Happy Holidays! We wish you a happy and safe holiday season. Please note that the ABCB office will be closed from 24 December 2024 until 2 January 2025.
(1) Compliance with Part 7.5 for wall cladding is achieved if—
it is installed in accordance with—
7.5.2 for timber cladding, including weatherboards and profiled boards; and
7.5.3 for fibre-cement and hardboard wall cladding boards; and
7.5.4 for fibre-cement, hardboard and plywood sheet wall cladding; and
fibre-cement sheet eaves where provided, are installed in accordance with 7.5.5; and
openings and penetrations in cladding are flashed in accordance with 7.5.6; and
the bottom surface of the cladding terminates in accordance with 7.5.7; and
parapets, where provided, are capped in accordance with 7.5.8.
(2) Part 7.5 need not be complied with if H1D7(5) is complied with.
Explanatory information: Masonry wall cladding
Masonry wall cladding, including masonry veneer, is not covered by this Part but is covered by NCC Volume Two H1D5 and Section 5 of the ABCB Housing Provisions.
Explanatory information: Alternative wall cladding materials and systems
The provisions of this Part and those of NCC Volume Two H1D5 and Section 5 (Masonry) of the ABCB Housing Provisions do not cover all of the wall cladding materials that may be used for a Class 1 or Class 10 building.
(1) Timber wall cladding must be installed in accordance with (2), (3), (4) and (5).
(2) Splayed timber weatherboards must be fixed in accordance with Figure 7.5.2a and Figure 7.5.2b and with a lap not less than—
30 mm for hardwood, Cypress and treated pine; and
20 mm for Western Red Cedar; and
25 mm for Baltic Pine.
(3) Profiled timber boards must be—
fixed in a horizontal, vertical or diagonal direction with the overlap and groove closely fitted, where provided; and
with tongue and groove profile, fixed with tongue edge up, where they are fixed in a horizontal or diagonal direction; and
where fixed in a vertical or diagonal direction, provided with a vapour permeable sarking complying with AS 4200.1 (see Figure 7.5.2c) installed behind boards with—
each adjoining sheet or roll being—
overlapped not less than 150 mm; or
taped together; and
sarking fixed to supporting members at not more than 300 mm centres.
(4) Splayed and profiled timber weatherboards must be fixed in accordance with Table 7.5.2, with—
one fixing at each stud or equivalent framing member for splayed timber weatherboards; and
one fixing provided at each stud or equivalent framing member for profiled timber boards not more than 130 mm wide; and
two fixings provided at each stud or equivalent framing member for profiled timber board more than 130 mm wide; and
fixings located so that the fixing does not penetrate the tip or thinner edge of the board beneath.
(5) Fixings used for timber cladding must comply with the following:
Where fixings are punched or countersunk and filled prior to painting, fixings must be standard steel flat head nails or standard steel self embedding head screws.
Uncoated copper or steel fixings must not be used for Western Red Cedar (silicon bronze, monel metal, stainless steel or hot-dipped galvanised are suitable).
Where the building is located within 200 m of breaking surf, fixings must be—
stainless steel when fixed into timber framing members; or
hot-dipped galvanized (min 600 g/m2) when fixed into steel framing members.
In all other cases, fixings must be hot-dipped galvanised (min. 600 g/m2) flat head nails or hot dipped galvanised (min 600 g/m2) self embedding head or wafer head screws.
Table 7.5.2 Fixing requirements—Splayed and profiled timber weatherboards
Wind class
Maximum stud spacing (mm)
Minimum nominal stud fixings
N1 - N3
600
Timber: 2.8 G or (8-18) S
Steel: (8-18) S
Table Notes
G = galvanised plain shank, threaded or equivalent nails.
S = self embedding head or wafer head screw.
Fasteners must penetrate not less than 30 mm into timber frames and not less than two full screw threads through steel frames.
Wall cladding may be fixed through timber or metal battens attached to the wall frame in accordance with AS 1684.2, AS 1684.3, AS 1684.4 or NASH standard as appropriate (see fixing requirements for roof battens) so long as the minimum penetration into the wall frame is achieved.
Steel framing members must have a base metal thickness (BMT) not less than that required for a roof batten in NASH standard.
