Specification J5.2e Energy Efficiency Ratios
This Specification contains the requirements for the energy efficiency ratios of—
refrigerant chillers used as part of an air-conditioning system; and
packaged air-conditioning equipment.
To clarify that provides the energy efficiency ratio requirements for refrigerant chillers that are used as part of an air-conditioning system, and packaged air-conditioning equipment.
An air-conditioning system refrigerant chiller with a capacity not more than 350 kWr must have an energy efficiency ratio complying with Table 2a when determined in accordance with AHRI 550/590.
Table 2a MINIMUM ENERGY EFFICIENCY RATIO FOR REFRIGERANT CHILLERS
Equipment | Minimum energy efficiency ratio (Wr/Winput power) | |
---|---|---|
For full load operation | For integrated part load | |
Water cooled chiller | 4.2 | 5.2 |
Air cooled or evaporatively cooled chiller | 2.5 | 3.4 |
Package air-conditioning equipment with a capacity of not less than 65 kWr, including a split unit and a heat pump, must have a minimum energy efficiency ratio when cooling complying with Table 2b when tested in accordance with AS/NZS 3823.1.2 at test condition T1.
Table 2b MINIMUM ENERGY EFFICIENCY RATIO FOR PACKAGED AIR-CONDITIONING EQUIPMENT
Equipment | Minimum energy efficiency ratio (Wr/Winput power) | |
---|---|---|
65 kWr to 95 kWr capacity | More than 95 kWr capacity | |
Air-conditioner — cooling | 2.70 | 2.80 |
Heat pump — cooling | 2.60 | 2.70 |
To facilitate the efficient use of energy by detailing the requirements for packaged air-conditioners, and chillers that are part of an air-conditioning system.
covers the requirements for refrigerant chillers and specifies that the performance of a refrigerant chiller of capacity up to 350 kWr that is part of an air-conditioning system must have an energy efficiency ratio complying with . The energy efficiency ratio must be determined by testing in accordance with the American Air-Conditioning & Refrigeration Institute (AHRI) Standard AHRI 550/590.
This standard requires chillers to be tested at full load and at a series of part loads, which are then integrated into a single number part-load efficiency. Part load (or integrated part load) is far more critical than a full load as a single chiller will not operate for many hours of a typical year at full load.
Chillers of 350 kWr capacity and above are regulated under MEPS.
states that packaged air-conditioning equipment with a capacity of 65 kWr and above must have a minimum energy efficiency ratio when cooling complying with , when tested in accordance with AS/NZS 3823.1.2 at test condition T1. specifies the efficiencies required for packaged air-conditioning equipment including a split system and a heat pump.
AS/NZS 3823.1.2 has various test conditions so this clause requires the equipment to be tested at condition T1. This standard covers the performance of electrical appliances - air-conditioners and heat pumps, ducted air-conditioners and air-to-air heat pumps - testing and rating for performance.
Note that the energy efficiency of packaged air-conditioning equipment up to 65 kWr capacity is controlled by MEPS.
A packaged air-conditioner is a modular factory assembled air-conditioning unit. These units are self-contained and include within the unit all the components for heating and/or cooling such as fans, controls, a refrigeration system, heating coil and sometimes the heater. Split systems are a type of packaged air-conditioner where the indoor and outdoor units are separately installed and are electrically connected and joined by refrigeration piping on site.