Specification JV Annual Energy Consumption Criteria

Specification JV Annual Energy Consumption Criteria

1. Scope

This Specification contains the requirements for calculating the annual energy consumption of services in a building.

Intent

To clarify the requirements of the calculation for the annual energy consumption of services.

2. Annual energy consumption of services

The annual energy consumption

(a)

for air-conditioning, must be calculated on the basis of—

(i)

the daily occupancy and operation profiles in Tables 2a to 2g; and

(ii)

plant serving public areas of a Class 3 or 9c building being available on thermostatic control 24 hours per day; and

(iii)

the internal heat gains in a building—

(A)

from occupants and hot meals, in accordance with one of the options in Table 2j; and

(B)

from appliances and equipment, in accordance with Table 2h; and

(C)

from artificial lighting, that is calculated in (b); and

(b)

for artificial lighting, must be calculated on the basis of the proposed level of artificial lighting in the building with the daily profile in Tables 2a to 2g; and

(c)

for heated water supply, must be calculated on the basis of the consumption rates of Table 2i.

Table 2a OCCUPANCY AND OPERATION PROFILES OF A CLASS 3 OR 9c BUILDING

Time period

(local standard time)

Occupancy Artificial lighting Air-conditioning
Monday to Friday Saturday, Sunday and holidays Monday to Friday Saturday, Sunday and holidays
12:00am to 1:00am 85% 85% 5% On On
1:00am to 2:00am 85% 85% 5% On On
2:00am to 3:00am 85% 85% 5% On On
3:00am to 4:00am 85% 85% 5% On On
4:00am to 5:00am 85% 85% 5% On On
5:00am to 6:00am 85% 85% 25% On On
6:00am to 7:00am 85% 85% 80% On On
7:00am to 8:00am 80% 85% 80% On On
8:00am to 9:00am 50% 50% 50% On On
9:00am to 10:00am 10% 50% 20% Off On
10:00am to 11:00am 10% 20% 20% Off Off
11:00am to 12:00pm 10% 20% 20% Off Off
12:00pm to 1:00pm 10% 20% 20% Off Off
1:00pm to 2:00pm 10% 20% 20% Off Off
2:00pm to 3:00pm 10% 20% 20% Off Off
3:00pm to 4:00pm 10% 30% 20% Off Off
4:00pm to 5:00pm 50% 50% 20% On On
5:00pm to 6:00pm 50% 50% 50% On On
6:00pm to 7:00pm 70% 50% 50% On On
7:00pm to 8:00pm 70% 70% 50% On On
8:00pm to 9:00pm 80% 80% 50% On On
9:00pm to 10:00pm 85% 80% 50% On On
10:00pm to 11:00pm 85% 85% 50% On On
11:00pm to 12:00am 85% 85% 5% On On
Note: The occupancy profile is expressed as a percentage of the maximum number of people that can be accommodated in the Class 3 or 9c building. The artificial lighting profile is expressed as a percentage of the maximum illumination power density permitted under Part J6.

Table 2b OCCUPANCY AND OPERATION PROFILES OF A CLASS 5 BUILDING, A CLASS 7 WAREHOUSE, A CLASS 8 LABORATORY OR A CLASS 9a CLINIC, DAY SURGERY OR PROCEDURE UNIT

Time period

(local standard time)

Occupancy

Monday to Friday

Artificial lighting

Monday to Friday

Appliances and equipment

Monday to Friday

Air-conditioning

Monday to Friday

12:00am to 1:00am 0% 10% 10% Off
1:00am to 2:00am 0% 10% 10% Off
2:00am to 3:00am 0% 10% 10% Off
3:00am to 4:00am 0% 10% 10% Off
4:00am to 5:00am 0% 10% 10% Off
5:00am to 6:00am 0% 10% 10% Off
6:00am to 7:00am 0% 10% 10% Off
7:00am to 8:00am 15% 40% 25% On
8:00am to 9:00am 60% 80% 70% On
9:00am to 10:00am 100% 100% 100% On
10:00am to 11:00am 100% 100% 100% On
11:00am to 12:00pm 100% 100% 100% On
12:00pm to 1:00pm 100% 100% 100% On
1:00pm to 2:00pm 100% 100% 100% On
2:00pm to 3:00pm 100% 100% 100% On
3:00pm to 4:00pm 100% 100% 100% On
4:00pm to 5:00pm 100% 100% 100% On
5:00pm to 6:00pm 50% 80% 60% On
6:00pm to 7:00pm 15% 60% 25% Off
7:00pm to 8:00pm 5% 40% 15% Off
8:00pm to 9:00pm 5% 20% 15% Off
9:00pm to 10:00pm 0% 10% 10% Off
10:00pm to 11:00pm 0% 10% 10% Off
11:00pm to 12:00am 0% 10% 10% Off

Notes:

  1. The occupancy profile is expressed as a percentage of the maximum number of people that can be accommodated in the building. The artificial lighting profile is expressed as a percentage of the maximum illumination power density permitted under Part J6. The appliances and equipment profile is expressed as a percentage of the maximum internal heat gain in Table 2h. The air-conditioning profile is expressed as the plant status.
  2. Saturday and Sunday profiles are 10% continuous artificial lighting and 10% continuous appliances and equipment. There is no occupancy and the air-conditioning is "off".

