NCC 2019 Volume One Amendment 1
Search the National Construction Code editions
Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements EP4.1 to EP4.3 are satisfied by complying with—
E4.1 to E4.9; and
in a building in an alpine area, Part G4; and
for a building containing an occupiable outdoor area, Part G6; and
for additional requirements for Class 9b buildings, Part H1; and
for farm buildings and farm sheds, Part H3.
Where a Performance Solution is proposed, the relevant Performance Requirements must be determined in accordance with A2.2(3) and A2.4(3) as applicable.
To clarify that compliance with EP4.1 to EP4.3 will be achieved by compliance with E4.1 to E4.9 in the case of all buildings, Part G3 in the case of buildings with an atrium, Part G4 in the case of buildings in alpine areas, Part G6 in the case of occupiable outdoor areas,Part H1 in the case of theatres, stages and public halls and Part H3 for farm buildings and farm sheds.
Where a solution is proposed to comply with the Deemed-to-Satisfy Provisions, E4.0 clarifies that, for most buildings, if compliance can be demonstrated with E4.1 to E4.9, then compliance has been achieved with EP4.1 to EP4.3. The exceptions to this general rule are as follows:
Where a Performance Solution is proposed, the relevant Performance Requirements must be determined in accordance with A2.2(3) and A2.4(3) as applicable. (See commentary on Part A2).
This clause has deliberately been left blank.
In accordance with the decision not to change the numbering of the BCA from that of the previous edition, the space previously occupied by this provision has been left blank. The previous E4.1 provisions are now located in the BCA Performance Requirements.
An emergency lighting system must be installed—
in every fire-isolated stairway, fire-isolated passageway or fire-isolated ramp; and
in every storey of a Class 5, 6, 7, 8 or 9 building where the storey has a floor area more than 300 m2—
in every passageway, corridor, hallway, or the like, that is part of the path of travel to an exit; and
in any room having a floor area more than 100 m2 that does not open to a corridor or space that has emergency lighting or to a road or open space; and
in any room having a floor area more than 300 m2; and
in every passageway, corridor, hallway, or the like, having a length of more than 6 m from the entrance doorway of any sole-occupancy unit in a Class 2 or 3 building or Class 4 part of a building to the nearest doorway opening directly to—
an external stairway serving instead of a fire-isolated stairway under D1.8; or
an external balcony leading to a fire-isolated stairway, fire-isolated passageway or fire-isolated ramp; or
a road or open space; and
in every required non-fire-isolated stairway; and
in a sole-occupancy unit in a Class 5, 6 or 9 building if—
the floor area of the unit is more than 300 m2; and
an exit from the unit does not open to a road or open space or to an external stairway, passageway, balcony or ramp, leading directly to a road or open space; and
in every room or space to which there is public access in every storey in a Class 6 or 9b building if—
the floor area in that storey is more than 300 m2; or
any point on the floor of that storey is more than 20 m from the nearest doorway leading directly to a stairway, ramp, passageway, road or open space; or
in a Class 9a health-care building—
in every passageway, corridor, hallway, or the like, serving a treatment area or a ward area; and
in every room having a floor area of more than 120 m2 in a patient care area; and
in every Class 9c building excluding within sole-occupancy units; and
in every required fire control centre.
To minimise the risk of death or injury to occupants during an emergency because of an inability to see their way along an exit path of travel.
See the comment on EP4.1.
E4.2 sets out the locations in buildings, and in some cases the classes of building, in which emergency lighting must be installed.
Each sub-provision of E4.2 must be considered separately. It is possible that more than one may apply to any single building. Where any sub-provision requires emergency lighting, such lighting must be provided, even though another sub-provision may appear to provide an exemption.
Consider a single storey building comprised of three open plan Class 6 sole-occupancy units of 150 m2 each, where each sole-occupancy unit has one exit direct to open space:
In this case, as E4.2(f) requires emergency lighting, such lighting must be provided despite the fact that the sole-occupancy units do not require such lighting under E4.2(e).
