NSW Part J(A)3 Air-Conditioning and Ventilation Systems

NSW Part J(A)3 Air-Conditioning and Ventilation Systems

NSW J(A)3.0 Deemed-to-Satisfy Provisions

(a)

Where a Deemed-to-Satisfy Solution is proposed, Performance Requirement NSW J(A)P3 is satisfied by complying with NSW J(A)3.1 and NSW J(A)3.2.

(b)

Where a Performance Solution is proposed, the relevant Performance Requirements must be determined in accordance with A0.7.

NSW J(A)3.1 Application of Part

The Deemed-to-Satisfy Provisions of this Part apply to a Class 2 building and a Class 4 part of a building.

NSW J(A)3.2 Compliance with BCA provisions

Class 2 buildings and Class 4 parts of buildings must comply with the following national BCA provisions, as applicable—

(a)

J5.2(a) to (d) and (f) to (g) Air conditioning systems; and

(b)

J5.3 Mechanical ventilation systems; and

(c)

J5.4 Miscellaneous exhaust systems.

Note: Compliance is not required with the national BCA provisions of J5.2(e) as those matters are regulated under BASIX.