Table 2c OCCUPANCY AND OPERATION PROFILES OF A CLASS 6 SHOP OR SHOPPING CENTRE

Time period

(local standard time)

Occupancy

(Daily)

Artificial lighting

(Daily)

Appliances and equipment

(Daily)

Air-conditioning

(Daily)

12:00am to 1:00am 0% 10% 10% Off
1:00am to 2:00am 0% 10% 10% Off
2:00am to 3:00am 0% 10% 10% Off
3:00am to 4:00am 0% 10% 10% Off
4:00am to 5:00am 0% 10% 10% Off
5:00am to 6:00am 0% 10% 10% Off
6:00am to 7:00am 0% 10% 10% Off
7:00am to 8:00am 10% 100% 70% On
8:00am to 9:00am 20% 100% 70% On
9:00am to 10:00am 20% 100% 70% On
10:00am to 11:00am 15% 100% 70% On
11:00am to 12:00pm 25% 100% 70% On
12:00pm to 1:00pm 25% 100% 70% On
1:00pm to 2:00pm 15% 100% 70% On
2:00pm to 3:00pm 15% 100% 70% On
3:00pm to 4:00pm 15% 100% 70% On
4:00pm to 5:00pm 15% 100% 70% On
5:00pm to 6:00pm 5% 100% 70% On
6:00pm to 7:00pm 5% 100% 70% Off
7:00pm to 8:00pm 0% 10% 10% Off
8:00pm to 9:00pm 0% 10% 10% Off
9:00pm to 10:00pm 0% 10% 10% Off
10:00pm to 11:00pm 0% 10% 10% Off
11:00pm to 12:00am 0% 10% 10% Off

Note: The occupancy profile is expressed as a percentage of the maximum number of people that can be accommodated in the building. The artificial lighting profile is expressed as a percentage of the maximum illumination power density permitted under Part J6. The appliances and equipment profile is expressed as a percentage of the maximum internal heat gain in Table 2h. The air-conditioning profile is expressed as the plant status.

Table 2d OCCUPANCY AND OPERATION PROFILES OF A CLASS 6 RESTAURANT OR CAFE

Time period

(local standard time)

Occupancy

(Monday to Saturday)

Artificial lighting

(Monday to Saturday)

Appliances and equipment

(Monday to Saturday)

Air-conditioning

(Monday to Saturday)

12:00am to 1:00am 0% 5% 15% Off
1:00am to 2:00am 0% 5% 15% Off
2:00am to 3:00am 0% 5% 15% Off
3:00am to 4:00am 0% 5% 15% Off
4:00am to 5:00am 0% 5% 15% Off
5:00am to 6:00am 0% 5% 15% Off
6:00am to 7:00am 5% 40% 40% Off
7:00am to 8:00am 5% 40% 40% On
8:00am to 9:00am 5% 60% 60% On
9:00am to 10:00am 5% 60% 60% On
10:00am to 11:00am 20% 90% 90% On
11:00am to 12:00pm 50% 90% 90% On
12:00pm to 1:00pm 80% 90% 90% On
1:00pm to 2:00pm 70% 90% 90% On
2:00pm to 3:00pm 40% 90% 90% On
3:00pm to 4:00pm 20% 90% 90% On
4:00pm to 5:00pm 25% 90% 90% On
5:00pm to 6:00pm 50% 90% 90% On
6:00pm to 7:00pm 80% 90% 90% On
7:00pm to 8:00pm 80% 90% 90% On
8:00pm to 9:00pm 80% 90% 90% On
9:00pm to 10:00pm 50% 90% 90% On
10:00pm to 11:00pm 35% 50% 50% On
11:00pm to 12:00am 20% 30% 30% On

Notes:

  1. The occupancy profile is expressed as a percentage of the maximum number of people that can be accommodated in the building. The artificial lighting profile is expressed as a percentage of the maximum illumination power density permitted under Part J6. The appliances and equipment profile is expressed as a percentage of the maximum internal heat gain in Table 2h. The air-conditioning profile is expressed as the plant status.
  2. Sunday profiles is 5% continuous artificial lighting and 5% continuous appliances and equipment. There is no occupancy and the air-conditioning is "off".

