Happy Holidays! We wish you a happy and safe holiday season. Please note that the ABCB office will be closed from 24 December 2024 until 2 January 2025.
(1) A separating wall between Class 1 buildings, or a wall that separates a Class 1 building from a Class 10a building which is not associated with the Class 1 building must—
(2) A wall required to have sound insulation must continue to—
the underside of the roof above; or
a ceiling that provides the sound insulation required for the wall.
Explanatory information
Insulation to reduce both airborne and impact noise transmission is required for parts of a wall that are common to adjoining Class 1 buildings but not parts of a wall located in the subfloor.
Rw is a measure of airborne sound insulation. Ctr is a spectrum adjustment factor that adjusts for low frequency sound levels. Ctr has been chosen in recognition of the problems caused by the high bass frequency outputs of modern home theatre systems and music reproduction equipment used by occupants of Class 1 buildings.
The wall configurations described in 10.7.5 to 10.7.8 are typical examples. Other proprietary methods are available via testing to AS/NZS ISO 717.1 for meeting the Rw + Ctr requirements of 10.7.1.
To achieve the appropriate level of sound insulation, walls must be constructed as follows:
Stud wall junction — junctions of sound insulated walls with any perimeter walls and roof cladding must be sealed in accordance with Figure 10.7.3a.
Masonry — units must be laid with all joints filled solid, except for articulation joints complying with 5.6.8, including those between the masonry and any adjoining construction.
Concrete panels — must have joints between panels and any adjoining construction filled solid.
Plasterboard sheeting —
If two layers are required, the second layer joints must not coincide with those of the first layer (see Figure 10.7.3b).
Joints between sheets including the outer layer or between sheets and any adjoining construction must be taped and filled solid.
Steel framed construction — steel framing and perimeter members must be installed as follows:
Steel framing members must be not less than 0.6 mm thick.
Studs must be not less than 63 mm in depth unless another depth is specified in 10.7.5 to 10.7.8.
All steel members at the perimeter of the wall must be securely fixed to the adjoining structure and the joints must be caulked so that there are no voids between the steel members and the wall.
Timber-framed construction — timber studs and perimeter members must be installed as follows:
Noggings and like members must not bridge between studs supporting different wall leaves.
All timber members at the perimeter of the wall must be securely fixed to the adjoining structure and the joints must be caulked so there are no voids between the timber members and the wall.
in the case of a water supply pipe that serves one dwelling, not be fixed to the wall leaf on the side of any other dwelling and have a clearance not less than 10 mm to the other wall leaf.
(3) Electrical outlets must be offset from each other—
in masonry walling, not less than 100 mm; and
in timber or steel-framed walling, not less than 300 mm.
has an Rw + Ctr of not less than 50, if constructed in accordance with Figure 10.7.5b.
(4) A single leaf of 110 mm clay brick masonry with—
a row of 70 mm x 35 mm timber studs or 64 mm steel studs at 600 mm centres, spaced 20 mm from the masonry wall; and
50 mm thick mineral insulation or glass wool insulation with a density of 11 kg/m3 positioned between studs; and
one layer of 13 mm plasterboard fixed to outside face of studs and outside face of masonry,
has an Rw + Ctr of not less than 50, if constructed in accordance with Figure 10.7.5c.
(5) A single leaf of 90 mm clay brick masonry with—
a row of 70 mm x 35 mm timber studs or 64 mm steels studs at 600 mm centres, spaced 20 mm from each face of the masonry wall; and
50 mm thick mineral insulation or glass wool insulation with a density of 11 kg/m3 positioned between studs in each row; and
one layer of 13 mm plasterboard fixed to studs on each outside face,
has an Rw + Ctr of not less than 50, if constructed in accordance with Figure 10.7.5d.
(6) A single leaf of 220 mm brick masonry with 13 mm cement render on each face has an Rw + Ctr of not less than 50, if constructed in accordance with Figure 10.7.5e.
Acceptable forms of construction for concrete walls
2019: Table 3.8.6.1b
(1) Acceptable forms of construction for concrete walls are set out in (2) to (5).
(2) 150 mm thick plain off form concrete, has an Rw + Ctr of not less than 50, if constructed in accordance with Figure 10.7.6a.
