NCC 2016 Volume Two
Search the National Construction Code editions
Part 3.5.2 Gutters And Downpipes
Appropriate :
Where an alternative gutter and downpipe system is proposed as a Performance Solution to that described in Part 3.5.2, that proposal must comply with—
P2.2.1 is satisfied for gutters and downpipes if they are designed and constructed in accordance with one of the following:
AS/NZS 3500.3.
Section 5 of AS/NZS 3500.5.
Compliance with this acceptable construction practice satisfies Performance RequirementP2.2.1 for gutters and downpipes provided the roof drainage system is connected to a stormwater drainage system that complies with Part 3.1.2.
This Part does not apply to the removal of surface water from a storm having an average recurrence interval of 100 years for a Class 10 building where in the particular case there is no necessity for compliance.
Gutters, downpipes and flashings must—
be manufactured in accordance with AS/NZS 2179.1 for metal; and
be manufactured in accordance with AS 1273 for UPVC components; and
be compatible with all upstream roofing materials in accordance with 3.5.1.3(c); and
not contain any lead if used on a roof forming part of a potable water catchment area.
The size of guttering must—
for eaves gutters, be in accordance with Table 3.5.2.2; and
for box gutters, be in accordance with AS/NZS 3500.3 or Section 5 of AS/NZS 3500.5; and
be suitable to remove rainwater falling at the appropriate 5 minute duration rainfall intensity listed in Table 3.5.2.1 as follows—
for eaves gutters — 20 year average recurrence interval; and
for eaves gutter overflow measures — 100 year average recurrence interval; and
for box and valley gutters — 100 year average recurrence interval.
Gutters must be installed with a fall of not less than—
1:500 for eaves gutters, unless fixed to metal fascias; and
1:100 for box gutters.
Eaves gutters must be—
supported by brackets securely fixed at stop ends and at not more than 1.2 m centres; and
be capable of removing the overflow volume specified in Table 3.5.2.3.
Overflow measures in accordance with Table 3.5.2.4 are deemed to be capable of removing the overflow volume specified in that Table.
Valley gutters on a roof with a pitch—
more than 12.5 degrees — must have width of not less than 400 mm and be wide enough to allow the roof covering to overhang not less than 150 mm each side of the gutter; or
not more than 12.5 degrees — must be designed as a box gutter.
The requirement of (b)(ii) does not apply to eaves gutters fixed to a verandah or an eave that is greater than 450 mm in width, which—
has no lining; or
is a raked verandah or a raked eave with a lining sloping away from the building.
Worked example — Determining appropriate overflow measures
The location of a proposed building is in Wollongong, NSW. Using Table 3.5.2.1 the 5 minute duration rainfall intensity for a 100 year average recurrence interval is 308 mm/h. The 5 minute duration rainfall intensities in Table 3.5.2.3 are provided in 25 mm/h increments, therefore for the purpose of the worked example 325 mm/h will be used.
provides required overflow volumes in both litres per second for dedicated overflow measures and litres per second per metre for continuous overflow measures. Where both dedicated and continuous measures are proposed, Table 3.5.2.3b can be used to determine the required overflow volume.
The selected dedicated overflow measure is an end-stop weir which provides 0.5 L/s.
One end-stop weir does not achieve the required overflow volume of 5.4 L/s, and additional overflow measures are required to remove the overflow volume.
A front face slotted gutter is the selected overflow measure as it provides 0.5 L/s/m. Taking account of the eaves gutter length (10 m), the combined overflow measures (0.5 L/s for the end-stop weir and 0.5 L/s/m × 10 m) will remove up to 5.5 L/s.
Downpipes must—
not serve more than 12 m of gutter length for each downpipe; and
be located as close as possible to valley gutters; and
be selected in accordance with the appropriate eaves gutter section as shown in Table 3.5.2.2.
A maximum 12 m gutter length served by each downpipe is to ensure effective fall and adequate capacity to discharge all water anticipated during a storm having an average recurrence interval of 20 years.
Where a rainhead overflow device is incorporated in the top of the downpipe, its overflow discharge should be directed away from the building.