Table 2e OCCUPANCY AND OPERATION PROFILES OF A CLASS 9a WARD AREA

Time period

(local standard time)

Occupancy Artificial lighting Air-conditioning
Monday to Friday Saturday and Sunday Monday to Friday Saturday and Sunday
12:00am to 1:00am 85% 85% 5% On On
1:00am to 2:00am 85% 85% 5% On On
2:00am to 3:00am 85% 85% 5% On On
3:00am to 4:00am 85% 85% 5% On On
4:00am to 5:00am 85% 85% 5% On On
5:00am to 6:00am 85% 85% 25% On On
6:00am to 7:00am 85% 85% 80% On On
7:00am to 8:00am 85% 85% 80% On On
8:00am to 9:00am 85% 85% 50% On On
9:00am to 10:00am 85% 85% 20% On On
10:00am to 11:00am 85% 85% 20% On On
11:00am to 12:00pm 85% 85% 20% On On
12:00pm to 1:00pm 85% 85% 20% On On
1:00pm to 2:00pm 85% 85% 20% On On
2:00pm to 3:00pm 85% 85% 20% On On
3:00pm to 4:00pm 85% 85% 20% On On
4:00pm to 5:00pm 85% 85% 20% On On
5:00pm to 6:00pm 85% 85% 50% On On
6:00pm to 7:00pm 85% 85% 50% On On
7:00pm to 8:00pm 85% 85% 50% On On
8:00pm to 9:00pm 85% 85% 50% On On
9:00pm to 10:00pm 85% 85% 50% On On
10:00pm to 11:00pm 85% 85% 50% On On
11:00pm to 12:00am 85% 85% 5% On On
Note:The occupancy profile is expressed as a percentage of the maximum number of people that can be accommodated in the building. The artificial lighting profile is expressed as a percentage of the maximum illumination power density permitted under Part J6. The air-conditioning profile is expressed as the plant status.

Table 2f OCCUPANCY AND OPERATION PROFILES OF A CLASS 9b THEATRE OR CINEMA

Time period

(local standard time)

Occupancy Artificial lighting Air-conditioning
Monday to Friday Sat. & Sun Monday to Friday Sat. & Sun Monday to Friday Sat. & Sun
12:00am to 1:00am 0% 0% 5% 5% Off Off
1:00am to 2:00am 0% 0% 5% 5% Off Off
2:00am to 3:00am 0% 0% 5% 5% Off Off
3:00am to 4:00am 0% 0% 5% 5% Off Off
4:00am to 5:00am 0% 0% 5% 5% Off Off
5:00am to 6:00am 0% 0% 5% 5% Off Off
6:00am to 7:00am 0% 0% 5% 5% Off Off
7:00am to 8:00am 0% 0% 5% 5% Off On
8:00am to 9:00am 0% 20% 100% 100% Off On
9:00am to 10:00am 0% 80% 10% 10% Off On
10:00am to 11:00am 0% 80% 10% 10% Off On
11:00am to 12:00pm 0% 80% 10% 10% On On
12:00pm to 1:00pm 20% 20% 100% 100% On On
1:00pm to 2:00pm 80% 80% 5% 5% On On
2:00pm to 3:00pm 80% 80% 5% 5% On On
3:00pm to 4:00pm 80% 80% 5% 5% On On
4:00pm to 5:00pm 80% 80% 5% 5% On On
5:00pm to 6:00pm 20% 20% 100% 100% On On
6:00pm to 7:00pm 20% 20% 100% 100% On On
7:00pm to 8:00pm 80% 80% 100% 100% On On
8:00pm to 9:00pm 80% 80% 5% 5% On On
9:00pm to 10:00pm 80% 80% 5% 5% On On
10:00pm to 11:00pm 80% 80% 5% 5% On On
11:00pm to 12:00am 10% 10% 100% 100% On On
Note:The occupancy profile is expressed as a percentage of the maximum number of people that can be accommodated in the building. The artificial lighting profile is expressed as a percentage of the maximum illumination power density permitted under Part J6. The air-conditioning profile is expressed as the plant status.

