Filter
Section F Health and Amenity
Part F2 Sanitary Facilities
Tas Table F2.3 Sanitary Facilities in Class 3, 5, 6, 7, 8 and 9 Buildings
Delete the Note in Table F2.3 alongside early childhood centres and replace it with the following:
Note: |
If the centre accommodates children under 4 years of age the facilities for use by
|
After F2.8 insert Tas F2.101 as follows:
Tas F2.101 Non-flushed Urinals
Non-flushed urinals not connected to a sewerage system must comply with Tas F2.102.
After Tas F2.101 insert Tas F2.102 as follows:
Tas F2.102 Installation of Closet Fixtures
If a sufficient sewerage system is not available, an authorised alternative means of disposal of sewage, may be installed.
If sanitary facilities are not water-flushed, the following provisions apply:
A pit latrine, an incinerating toilet, a chemical toilet, a removable pan or a non-flushing urinal must not be within 2 m of a building containing habitable rooms.
The floor on which a removable pan is placed must be impervious.
A room containing a composting toilet must be separated from habitable rooms by way of a permanently ventilated air lock (which may be a circulation space).
The minimum ventilation required under (iii) shall be the greater of—
8000 mm2; or
1/500th of the floor area of the circulation space.
Access for maintenance or removal of waste from a composting toilet must be by way of an access door which opens directly to the outside of the building.