Part 5.4 Unreinforced single leaf masonryPart 5.4 Unreinforced single leaf masonry
5.4.1
Application of Part 5.4
New for 2022
5.4.1
Application of Part 5.4
New for 2022
5.4.2
External walls
New for 2022
5.4.2
External walls
New for 2022
- The roof frame must be connected continuously to the top of the wall (see Figure 5.4.2a).
- Stack bonded piers must have wall ties at every fourth course.
- Pier and return supports size limitations for—
- single leaf unreinforced masonry walls with engaged piers, must comply with Table 5.4.2a and Figure 5.4.2b; and
- single leaf unreinforced masonry walls with return supports, must comply with Table 5.4.2b and Figure 5.4.2c.
- An engaged pier or return wall must be provided at both sides of an opening.
- The width of an opening must be not more than the spacing between the engaged piers unless the engaged piers either side of the opening are designed in accordance with AS 3700.
- Articulation joints must be located within 300 mm of vertical supports in accordance with 5.6.8.
- the building measured in the direction of the span of the roof is not more than 9 m and the height is not more than 2.7m; and
- engaged piers are provided that are in accordance with Tables 5.4.2c and 5.4.2d; and
- the roof does not place any spreading thrust onto the external walls; and
- the Class 10a building is located in an area with a wind class of not more than N2.
Element | Symbol used in Figure 5.4.2b | Thickness of wall (T) | |
---|---|---|---|
90 | 110 | ||
Pier size (minimum) (not more than N2) | A x B | 290 x 190 (800 spacing) | 350 x 230 (1150 spacing) |
Pier size (minimum) (not more than N3) | A x B | 290 x 290 (700 spacing) | 350 x 350 (1050 spacing) |
Spacing of returns (maximum) | S | 700 | 1050 |
Height (maximum) | H | 2400 | 2700 |
Table Notes
- Dimensions are in mm.
- Return supports are not required for 140 mm and 190 mm thick walls.
Element | Symbol used in Figure 5.4.2c | Thickness of wall (T) | |||
---|---|---|---|---|---|
90 | 110 | 140 | 190 | ||
Return length (minimum) | R | 450 | 450 | – | – |
Spacing of returns (maximum) (N2) | S | 1050 | 1300 | – | – |
Spacing of returns (maximum) (N3) | S | 600 | 750 | – | – |
Height (maximum) | H | 2400 | 2400 | 1700 (N2) | 2300 (N2) |
Table Notes
- Dimensions are in mm.
- Return supports are not required for 140 mm and 190 mm thick walls.
Wall thickness (mm) | Pier thickness (mm) | Pier width (mm) | Spacing (mm) for wind class | |
---|---|---|---|---|
N1 | N2 | |||
90 | 190 | 290 | 1000 | 600 |
90 | 290 | 190 | 1700 | 1200 |
90 | 290 | 290 | 2600 | 1800 |
110 | 230 | 230 | 1320 | 840 |
110 | 230 | 350 | 2040 | 1320 |
110 | 350 | 230 | 3240 | 2160 |
110 | 350 | 350 | 4920 | 3360 |
Wall thickness (mm) | Pier thickness (mm) | Pier width (mm) | Spacing (mm) for wind class | |
---|---|---|---|---|
N1 | N2 | |||
90 | 190 | 290 | 700 | 500 |
90 | 290 | 190 | 1300 | 900 |
90 | 290 | 290 | 2000 | 1400 |
110 | 230 | 230 | 960 | 600 |
110 | 230 | 350 | 1440 | 960 |
110 | 350 | 230 | 2520 | 1680 |
110 | 350 | 350 | 3840 | 2520 |
5.4.3
Internal walls
New for 2022
5.4.3
Internal walls
New for 2022
Internal masonry walls must be engaged with other walls, must comply with the relevant provisions of this Part and must be—
- not less than 75 mm thick; and
- supported by either—
- the ceiling structure in accordance with Figure 5.4.3a; or
- return walls in accordance with Figure 5.4.3b.
Explanatory information
A full height door frame or stud fastened at the roof framing and tied to the wall at 300 mm centres can be considered equivalent to a return wall.
5.4.4
Vertical articulation joints
New for 2022
5.4.4
Vertical articulation joints
New for 2022
Vertical articulation joints must be provided in accordance with 5.6.8.
5.4.5
Damp-proof courses and flashing materials
New for 2022
5.4.5
Damp-proof courses and flashing materials
New for 2022
Where required, damp-proof courses and flashing must be provided in accordance with 5.7.3 and 5.7.4.