Table 2g OCCUPANCY AND OPERATION PROFILES OF A CLASS 9b SCHOOL

Time period

(local standard time)

Occupancy Artificial lighting Appliances and equipment Air-conditioning
Monday to Friday Monday to Friday Monday to Friday Monday to Friday
12:00am to 1:00am 0% 5% 5% Off
1:00am to 2:00am 0% 5% 5% Off
2:00am to 3:00am 0% 5% 5% Off
3:00am to 4:00am 0% 5% 5% Off
4:00am to 5:00am 0% 5% 5% Off
5:00am to 6:00am 0% 5% 5% Off
6:00am to 7:00am 0% 5% 5% Off
7:00am to 8:00am 5% 30% 30% On
8:00am to 9:00am 75% 85% 85% On
9:00am to 10:00am 90% 95% 95% On
10:00am to 11:00am 90% 95% 95% On
11:00am to 12:00pm 90% 95% 95% On
12:00pm to 1:00pm 50% 80% 70% On
1:00pm to 2:00pm 50% 80% 70% On
2:00pm to 3:00pm 90% 95% 95% On
3:00pm to 4:00pm 70% 90% 80% On
4:00pm to 5:00pm 50% 70% 60% On
5:00pm to 6:00pm 20% 20% 20% Off
6:00pm to 7:00pm 20% 20% 20% Off
7:00pm to 8:00pm 20% 20% 20% Off
8:00pm to 9:00pm 10% 10% 10% Off
9:00pm to 10:00pm 5% 5% 5% Off
10:00pm to 11:00pm 5% 5% 5% Off
11:00pm to 12:00am 5% 5% 5% Off

Notes:

  1. The occupancy profile is expressed as a percentage of the maximum number of people that can be accommodated in the building. The artificial lighting profile is expressed as a percentage of the maximum illumination power density permitted under Part J6. The appliances and equipment profile is expressed as a percentage of the maximum internal heat gain in Table 2h. The air-conditioning profile is expressed as the plant status.
  2. Saturday and Sunday profiles are 5% continuous artificial lighting and 5% continuous appliances and equipment. There is no occupancy and the air-conditioning is "off".

Table 2h INTERNAL HEAT GAINS FOR APPLIANCES AND EQUIPMENT

Application Internal sensible heat gain rate (W/m2)
Sole-occupancy unit of a Class 3 building, a Class 9a building ward area or Class 9c building 5 W/m2 averaged for 24 hours per day, 7 days per week, continuous operation
Class 5 building, Class 8 laboratory and a Class 9a clinic, day surgery and a procedure unit 15 W/m2
Class 6 shop and shopping centre, Class 6 cafe and restaurant and Class 9b school 5 W/m2
Other applications No load

Table 2i HEATED WATER SUPPLY CONSUMPTION RATES

Application Daily consumption rate
Residential part of a hotel or motel 75 L/sole-occupancy unit
Dormitory, boarding house, guest house, hostel, lodginghouse and backpackers accommodation 50 L/person
Residential part of a school, accommodation for the aged, children or people with a disability and a detention centre or a health care building which accommodates members of staff
Class 9c building
Office, laboratory, shop and assembly building 4 L/person
Dining room, restaurant and cafe 9 L/meal
Health care building ward area 70 L/patient
School 7 L/person
Other applications 4 L/person

Table 2J INTERNAL HEAT GAINS FOR OCCUPANTS AND HOT MEALS

Application Internal heat gains per person
Dining room, restaurant or cafe
  1. 80 W sensible heat gain and 80 W latent heat gain
  2. The average adjusted metabolic rate for sedentary work from Table 45 of AIRAH-DA09
  3. The heat emission rate for sedentary work from Table 6.3 of CIBSE Guide A
Other applications
  1. 75 W sensible heat gain and 55 W latent heat gain
  2. An average adjusted metabolic rate from Table 45 of AIRAH-DA09
  3. A heat emission rate from Table 6.3 of CIBSE Guide A

Notes:

  1. The number of people must be calculated in accordance with D1.13.
  2. For a dining room, restaurant or cafe, the internal heat gains per person account for heat gains from both occupants and hot meals. For other applications, the internal heat gains per person only account for heat gains from occupants.
Intent

To outline the inclusions in the method of calculation of annual energy consumption.

The Specification sets out a standard procedure for calculating annual energy consumption and provides various options in to account for heat gains per person and where applicable, heat gains from meals. The number of people must be calculated in accordance with .

Although the values stated may not be those actually achieved in some buildings, the values are derived from industry accepted data sources and are considered the most typical. The same rates apply for the proposed building and reference building under .

They do not have to be used as part of the Verification Method provided the operating hours of the building per year used in the calculation are not less than 2,500 hours (see ).

to provide occupancy and equipment operation profiles for different building classifications and uses. Those for office buildings are the same as those used in the Australian Building Greenhouse Rating Scheme (ABGR) with respect to people and air-conditioning but not for lighting and office equipment. ABGR has higher values for equipment use.