NCC 2019 Volume One Amendment 1
Search the National Construction Code editions
Part G3 Atrium construction
This Part does not apply to an atrium which—
connects only 2 storeys; or
connects only 3 storeys if—
each storey is provided with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification E1.5 throughout; and
one of those storeys is situated at a level at which there is direct egress to a road or open space.
The Objectives and Functional Statements for Part G3 are contained in Sections C, D and E of this Guide. The Performance Requirements for Part G3 are in Sections C, D and E. Part G3 contains additional Deemed-to-Satisfy Provisions for buildings that contain an atrium.
The Objectives and Functional Statements for Part G3 are contained in Sections C, D and E of this Guide. The Performance Requirements for Part G3 are in Sections C, D and E. Part G3 contains additional Deemed-to-Satisfy Provisions for buildings that contain an atrium.
The Objectives and Functional Statements for Part G3 are contained in Sections C, D and E of this Guide. The Performance Requirements for Part G3 are in Sections C, D and E. Part G3 contains additional Deemed-to-Satisfy Provisions for buildings that contain an atrium.
To clarify which atriums must comply with Part G3.
The BCA defines the term “atrium”. It is important to understand this BCA definition before considering Part G3. See definition in Schedule 3.
Part G3 does not apply to an atrium if it connects two storeys in a non-sprinkler protected building, or up to three storeys if each of the connected storeys is sprinkler protected and one of those storeys is at a level giving egress to a road or open space.
This provision is consistent with D1.12, which deals with the number of floors that can be connected by a non-required non-fire-isolated stairway, ramp or escalator.
An atrium well must have a width throughout the well that is able to contain a cylinder having a horizontal diameter of not less than 6 m.
To minimise the risk that radiant heat from a fire will affect people or materials on the other side of an atrium well.
The BCA defines the terms “atrium” and “atrium well”. It is important to understand these BCA definitions, before considering Part G3. See definitions in Schedule 3.
An atrium well is not limited to having a maximum size, nor is there a limitation on its shape, except that it must contain a space throughout which could contain a cylinder with a diameter of 6 metres. This 6 metres is equal to the minimum distance between unprotected openings in external walls of adjoining buildings required by C3.2. This diameter void is intended to reduce the effects of radiant heat from a fire:
Figure G3.2 illustrates the method of measuring the atrium well to comply with G3.2 and the location of an atrium’s bounding walls.
An atrium must be separated from the remainder of the building at each storey by bounding walls set back not more than 3.5 m from the perimeter of the atrium well except in the case of the walls at no more than 3 consecutive storeys if—
one of those storeys is at a level at which direct egress to a road or open space is provided; and
the sum of the floor areas of those storeys that are contained within the atrium is not more than the maximum area that is permitted in Table C2.2.
To minimise the risk of spread of fire and smoke from or to the atrium or other parts of the building.
G3.3 requires the use of bounding walls, which limit the risk of fire and smoke spreading from the atrium to other parts of the building and other parts of the building to the atrium.
The detailed requirements for bounding walls are explained in the Comments on Clause 2.4 of Specification G3.8.
The bounding wall and 3.5 metre setback requirements do not apply where there are three or less consecutive storeys and:
Figure G3.3 illustrates the floors included in the area permitted by Table C2.2.
Figure G3.2 illustrates the location of an atrium’s bounding walls.
Bounding walls must—
have an FRL of not less than 60/60/60, and—
extend from the floor of the storey to the underside of the floor next above or to the underside of the roof; and
have any door openings protected with self-closing or automatic –/60/30 fire doors; or
be constructed of fixed toughened safety glass, or wired safety glass in non-combustible frames, with—
any door openings fitted with a self-closing smoke door complying with Specification C3.4; and
the walls and doors protected with wall-wetting systems in accordance with Specification G3.8; and
a fire barrier with an FRL of not less than –/60/30 installed in any ceiling spaces above the wall.
To limit the spread of fire between different parts of a building by way of an atrium.
G3.4 establishes the required FRL and acceptable construction requirements for the bounding walls required by G3.3. See Figure G3.4.
The walls bounding an atrium are not fire walls as defined in the BCA. Therefore, these walls do not create separate fire compartments within a storey of the building. The bounding walls define the extent of the part of the building regarded by the BCA to be an “atrium”. See Figure G3.2.
G3.4 prescribes two options for construction of bounding walls:
If a bounding wall separating an atrium from the remainder of the building is set back from the perimeter of the atrium well, a barrier that is imperforate and non-combustible, and not less than 1 m high must be provided.
To maximise the safety of people who have access around an atrium.
To maximise public safety, a barrier is required at the edge of a balcony to an atrium. The barrier must:
G3.5 takes precedence over the provisions of D2.16 for barriers around an atrium.
In an atrium—
the roof must have the FRL prescribed in Table 3 of Specification C1.1; or
the roof structure and membrane must be protected by a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification E1.5.
To minimise the risk that the roof of an atrium will not remain in place during a fire.
Clause 3 of Specification G3.8 requires smoke extraction through the roof, or near the top of an atrium—this smoke extraction is required to be by mechanical exhaust or by smoke and heat vents.
It is therefore important that the roof remains in place during a fire and not allow the re-circulation of smoke. To achieve this, G3.6 requires:
The materials used in the roof must comply with:
All areas within an atrium must have access to at least 2 exits.
To require that safe egress is available from an atrium.
Although the building may have an effective height of less than 25 metres, two exits are required from any area within an atrium. This is due to the additional fire hazard associated with atriums.
There may be other parts of the BCA which permit buildings to have only a single exit. G3.7 overrides any such provisions insofar as they relate to atriums.
All other aspects of the means of access and egress from an atrium must comply with Section D.
Sprinkler systems, smoke control, fire detection and alarm systems, and emergency warning and intercom systems must be installed in compliance with Specification G3.8.
To specify the additional fire and smoke control systems required for an atrium.
Because of the additional fire hazard associated with an atrium, special fire and smoke control measures are required to reduce the likelihood of conditions being reached which could endanger the safety of occupants before they have time to evacuate. These measures are set out in Specification G3.8.