NCC 2019 Volume One Amendment 1
Search the National Construction Code editions
Part E1 Fire fighting equipment
A fire hose reel system must be installed to the degree necessary to allow occupants to safely undertake initial attack on a fire appropriate to—
the size of the fire compartment; and
the function or use of the building; and
any other fire safety systems installed in the building; and
the fire hazard.
The Objective of this Part is to—
safeguard occupants from illness or injury while evacuating during a fire; and
provide facilities for occupants and the fire brigade to undertake fire-fighting operations; and
prevent the spread of fire between buildings.
If a fire occurs in a building it must not endanger evacuating occupants or spread to another building.
Facilities to fight a fire in its early stagesSimple and lightweight equipment allows occupants to attack a fire during its early stages. Provision of this equipment often helps occupants to either extinguish or limit the development of a fire before the fire brigade arrives.
Facilities to assist the fire brigadeTo assist in stopping or limiting the spread of fire, facilities must be provided to assist the fire brigade.
A building is to be provided with fire-fighting equipment to safeguard against fire spread—
to allow occupants time to evacuate safely without being overcome by the effects of fire; and
so that occupants may undertake initial attack on a fire; and
so that the fire brigade have the necessary equipment to undertake search, rescue, and fire-fighting operations; and
to other parts of the building; and
between buildings.
Suitable facilities to be installed
Suitable facilities may need to be installed in a building to minimise the risk of fire spread to:
Facilities may be manually or automatically operated ,and include :fire hydrants ;fire hose reels; sprinkler systems; portable fire extinguishers.
Buildings may incorporate afire-control centre.
Fire hose reels in buildings allow occupants to fight a fire. The fire may be in its infancy, and early control or extinguishment may reduce the hazard, allow more time for evacuation and prevent structural damage.
See the explanation of this term in A1.0(3)(c).
As set out in EP1.1, fire hose reels must be installed when necessary, and be appropriate to a number of factors, including:
E1.4 provides a number of examples where fire hose reels must be installed if the proposal being considered involves a solution which uses the Deemed-to-Satisfy Provisions.
If a Performance Solution is used, it may be appropriate to assess it using E1.4 for guidance purposes. However, it is stressed that compliance with E1.4 is not compulsory if alternative means can be found to satisfy the appropriate authority that the Performance Requirements will be achieved.
Fire extinguishers must be installed to the degree necessary to allow occupants to undertake initial attack on a fire appropriate to—
the function or use of the building; and
any other fire safety systems installed in the building; and
the fire hazard.
Fire extinguishers in buildings allow occupants to fight fires. Extinguishment may complete all the functions listed in EP1.1 above.
Fire extinguishers should be located in plain view, along normal paths of travel and near exits where possible. They should not be located in hazardous places.
This expression’s use in EP1.2 indicates that the BCA recognises that not all buildings need fire extinguishers; and fire extinguishers are used for specific purposes, as set out in AS 2444.
Any decision made in this context can extend to not requiring an item to be installed or a particular level of performance to be achieved, if that is the appropriate action to be taken.
As set out in EP1.2, fire extinguishers must be installed when necessary, and be appropriate to a number of factors, including:
Table E1.6 provides a number of examples where fire extinguishers must be installed if the proposal being considered involves a solution which uses the Deemed-to-Satisfy Provisions.
If a Performance Solution is being used, it may be appropriate to assess it using Table E1.6 for guidance purposes. However, it is stressed that compliance with Table E1.6 is not compulsory if alternative means can be found to satisfy the appropriate authority that the Performance Requirements will be achieved.
A fire hydrant system must be provided to the degree necessary to facilitate the needs of the fire brigade appropriate to—
fire-fighting operations; and
the floor area of the building; and
the fire hazard.
EP1.3 only applies to a building where a fire brigade is available to attend.
The intent of installing a fire hydrant system is to provide adequate water, under sufficient pressure and flow, to allow the fire brigade to fight fires.
Under its Application provision, EP1.3 only applies to buildings located in an area serviced by a fire brigade. This is primarily because the pressures and flows from a fire hydrant are such that hydrants should only be used by the fire brigade.
It is expected that designers will meet any special fire brigade requirements, which may cover such matters as the types of couplings and special flows and pressures to suit a particular nozzle.
The use of the expression “to the degree necessary” in EP1.3 indicates that the BCA recognises that not all buildings need fire hydrants.
Any decision made in this context can extend to not requiring an item to be installed or a particular level of performance to be achieved, if that is the appropriate action to be taken.