Emergency lighting is required to be installed in all fire-isolated exits, because it is unusual for them to be provided with sufficient amounts of natural lighting for safe evacuation.
Emergency lighting is required in every storey with a floor area over 300 m2 in a Class 5–9 building, as follows:
Emergency lighting is required in any passageway, corridor, hallway, or the like in Class 2 and Class 3 buildings and Class 4 parts, if the distance of travel from the door leading from a sole-occupancy unit is greater than six metres to:
This provision reflects the likelihood that such buildings will be occupied at night, when the occupants are likely to be asleep.
Emergency lighting is required to be installed in all required non-fire-isolated stairways (note that E4.2(d) applies even if the other provisions of E4.2 do not require the installation of emergency lighting).
Emergency lighting is required to be installed in a sole-occupancy unit of a Class 5, Class 6 or Class 9 building if:
Emergency lighting is required to be installed in every publicly accessible room or space in a Class 6 or Class 9b building if:
This provision reflects the likelihood that such buildings are used by large numbers of the public who do not have any knowledge of the building or its exits.
Emergency lighting is required to be installed in the specified areas in Class 9a buildings, because such buildings are used by patients who may require assistance to evacuate.
Emergency lighting is required to be installed throughout Class 9c buildings excluding within the sole-occupancy units. The requirement is generally aligned with the principles for emergency lighting in Class 9a buildings as described above.
Emergency lighting is required to be installed in required fire control centres, because they are designed for use by the fire brigade during an emergency, such as a fire.
Distances, other than vertical rise, must be measured along the shortest path of travel whether by straight lines, curves or a combination of both.
To clarify how distance must be measured for the purposes of emergency lighting required under E4.2.
See the comment on EP4.1.
While not specifically stated, the intention is that the distances referred to in E4.3 to be those calculated in accordance with E4.2(c) and (f)(ii).
The E4.2(c) and (f)(ii) distances are required to be measured the same way as those specified in Section D. See D1.15.
Every required emergency lighting system must comply with AS/NZS 2293.1.
To specify how an emergency lighting system must operate, to minimise the risk of death or injury to occupants during an emergency because of an inability to see their way along an exit path of travel.
See the comment on EP4.1.
An emergency lighting system must provide the visual conditions necessary for safe evacuation during an emergency such as a fire. It must be installed in accordance with AS/NZS 2293.1.
It should be noted that this is an emergency lighting system which is only required to operate during an emergency. F4.4(a)(i) requires artificial lighting to be provided within required stairways, passageways and ramps, but does not require such lighting to be illuminated at all times.
An exit sign must be clearly visible to persons approaching the exit, and must be installed on, above or adjacent to each—
door from an enclosed stairway, passageway or ramp at every level of discharge to a road or open space; and
horizontal exit; and
To minimise the risk of death or injury to occupants during an emergency because of an inability to find an exit.
See the comment on EP4.1.
E4.5 sets out the locations in a building requiring the installation of exit signs. Signs must be clearly visible to occupants approaching the exit. They need to be located on, above or adjacent to the specified exits and doors.
If an exit is not readily apparent to persons occupying or visiting the building then exit signs must be installed in appropriate positions in corridors, hallways, lobbies, and the like, indicating the direction to a required exit.
To minimise the risk of death or injury to occupants during an emergency because of an inability to find their way along an exit path of travel.
Exits may not be visible from all locations within a building. In such cases, exit signs with directional indicators (such as arrows) are required to clearly indicate the direction of travel to required exits.
E4.5 does not apply to—
a Class 2 building in which every door referred to is clearly and legibly labelled on the side remote from the exit or balcony—
with the word “EXIT” in capital letters 25 mm high in a colour contrasting with that of the background; or
by some other suitable method; and
an entrance door of a sole-occupancy unit in a Class 2 or 3 building or Class 4 part of a building.
