Section D Access and Egress

Section D Access and Egress

Part D1 Provision for Escape

Substitute the lead-in to D1.4(d) as follows:

Vic D1.4 Exit travel distances

(d)

Class 9 buildings — in a patient care area in a Class 9a building and in a children's service

Delete D1.6(f)(iv) as follows:

Vic D1.6 Dimensions of exits and paths of travel to exits

(f)
(iv)

(Deleted)

Part D2 Construction of Exits

Substitute D2.21 (a) as follows:

Vic D2.21 Operation of latch

(a)

A door in a required exit, forming part of a required exit or in the path of travel to a required exit must be readily openable without a key from the side that faces a person seeking egress, by—

(i)

a single hand downward action on a single device which is located between 900 mm and 1.1 m from the floor and if serving an area required to be accessible by Part D3

(A)

be such that the hand of a person who cannot grip will not slip from the handle during the operation of the latch; and

(B)

have a clearance between the handle and the back plate or door face at the centre grip section of the handle of not less than 35 mm and not more than 45 mm; or

(ii)

a single hand pushing action on a single device which is located between 900 mm and 1.2 m from the floor,

except that an exit door from a children's service which does not open to an outdoor space enclosed in accordance with G1.3, must have the device located between 1.5 m and 1.65 m above the floor and the door must be self-closing.