Explanatory information: Fixing of wall cladding
7.5.2(4)(d) ensures the fixing of the wall cladding does not split the wall cladding board below. For example, for a 30 mm lap, fix 35 mm from the butt or 5 mm above the corresponding overlapping board (see Figure 7.5.2a).
Explanatory information: Timber cladding profiles
7.5.2 covers the following types of timber cladding profiles:
Horizontal bevel-back.
Horizontal rebated bevel-back.
Horizontal rusticated.
Vertical and horizontal shiplap.
Tongue and groove.
Explanatory information: Machine and hand driven nails
Table 7.5.2 applies to both machine and hand driven nails.
Fasteners must penetrate not less than 30 mm into timber frames and not less than two full screw threads through steel frames.
Steel framing members must have a base metal thickness (BMT) not less than that required for a roof batten in NASH standard.
Wall cladding may be fixed through timber or metal battens attached to the wall frame in accordance with AS 1684.2, AS 1684.3, AS 1684.4 or NASH standard as appropriate (see fixing requirements for roof battens) so long as the minimum penetration into the wall frame is achieved.
Fasteners must penetrate not less than 30 mm into timber frames and not less than two full screw threads through steel frames.
Steel framing members must have a base metal thickness (BMT) not less than that required for a roof batten in NASH standard.
Wall cladding may be fixed through timber or metal battens attached to the wall frame in accordance with AS 1684.2, AS 1684.3, AS 1684.4 or NASH standard as appropriate (see fixing requirements for roof battens) so long as the minimum penetration into the wall frame is achieved.
Explanatory information
Where the wall cladding boards contain a shiplap join as opposed to a lapped join, 7.5.3(d) does not apply, and the joins between the boards are required to have the overlap and groove closely fitted.
Table 7.5.4a Stud and fixing spacings for 6 mm fibre-cement sheet wall cladding
Wind class
Maximum stud spacing (mm)
Maximum nail spacing within 1.2 m of the external corners of the building (mm) Note 1
Maximum nail spacing elsewhere (mm) Note 1
N1
≤ 1.2 m of external building corners: 600 Elsewhere: 600
Body: 300, Edges: 200
Body: 300, Edges: 200
N2
≤ 1.2 m of external building corners: 600 Elsewhere: 600
Body: 200, Edges: 200
Body: 300, Edges: 200
N3
≤ 1.2 m of external building corners: 450 Elsewhere: 600
Body: 200, Edges: 200
Body: 200, Edges: 200
Table Notes
Maximum nail spacing using 2.8 mm fibre-cement nails.
Fixings must be located not less than 50 mm from the edge of all corners.
Fasteners must penetrate not less than 30 mm into a timber frame.
Wall cladding may be fixed through timber or metal battens attached to the wall frame in accordance with AS 1684.2, AS 1684.3, AS 1684.4 or NASH standard as appropriate (see fixing requirements for roof battens) so long as the minimum penetration into the wall frame is achieved.
Table 7.5.4b Stud and fixing spacings for 9.5 mm thick hardboard sheet wall cladding
Wind class
Maximum stud spacing (mm)
Maximum nail spacing within 1.2 m of the external corners of the building (mm) Note 1
Maximum nail spacing elsewhere (mm) Note 1
N1
600
Body: 300, Edges: 150
Body: 300, Edges: 150
N2
600
Body: 300, Edges: 150
Body: 300, Edges: 150
N3
600
Body: 300, Edges: 150
Body: 300, Edges: 150
Table Notes
Maximum nail spacing using 2.8 mm galvanised clouts or flat head nails.
Fixings must be positioned a minimum of 12 mm from the edge of the sheet and not less than 50 mm from the edge of all corners.
Fasteners must penetrate not less than 30 mm into the timber frame.
Wall cladding may be fixed through timber or metal battens attached to the wall frame in accordance with AS 1684.2, AS 1684.3, AS 1684.4 or NASH standard as appropriate (see fixing requirements for roof battens) so long as the minimum penetration into the wall frame is achieved.
