NCC 2019 Volume One Amendment 1
Search the National Construction Code editions
Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements FP5.1 to FP5.6 are satisfied by complying with F5.1 to F5.7.
Where a Performance Solution is proposed, the relevant Performance Requirements must be determined in accordance with A2.2(3) and A2.4(3) as applicable.
The Deemed-to-Satisfy Provisions of this Part apply to Class 2 and 3 buildings and Class 9c buildings.
To clarify that Part F5 only applies to Class 2, Class 3 and Class 9c buildings.
A form of construction required to have an airborne sound insulation rating must—
have the required value for weighted sound reduction index (Rw) or weighted sound reduction index with spectrum adaptation term (Rw + Ctr) determined in accordance with AS/NZS ISO 717.1 using results from laboratory measurements; or
comply with Specification F5.2.
To clarify the means of determining the airborne sound insulation rating (Rw, Rw + Ctr).
Throughout the Part F5 Deemed-to-Satisfy Provisions, some forms of construction are required to have an Rw or Rw + Ctr. Rw and Ctr must be:
Rw is a measure of airborne sound insulation. Ctr is a spectrum adjustment factor which adjusts for low frequency sound levels. Ctr has been chosen in recognition of the problems caused by the high bass frequency outputs of modern home theatre systems and music reproduction equipment used by occupants of Class 2 and 3 buildings.
The Rw and Ctr must be determined in accordance with either AS/NZS ISO 717.1. These documents outline how to use test results from testing a building element to determine the Rw and Ctr of the building element. The test results must be obtained by testing the building element in accordance with ISO 140-3. ISO 140-3 is the method for testing the airborne sound insulation of building elements in the laboratory.
This part previously referenced Sound Transmission Class (STC) ratings as a measure of sound insulation. The STC rating has been replaced by Rw and Rw + Ctr. A note contained in Schedule 4 under AS/NZS ISO 717.1 states that materials tested in accordance with the previous Standard AS 1276 – 1979 must be considered equivalent to Rw values. These tests are only valid if they were issued prior to AS/NZS 1276.1 – 1999 being referenced in the BCA.
A floor in a building required to have an impact sound insulation rating must—
have the required value for weighted normalised impact sound pressure level (Ln,w) determined in accordance with AS ISO 717.2 using results from laboratory measurements; or
comply with Specification F5.2.
A wall in a building required to have an impact sound insulation rating must—
for a Class 2 or 3 building be of discontinuous construction; and
for a Class 9c building, must—
for other than masonry, be two or more separate leaves without rigid mechanical connection except at the periphery; or
be identical with a prototype that is no less resistant to the transmission of impact sound when tested in accordance with Specification F5.5 than a wall listed in Table 2 of Specification F5.2.
For the purposes of this Part, discontinuous construction means a wall having a minimum 20 mm cavity between 2 separate leaves, and
for masonry, where wall ties are required to connect leaves, the ties are of the resilient type; and
for other than masonry, there is no mechanical linkage between leaves except at the periphery.
To clarify the means of determining the impact sound insulation ratings.
In F5.4(a) floors separating certain areas are required to have an Ln,w. F5.3(a) outlines that the Ln,w must be:
Ln,w is a measure of impact sound insulation. The types of impact generated noise passing through floors that the requirements are aimed at minimising are noise associated with footsteps and moving of furniture.
F5.3(b)(i) requires walls of Class 2 and 3 buildings required to have an impact sound insulation rating to be of discontinuous construction. This term is defined in F5.3(c) and applies to all of Part F5 including Specifications F5.2 and F5.5.
F5.3(b)(ii) requires walls of a Class 9c building required to have an impact sound insulation rating to:
F5.3(c) sets out a definition of discontinuous construction. The definition applies to the whole of Part F5 (including Specifications F5.2 and F5.5) and is a wall having a cavity of at least 20 mm between 2 leaves, and:
A floor in a Class 2 or 3 building must have an Rw + Ctr (airborne) not less than 50 and an Ln,w (impact) not more than 62 if it separates—
a sole-occupancy unit from a plant room, lift shaft, stairway, public corridor, public lobby or the like, or parts of a different classification.
A floor in a Class 9c building separating sole-occupancy units must have an Rw not less than 45.
To minimise the transmission of sound through floors separating sole-occupancy units, and floors separating sole-occupancy units and certain types of space.
F5.4 contains requirements for Class 2, 3 and 9c buildings.
For Class 2 and 3 buildings, a floor requires both airborne (Rw + Ctr) and impact sound insulation (Ln,w) if it separates:
For Class 9c buildings, a floor requires airborne sound insulation if it separates sole-occupancy units.
The requirements differ between Class 2 and 3 buildings, and Class 9c buildings. This is due to sole-occupancy units in Class 2 and 3 buildings being ‘noisier’ than sole-occupancy units in Class 9c buildings. The reasons include the presence of televisions, stereos and DVDs and activities that may be conducted in Class 2 and 3 buildings. Therefore, Ctr and impact sound insulation only apply to Class 2 and 3 buildings. Also, the level of airborne sound insulation required in Class 9c buildings is less.
A wall in a Class 2 or 3 building must—
have an Rw + Ctr (airborne) not less than 50, if it separates sole-occupancy units; and
have an Rw (airborne) not less than 50, if it separates a sole-occupancy unit from a plant room, lift shaft, stairway, public corridor, public lobby or the like, or parts of a different classification; and
comply with F5.3(b) if it separates—
a bathroom, sanitary compartment, laundry or kitchen in one sole-occupancy unit from a habitable room (other than a kitchen) in an adjoining unit; or
a sole-occupancy unit from a plant room or lift shaft.