(3) 200 mm thick concrete panel with one layer of 13 mm plasterboard or 13 mm cement render on each face, has an Rw + Ctr of not less than 50, if constructed in accordance with Figure 10.7.6b.
(4) A 100 mm thick concrete panel with—
a row of 64 mm steel studs at 600 mm centres, spaced 25 mm from the concrete panel; and
80 mm thick polyester insulation or 50 mm thick glass wool insulation with a density of 11 kg/m3, positioned between studs; and
two layers of 13 mm plasterboard fixed to the outside face of studs and one layer of 13 mm plasterboard fixed to the outside face of the concrete panel,
has an Rw + Ctr of not less than 50, if constructed in accordance with Figure 10.7.6c.
(5) A 125 mm thick concrete panel with—
a row of 64 mm steel studs at 600 mm centres, spaced 20 mm from the concrete panel; and
70 mm polyester insulation with a density of 9 kg/m3, positioned between studs; and
one layer of 13 mm plasterboard fixed to the outside face of the studs,
has an Rw + Ctr of not less than 50, if constructed in accordance with Figure 10.7.6d.
Acceptable forms of construction for autoclaved aerated concrete walls
2019: Table 3.8.6.1c
(1) Acceptable forms of construction for autoclaved aerated concrete walls are set out in (2) to (4).
(2) A 75 mm thick autoclaved aerated concrete wall panel with—
a row of 64 mm steel studs at 600 mm centres, spaced 20 mm from the autoclaved aerated concrete wall panel; and
75 mm thick glass wool insulation with a density of 11 kg/m3 positioned between studs; and
one layer of 10 mm moisture resistant plasterboard or 13 mm fire protective grade plasterboard fixed to outside face of studs and outside face of autoclaved aerated concrete wall panel,
has an Rw + Ctr of not less than 50, if constructed in accordance with Figure 10.7.7a.
(3) A 75 mm thick autoclaved aerated concrete wall panel with—
a row of 64 mm steel studs at 600 mm centres, spaced 35 mm from the autoclaved aerated concrete panel wall; and
28 mm metal furring channels fixed to the outside face of the autoclaved aerated concrete wall panel, with 50 mm thick polyester insulation with a density of 9 kg/m3 positioned between furring channels and one layer of 13 mm fire protective grade plasterboard fixed to furring channels; and
105 mm thick glass wool insulation with a density of 7 kg/m3 positioned between studs; and
one layer of 13 mm fire protective grade plasterboard fixed to the outside face of the studs,
has an Rw + Ctr of not less than 50, if constructed in accordance with Figure 10.7.7b.
(4) Two leaves of 75 mm autoclaved aerated concrete wall panel with—
a cavity not less than 30 mm between panels containing 50 mm glass wool insulation with a density of 11 kg/m3; and
one layer of 10 mm plasterboard fixed to outside face of each panel,
has an Rw + Ctr of not less than 50, if constructed in accordance with Figure 10.7.7c.
Acceptable forms of construction for timber and steel framed walls
2019: Table 3.8.6.1d
(1) Acceptable forms of construction for timber and steel framed walls are set out in (2) and (3).
(2) Two rows of 90 mm x 35 mm timber studs or two rows of 64 mm steels studs at 600 mm centres with—
an air gap not less than 20 mm between the rows of studs; and
50 mm thick glass wool insulation or 60 mm thick polyester insulation with a density of 11 kg/m³, positioned between one row of studs, and
two layers of 13 mm fire protective grade plasterboard or one layer of 6 mm fibre cement sheet and one layer of 13 mm fire protective grade plasterboard, fixed to outside face of studs,
has an Rw + Ctr of not less than 50, if constructed in accordance with Figure 10.7.8a.
(3) Two rows of 64 mm steel studs at 600 mm centres with—
an air gap not less than 80 mm between the rows of studs; and
200 mm thick polyester insulation with a density of 14 kg/m3 positioned between studs; and
one layer of 13 mm fire-protective grade plasterboard and one layer 13 mm plasterboard on one outside face and one layer of 13 mm fire-protective grade plasterboard on the other outside face,
has an Rw + Ctr of not less than 50, if constructed in accordance with Figure 10.7.8b.