As set out in EP1.3, a fire hydrant system must be installed when necessary, and be appropriate to a number of factors, including:
E1.3 provides a number of examples where fire hydrants must be installed if the proposal being considered involves a solution which uses the Deemed-to-Satisfy Provisions.
If a Performance Solution is used, it may be appropriate to assess it using E1.3 for guidance purposes. However it is stressed that compliance with E1.3 is not compulsory if alternative means can be found to satisfy the appropriate authority that the Performance Requirements will be achieved.
An automatic fire suppression system must be installed to the degree necessary to control the development and spread of fire appropriate to—
the size of the fire compartment; and
the function or use of the building; and
the fire hazard; and
the height of the building.
A sprinkler system is only one type of automatic fire suppression system. EP1.4 is not limited to sprinkler systems. If it can be demonstrated that another automatic fire system can control the development and spread of a fire, it may comply with EP1.4. Its activation must be “automatic” and must not depend on human intervention.
Automatic fire suppression systems, such as sprinkler systems, are normally used in a building to contain and extinguish fire. When an automatic fire suppression system operates, it not only controls or limits the fire development, but statistics show that, in most cases, the fire is extinguished before the fire brigade arrives at the building.
An automatic fire suppression system is regarded as part of a building’s life safety package because:
The use of the expression “to the degree necessary” in EP1.4 indicates that the BCA recognises that not all buildings need an automatic fire suppression system.
Any decision made in this context can extend to not requiring an item to be installed or particular level of performance to be achieved, if that is the appropriate action to be taken.
As set out in EP1.4, an automatic fire suppression system, such as a sprinkler system, must be installed when necessary, and be appropriate to a number of factors.
When implementing, the likely size and intensity of a fire should be taken into consideration. This can be as measured by:
E1.5 provides a number of examples where a sprinkler system must be installed if the proposal being considered involves a solution which uses the Deemed-to-Satisfy Provisions.
If a Performance Solution to the Deemed-to-Satisfy Provisions in Part E1 is being used, it may be appropriate to assess it using E1.5 for guidance purposes. However, it is stressed that compliance with E1.5 is not compulsory if alternative means can be found to satisfy the appropriate authority that the Performance Requirements will be achieved.
Suitable means of fire-fighting must be installed to the degree necessary in a building under construction to allow initial fire attack by construction workers and for the fire brigade to undertake attack on the fire appropriate to—
the fire hazard; and
the height the building has reached during its construction.
A fire in a building under construction represents a significant public safety, health and amenity risk. Accordingly, there is a need for firefighting in such buildings.
This Performance Requirement recognises the fact that a significant number of fires occur in buildings during their construction or major refurbishment. Statistics indicate that a number of fires have been started by sparks. The fire has then spread because services were turned off for construction purposes.
The use of the expression “to the degree necessary” in EP1.5 indicates that the BCA recognises that not all buildings need firefighting services during construction.
Any decision made in this context can extend to not requiring an item to be installed or a particular level of performance to be achieved, if that is the appropriate action to be taken.
As set out in EP1.5, firefighting services must be installed in buildings under construction when necessary, and must be appropriate to a number of factors, including:
E1.9 provides a number of examples where firefighting services must be installed if the proposal being considered involves a solution which uses the Deemed-to-Satisfy Provisions.
If a Performance Solution to the Deemed-to-Satisfy Provisions in Part E1 is being used, it may be appropriate to assess it using E1.9 for guidance purposes. However, it is stressed that compliance with E1.9 is not compulsory if alternative means can be found to satisfy the appropriate authority that the Performance Requirements will be achieved.
Suitable facilities must be provided to the degree necessary in a building to co-ordinate fire brigade intervention during an emergency appropriate to—
the function or use of the building; and
the floor area of the building; and
the height of the building.
EP1.6 requires that a part of a building be set aside for the fire brigade to co-ordinate its search and rescue, and firefighting operations during a fire. These areas are referred to as “fire control centres”.
The use of the expression “to the degree necessary” in EP1.6 indicates that the BCA recognises that not all buildings need a fire control centre.
Any decision made in this context can extend to not requiring an item to be installed or a particular level of performance to be achieved, if that is the appropriate action to be taken.
As set out in EP1.6, co-ordination facilities must be installed when necessary, and be appropriate to a number of factors, including:
E1.8 provides a number of examples where a fire control centre must be installed if the proposal being considered involves a solution which uses the Deemed-to-Satisfy Provisions.
If a Performance Solution to the Deemed-to-Satisfy Provisions in Part E1 is being used, it may be appropriate to assess it using E1.8 for guidance purposes. However, it is stressed that compliance with E1.8 is not compulsory if alternative means can be found to satisfy the appropriate authority that the Performance Requirements will be achieved.