or baths, must extend to the bottom edge of the wall sheeting or render.
10.2.25
Shower area floor membrane application
New for 2022
10.2.25
Shower area floor membrane application
New for 2022
For hobless showers, or showers with hobs or stepdowns, the membrane must be applied over the floor and up the vertical face of the wall substrate to a minimum height of 1800 mm above the finished tile level of the floor.
10.2.26
Shower area membrane requirements for wall sheeting substrates
New for 2022
10.2.26
Shower area membrane requirements for wall sheeting substrates
New for 2022
10.2.27
Bond breaker installation for bonded membranes
New for 2022
10.2.27
Bond breaker installation for bonded membranes
New for 2022
Explanatory information
Typical details for bond breaker types are given in Explanatory Figure 10.2.27.
10.2.28
Installation of internal membranes
New for 2022
10.2.28
Installation of internal membranes
New for 2022
10.2.29
Membrane to drainage connection
New for 2022
10.2.29
Membrane to drainage connection
New for 2022
- A drainage flange must be installed with the waterproofing membrane terminated at or in the drainage flange to provide a waterproof connection (see Figure 10.2.29).
- Where a preformed shower base is used, provision must be made to drain the tile bed and provide a waterproof connection to the drain.
Explanatory information: Drainage flanges
- For membrane drainage connections in concrete floors: drainage flange may be either cast into the concrete slab or set into the top surface of the concrete slab or the tile bed.
- For membrane drainage connections in other floors: drainage flange may be either set into the floor substrate or the tile bed.
10.2.30
Drainage riser connection
New for 2022
10.2.30
Drainage riser connection
New for 2022
10.2.31
Door jambs on tiled floors
New for 2022
10.2.31
Door jambs on tiled floors
New for 2022
10.2.32
Shower screens
New for 2022
10.2.32
Shower screens
New for 2022
Explanatory information
A self-draining sub-sill is considered to be part of the shower screen.
- all vessels are provided with in-built overflow protection or have a permanent open trapped connection to the plumbing and drainage system (such as a WC pan); or
- the floor waste is provided solely for the connection of plumbing fixtures and all vessels in the wet area are provided with in-built overflow protection or have permanent open trapped connection to the plumbing and drainage system (such as a WC pan).
Provision of floor wastes