To specify some circumstances where risk levels do not warrant compliance with E4.5.
The BCA considers that the risks to occupants of units within a Class 2 building are less than those to occupants of Class 3 buildings and Class 4 parts. This is because occupants of Class 2 buildings are assumed to be more familiar with:
Consequently, E4.7(a) grants an exemption for Class 2 buildings from the need to comply with E4.5, on the condition that the buildings comply with certain specific provisions.
With regard to E4.7(a)(i), while the size and wording of the exit sign are specified, the structure, method of attachment, or colour and the like are not specified. However, the colour of the word must contrast with that of the background. The building proponent can make this decision as long as the appropriate authority is satisfied.
With regard to E4.7(a)(ii), if a suitable alternative means of notification can be found to the requirements of E4.7(a)(i), it may be used. The decision is made by the building proponent, who must satisfy the appropriate authority.
The BCA assumes that the occupants of units in Class 2 or Class 3 buildings, or in Class 4 parts of a building are familiar with the layouts of their units to allow E4.7(b) to grant an exemption so that exit signs are not required above what is described as the “entrance door”, being either:
Every required exit sign must comply with—
AS/NZS 2293.1; or
for a photoluminescent exit sign, Specification E4.8; and
be clearly visible at all times when the building is occupied by any person having the right of legal entry to the building.
To specify how exit signs must be designed and operate, to minimise the risk of death or injury to occupants during an emergency because of an inability to find an exit.
E4.8 sets out the provisions for required exit signs, which must meet the following criteria:
An emergency warning and intercom system complying where applicable with AS 1670.4 must be installed—
in a building with an effective height of more than 25 m; and
in a Class 3 building having a rise in storeys of more than 2 and used as—
the residential part of a primary or secondary school; or
accommodation for the aged, children or people with a disability; and
in a Class 3 building used as a residential care building, except that the system—
must be arranged to provide a warning for occupants; and
in areas used by the residents, may have its alarm adjusted in volume and content to minimise trauma consistent with the type and condition of residents; and
in a Class 9a building having a floor area of more than 1000 m2 or a rise in storeys of more than 2, and the system—
must be arranged to provide a warning for occupants; and
in a ward area, may have its alarm adjusted in volume and content to minimise trauma consistent with the type and condition of patients; and
in a Class 9b building—
used as a school and having a rise in storeys of more than 3; or
used as a theatre, public hall, or the like, having a floor area more than 1000 m2 or a rise in storeys of more than 2.
To minimise the risk of death or injury to occupants through lack of knowledge that an emergency exists or an evacuation is required.
See the comment on EP4.3.
E4.9 sets out the types of buildings requiring the installation of an emergency warning and intercom system.
Building proposals using the Deemed-to-Satisfy Provisions to achieve the Performance Requirements must comply with AS 1670.4, where applicable.
In a building with an effective height of more than 25 metres, if a fire starts on one floor, there is a considerable risk that occupants of the other floors might not be aware it has started. Co-ordination of the evacuation process is important. This reduces confusion and congestion in the stairways and accordingly the time taken for the evacuation.
In a building fire, the highest degree of risk is attached to such people as the very young, people with certain types of disability (such as a mobility disability), the elderly, and those asleep.
The BCA cannot address all possible permutations of people who are likely to be in any particular building. Nonetheless, it does attempt to address the risks that are most likely to be attached to the people most likely to be in particular types of building.
In most cases, the need to install an emergency warning and intercom system only applies to larger buildings. The reason for this requirement is the heightened risk that occupants may not be aware of a fire in another part of the building.
In Class 3 residential care buildings and in Class 9a buildings, many of the occupants or patients are unable to evacuate without assistance. There is also an enhanced risk in many of these buildings that residents or patients will be traumatised by loud or insistent alarms. To minimise this risk, the sound system and intercom system: