NCC 2016 Volume Two
Search the National Construction Code editions
Part 3.8.5 Ventilation
Appropriate :
Where an alternative ventilation system is proposed as a Performance Solution to that described in Part 3.8.5, that proposal must comply with—
The requirements of this Part are to be read in conjunction with the air movement requirements in Part 3.12.4. However, it should be noted that Part 3.12.4 does not apply in all States and Territories.
Except for an exhaust fan from a sanitary compartment, laundry or bathroom, Performance RequirementP2.4.5 is satisfied for a mechanical ventilation system if it is installed in accordance with AS 1668.2.
An exhaust fan from a sanitary compartment, laundry or bathroom must comply with the acceptable construction practice.
Compliance with this acceptable construction practice satisfies Performance Requirement for ventilation.
Ventilation must be provided to a habitable room, sanitary compartment, bathroom, shower room, laundry and any other room occupied by a person for any purpose by any of the following means:
Openings, windows, doors or other devices which can be opened—
with a ventilating area not less than 5% of the floor area of the room required to be ventilated; and
open to—
a suitably sized court, or space open to the sky; or
an open verandah, carport, or the like; or
an adjoining room in accordance with (b).
Natural ventilation to a room may come through a window, opening, door or other device from an adjoining room (including an enclosed verandah) if—
the room to be ventilated or the adjoining room is not a sanitary compartment; and
the window, opening, door or other device has a ventilating area of not less than 5% of the floor area of the room to be ventilated; and
the adjoining room has a window, opening, door or other device with a ventilating area of not less than 5% of the combined floor areas of both rooms; and
the ventilating areas specified may be reduced as appropriate if direct natural ventilation is provided from another source.
(See Figure 3.8.5.1)
permits a room's required ventilation to be "borrowed" from an adjoining room, i.e. an adjoining room's ventilation can be used to help make up the total amount of ventilation required.
The use of borrowed ventilation is acceptable if the provisions of 3.8.5.2(b) are applied to the subject room and to the total area of each relevant room.
Figure 3.8.5.1 METHOD OF DETERMINING AREAS OF OPENINGS FOR BORROWED VENTILATION |
---|
|
An exhaust fan or other means of mechanical ventilation may be used to ventilate a sanitary compartment, laundry or bathroom, or where mechanical ventilation is provided in accordance with 3.8.5.3(b), provided contaminated air exhausts—
directly to outside the building by way of ducts; or
into a roof space that—
is adequately ventilated by open eaves, and/or roof vents; or
is covered by roof tiles without sarking or similar materials which would prevent venting through gaps between the tiles.
Except where mechanical ventilation is provided in accordance with 3.8.5.3(b), 3.8.5.2(c) only applies where an exhaust fan or other means of mechanical ventilation is provided as the sole means of ventilation for a sanitary compartment, laundry or bathroom.
Sanitary compartments must not open directly into a kitchen or pantry unless—
access is by an airlock, hallway or other room, (see Figure 3.8.5.2); or
the sanitary compartment is provided with an exhaust fan or other means of mechanical exhaust ventilation.
Figure 3.8.5.2 ACCEPTABLE LOCATION OF NON MECHANICALLY VENTILATED SANITARY COMPARTMENT |
---|
|