NCC 2019 Volume One Amendment 1
Search the National Construction Code editions
Section E Services and equipment
Occupancy | Where sprinklers are required |
---|---|
Residential care building (Vic) | Throughout the building. |
Shared accommodation building | Throughout the building. |
Notes to Vic Table E1.5:
Subject to this Specification, an automatic fire sprinkler system must comply with—
for a Class 5, 6, 7, 8 or 9b building: AS 2118.1; or
for a Class 2, 3, 4, 9a or 9c building: AS 2118.1, except clause 5.9.10 of AS 2118.1 does not apply and is replaced with 'Covered balconies shall be sprinkler protected.'; or
for a Class 2 or 3 building with an effective height of not more than 25 m and a rise in storeys of 4 or more: Specification E1.5a and the relevant provisions of this Specification as applicable; or
for Class 4, 5, 6, 7, 8, 9a (other than a residential care building (Vic)) or 9b parts of a building less than 25 m in effective height, which also contains Class 2 or 3 parts: a sprinkler system in accordance with Specification E1.5a as for a Class 2 or 3 building and the relevant provisions of this Specification except—
a FPAA101D sprinkler system cannot be used where the Class 4, 5, 6, 7, 8, 9a (other than a residential care building (Vic)) or 9b parts—
contain more than 2 storeys;
are more than 25% of the total floor area of the building;
are located above the fourth storey; and
an FPAA101D or FPAA101H sprinkler system cannot be used where the Class 7a part (other than an open deck carpark) accommodates more than 40 vehicles; or
for a Class 2 or 3 building with a rise in storeys of not more than 3: AS 2118.4 as applicable; or
for a combined sprinkler and fire hydrant system: AS 2118.6; or
for a Class 9a health-care building used as a residential care building (Vic): AS 2118.4 as applicable; or
for a Class 9c building: AS 2118.4 as applicable.
2. System requirements
A required automatic fire sprinkler system installed in a Class 2 or 3 building with an effective height of not more than 25 m and a rise in storeys of 4 or more must comply with—
AS 2118.1 except clause 5.9.10 of AS 2118.1 does not apply and is replaced with 'Covered balconies shall be sprinkler protected'; or
AS 2118.4, as applicable; or
FPAA101D—
except for residential care buildings (Vic); and
except that clause 2.2.1 of FPAA101D applies as if the first paragraph is replaced with 'Covered balconies shall be sprinkler protected'; or
FPAA101H—
except for residential care buildings (Vic); and
except that clause 3.5.2.8 of FPAA101H applies as if the first paragraph is replaced with 'Covered balconies shall be sprinkler protected'; and
except that clause 3.5.3 of FPAA101H applies as if it is replaced with—
"3.5.3 Class 5, 6, 7, 8 and 9 parts of the building
The location and spacing of sprinklers in Class 5, 6, 7, 8 and 9b parts of the building shall be in accordance with Section 5 of AS 2118.1:2017.
The location and spacing of sprinklers in Class 9a and 9c parts of the building shall be in accordance with Section 5 of AS 2118.1:2017 except that clause 5.9.10 of AS 2118.1 does not apply and is replaced with 'Covered balconies shall be sprinkler protected'.".
In a Class 9c building—
if the building accommodates more than 20 residents, manual call points must be installed in paths of travel so that no point on a floor is more than 30 m from a manual call point; and
indication of the zone where the smoke detection system has actuated must be achieved by one of the following:
remote automatic indication of each zone must be given in each smoke compartment; and
indication of (aa) must be indicated on remote annunciator panels with alpha-numeric displays with a minimum of 20 characters of 9 mm minimum height; or
indication of the zone where the smoke detection system has actuated must be communicated via a suitable interface with the fire indicator panel to a portable remote communication device; and
at least one such portable remote communication device per smoke compartment must be provided to staff nominated by the owner or operator and properly instructed as to the duties and responsibilities involved; and
the portable remote communication device may be a pager with alpha-numeric display or portable telephone handset with capability of receiving alpha-numeric display.
Substitute Clause 8(b) and (c) of Specification E2.2a as follows:
A smoke detection system in a Class 9a health-care building, if the building accommodates more than 20 patients, unless the building is sprinklered and the sprinkler system is permanently connected to a fire station, or other approved monitoring service with a direct data link to a fire station, in accordance with Practice Note 07-2018.
(deleted).