Table 7.5.4c Stud and fixing spacings for plywood wall cladding equal to or greater than 6.5 mm thick
Wind class
Maximum stud spacing (mm)
Maximum nail spacing within 1.2 m of the external corners of the building (mm) Note 1
Maximum nail spacing elsewhere (mm) Note 1
N1
600
Body: 200, Edges: 100
Body: 200, Edges: 150
N2
600
Body: 200, Edges: 100
Body: 200, Edges: 150
N3
600
Body: 150, Edges: 100
Body: 200, Edges: 150
Table Notes
Maximum nail spacing using 2.8 mm or 3.5 mm galvanised clouts or flat head nails.
Fixings must be positioned a minimum of 12 mm from the edge of the sheet and not less than 50 mm from the edge of all corners.
Fasteners must penetrate not less than 30 mm into the timber frame
Wall cladding may be fixed through timber or metal battens attached to the wall frame in accordance with AS 1684.2, AS 1684.3, AS 1684.4 or NASH standard as appropriate (see fixing requirements for roof battens) so long as the minimum penetration into the wall frame is achieved.
Explanatory information
Where sheet bracing is also acting as structural bracing, fixing requirements are listed in AS 1684 and NASH Standard – Residential and Low-Rise Steel Framing, Part 2.
Openings in external wall cladding exposed to the weather must be flashed with materials complying with AS/NZS 2904 and in accordance with the following:
Flashings must be provided to bottom, tops and sides of openings, except as permitted by (d), and must be installed so that the flashing—
extends not less than 110 mm beyond the reveals on each side of the opening where practicable; and
overlap by not less than 75 mm in the direction of flow; and
be securely fastened at intervals of not more than 40 mm; and
have sealant installed between laps.
The method of flashing must be suitable for the framing and cladding used and any reveal for the window or door system or any architrave or finishing trims that may be installed.
The top of an opening need not be flashed where it is adequately protected by an eave of a width more than 3 times the height of the cladding above the opening (See Figure 7.5.6).
Flashings must be securely fixed at least 25 mm under the cladding and extend over the ends and edges of the framing of the opening.
Explanatory information
7.5.6(a)(i) applies ‘where practicable’ because it is often impractical to extend the flashing 110 mm beyond the reveal; for example, where openings are positioned adjacent to a corner or where two windows are within 110 mm of each other. In such cases consideration should be given to ensure the flashing prevents the penetration of water into the external wall.
50 mm above impermeable (paved or concreted) areas that slope away from the building in accordance with 3.3.3(a); or
150 mm in any other case.
(2) Wall cladding must extend a minimum of 50 mm below the bearer or lowest horizontal part of the suspended floor framing.
Explanatory information
The required clearances under 7.5.7 may also be subject to other requirements for drainage in Part 3.3, clearances for inspection zones for termite management in Part 3.4 and screening and sealing of gap requirements for construction in designated bushfire prone areas in H7D4, where appropriate.
Where a wall cladding is used to form a parapet wall, the cladding must be attached to a supporting frame and have a capping installed that complies with the following:
Cappings must—
be purpose made, machine-folded sheet metal or equivalent sections of a material compatible with all up and downstream metal roof covering materials in accordance with 7.2.2(2); and
extend not less than 50 mm down the sides of the parapet; and
be separated from the supporting framing by a vapour permeable sarking installed in accordance with (f); and
be fixed with either self drilling screws or rivets with rubber washers at intervals of not more than 500 mm that do not penetrate the top of cappings, except at joints and corners.
The top of the capping must slope a minimum of 5 degrees.
Joints in cappings must—
overlap by not less than 50 mm in the direction of flow; and
be securely fastened at intervals of not more than 40 mm; and
have sealant installed between laps.
Fixing for cappings must be compatible with the capping material in accordance with 7.2.2.
Lead cappings must not be used with prepainted steel or zinc/aluminium steel or on any roof if the roof is part of a drinking water catchment area.
Sarking must comply with AS 4200.1 and be installed behind all wall cladding where parapets are installed, with—
each adjoining sheet or roll being—
overlapped not less than 150 mm; or
taped together; and
sarking fixed to supporting members at not more than 300 mm centres.
Explanatory information
For the purposes of 7.5.8(f), sarking is required to be installed to the whole external wall which contains the parapet and extend to the top and back of the parapet. A gap should be provided between the sarking and the parapet capping to help control condensation.