A door may be incorporated in a wall in a Class 2 or 3 building that separates a sole-occupancy unit from a stairway, public corridor, public lobby or the like, provided the door assembly has an Rw not less than 30.
A wall in a Class 9c building must have an Rw not less than 45 if it separates—
a sole-occupancy unit from a kitchen, bathroom, sanitary compartment (not being an associated ensuite), laundry, plant room or utilities room.
In addition to (c), a wall separating a sole-occupancy unit in a Class 9c building from a kitchen or laundry must comply with F5.3(b).
To minimise the transmission of sound through walls separating sole-occupancy units and walls separating sole-occupancy units and certain types of spaces.
F5.5(a) and (b) apply to Class 2 and 3 buildings. F5.5(a) covers walls separating sole-occupancy units, and walls separating sole-occupancy units and certain spaces. F5.5(b) applies to a door assembly in a wall that separates a sole-occupancy unit from a common area. F5.5(c) and (d) apply to Class 9c buildings. F5.5(c) applies to walls which separate sole-occupancy units and sole-occupancy from certain spaces. F5.5(d) applies to a wall that separates a sole-occupancy unit from a kitchen or laundry. F5.5(e) and (f) contains additional requirements for sound insulated walls.
As with the requirements for floors, the requirements for walls differ between Class 2 and 3 buildings, and Class 9c buildings. This is due to sole-occupancy units in Class 2 and 3 buildings being ‘noisier’ than sole-occupancy units in Class 9c buildings. The reasons include the presence of televisions, stereos and DVDs and activities that may be conducted in Class 2 and 3 buildings. Therefore, Ctr only applies to Class 2 and 3 buildings. Also, the level of airborne sound insulation required in Class 9c buildings is less.
F5.5(a) outlines airborne and impact sound insulation requirements for walls. The airborne sound requirements apply to walls separating sole-occupancy units and a sole-occupancy unit from a plant room, lift shaft, stairway, public corridor, public lobby or the like, or parts of a different classification. For walls separating sole-occupancy units, the wall must have a Rw + Ctr not less than 50. For walls separating a sole-occupancy unit from a plant room, lift shaft, stairway, public corridor, public lobby or the like, or parts of a different classification, the wall must have a Rw not less than 50. For walls separating habitable areas (excluding a kitchen) in one sole-occupancy unit from a bathroom, laundry, kitchen or sanitary compartment in an adjoining unit, the wall must be discontinuous construction. For the purpose of the BCA, discontinuous construction is a wall having a minimum 20 mm cavity between 2 separate leaves, with:
Mechanical linkage at the periphery is referring to the connection of the wall to the floor/roof and adjoining walls such as an external wall etc. A staggered stud wall with common top/bottom plates is not considered to be discontinuous construction.
F5.5(b) provides a concession for a door assembly located in a wall that separates a sole-occupancy unit from public corridor or the like. The door requires an Rw of not less than 30 whereas the wall requires Rw of not less than 45. This concession does not apply to a door assembly in a wall separating sole-occupancy units. In this case the door assembly would need to meet the same requirements for the wall, i.e. Rw + Ctr 50.
F5.5(c) applies to Class 9c buildings and covers sound transmission through sole-occupancy units from certain adjoining rooms and spaces. The list of adjoining rooms and spaces does not include the words ‘or the like’ because it is intended to be specific to only those areas.
The list of other spaces in F5.5(c) does not include stairways, public corridors, hallways, etc. The reason is that aged care buildings are to be provided with a level of sound insulation around the resident bedroom/sleeping areas to ensure a level of privacy, but still allow the residents to be reassured they are not alone. If the Rw of the wall is too high it may create a feeling of isolation for the residents and this can be detrimental to their well being. Being able to hear sounds that are outside their bedroom provides reassurance that assistance is available. The walls of sole-occupancy units prescribed in F5.5(c) must be at least Rw 45.
F5.5(d) applies to Class 9c buildings and deals with reducing the level of impact sound through the walls of the sole-occupancy units from adjoining kitchens and laundries. To comply with F5.5(d), it is necessary for the wall to have an Rw not less than 45 (as required by F5.5(c)) and:
F5.5(e) and (f) requires sound insulated walls to extend to either the roof/floor above or a ceiling that provides the required level of sound insulation. This is to ensure that there is no space above the wall which provide a flanking path for sound to travel through.
If a duct, soil, waste or water supply pipe, including a duct or pipe that is located in a wall or floor cavity, serves or passes through more than one sole-occupancy unit, the duct or pipe must be separated from the rooms of any sole-occupancy unit by construction with an Rw + Ctr (airborne) not less than—
40 if the adjacent room is a habitable room (other than a kitchen); or
25 if the adjacent room is a kitchen or non-habitable room.
If a storm water pipe passes through a sole-occupancy unit it must be separated in accordance with (a)(i) and (ii).
To minimise the transmission of sound that may arise from services that pass through more than one sole-occupancy unit.
F5.6 details separation requirements for services. The requirements only apply to services which pass through more than one sole-occupancy unit or are located in a wall or floor cavity which separates sole-occupancy units. F5.6 does not apply if the pipe is only located in a single unit, or any part of a Class 2, 3 or 9c building which is not part of a sole-occupancy unit.
The Rw + Ctr values do not take account of the inherent acoustic properties of a pipe material.
A flexible coupling must be used at the point of connection between the service pipes in a building and any circulating or other pump.
To minimise transmission of sound from a pump.
F5.7 requires flexible couplings at connection points to or from a pump to minimise vibration and any consequent sound transmission along the piping.