Table 3.5.2.1 RAINFALL DURATION INTENSITIES
Locality | 5 minute duration rainfall intensity (mm/h) | Locality | 5 minute duration rainfall intensity (mm/h) | ||
---|---|---|---|---|---|
Average recurrence interval, once in— | Average recurrence interval, once in— | ||||
20 years | 100 years | 20 years | 100 years | ||
ACT | SA | ||||
Canberra | 143 | 193 | Adelaide |
124 |
184 |
Gungahlin |
137 |
179 | Gawler |
110 |
158 |
Tuggeranong |
148 | 210 | Mt Gambier | 103 | 144 |
Murray Bridge | 120 | 178 | |||
NSW | Port Augusta | 133 | 199 | ||
Albury | 139 | 180 | Port Pirie | 122 | 181 |
Broken Hill | 143 | 219 | Yorketown | 155 | 166 |
Goulburn | 121 | 156 | |||
Kiama | 226 | 319 | TAS | ||
Newcastle | 226 | 316 | Burnie | 128 | 180 |
Orange | 142 | 186 | Flinders Island | 122 | 166 |
Sydney | 200 | 262 | Hobart | 85 | 116 |
Avalon | 206 | 278 | Launceston | 90 | 121 |
Campbelltown | 167 | 222 | Queenstown | 94 | 120 |
Penrith | 180 | 244 | St. Marys | 146 | 203 |
Windsor | 175 | 233 | |||
Tweed Heads | 252 | 330 | VIC | ||
Wollongong | 217 | 308 | Ballarat | 131 | 188 |
Benalla | 146 | 194 | |||
NT | Geelong | 102 | 144 | ||
Alice Springs | 166 | 239 | Horsham | 120 | 173 |
Darwin | 233 | 274 | Lakes Entrance | 145 | 198 |
Katherine | 216 | 250 | Melbourne | 132 | 187 |
Hastings | 117 | 145 | |||
QLD | Sorrento | 106 | 140 | ||
Bamaga | 252 | 298 | Mildura | 142 | 218 |
Brisbane | 234 | 305 | Stawell | 130 | 186 |
Ipswich | 211 | 278 | |||
Victoria Point | 245 | 320 | WA | ||
Bundaberg | 265 | 340 | Albany | 125 | 178 |
Cairns | 229 | 278 | Broome | 232 | 287 |
Cloncurry | 218 | 278 | Bunbury | 147 | 199 |
Innisfail | 248 | 301 | Derby | 211 | 256 |
Mackay | 250 | 316 | Geraldton | 138 | 193 |
Mt Isa | 199 | 260 | Kalgoorlie | 137 | 204 |
Noosa Heads | 258 | 331 | Perth | 130 | 172 |
Rockhampton | 229 | 300 | Joondalup | 133 | 180 |
Toowoomba | 203 | 268 | Midland | 122 | 163 |
Townsville | 235 | 300 | Port Hedland | 168 | 230 |
Weipa | 239 | 283 | Tom Price | 138 | 182 |
Note: Locations used in this table are based on the nearest Bureau of Meteorology grid cell latitude and longitude to the central Post Office of each city or town, with the exception of Tom Price in WA, which uses the Police Station. |
Table 3.5.2.2 GUTTER AND DOWNPIPE SELECTION
Table a. Gutter sizes for various rainfall intensities and roof catchment areas per downpipe | |||||
---|---|---|---|---|---|
Design Rainfall Intensity (mm/h) (as per Table 3.5.2.1) | Roof Catchment Area per Downpipe — m2 | ||||
30 | 40 | 50 | 60 | 70 | |
Size of gutter required to drain roof catchment area into one (1) downpipe (A, B, C, D, E and F defined in Table b.) | |||||
90 | A or C | A or C | A or C | A or C | A or C |
120 | A or C | A or C | A or C | A or C | A or D |
140 | A or C | A or C | A or C | A or D | B or E |
160 | A or C | A or C | A or C | A or E | B or E |
175 | A or C | A or C | A or D | B or E | E |
200 | A or C | A or C | A or D | B or E | F |
225 | A or C | A or C | A or B | E | F |
255 | A or C | A or D | B or E | E | F |
275 | A or C | A or D | B or E | F | F |
325 | A or C | B or E | F | F | F |
425 | A or C | E | F | F | F |
Table b. Gutter sizes for various rainfall intensities | ||
---|---|---|
Gutter Type (as per Table a.) | Gutter description | Minimum Cross Sectional Area mm2 |
A | Medium rectangular gutter | 6500 |
B | Large rectangular gutter | 7900 |
C | 115 mm D gutter | 5200 |
D | 125 mm D gutter | 6300 |
E | 150 mm D gutter | 9000 |
F | Gutter must be designed in accordance with AS/NZS 3500.3 or Section 5 of AS/NZS 3500.5 |
Table c. Downpipe selection | |||||
---|---|---|---|---|---|
Downpipe Section | Gutter Sections — (as per Table b.) | ||||
A | B | C | D | E | |
75 mm dia. | Yes | Yes | Yes | Yes | No |
100 mm × 50 mm | Yes | Yes | Yes | Yes | Yes |
90 mm dia. | Yes | Yes | Yes | Yes | Yes |
100 mm × 75 mm | Yes | Yes | Yes | Yes | Yes |
Legend: Yes—downpipe is suitable for the eaves gutter selection; and |
Table 3.5.2.3 OVERFLOW VOLUME
Table a. Overflow volume for continuous measure (L/s/m) | ||||||||
---|---|---|---|---|---|---|---|---|
Design 5 minute duration rainfall intensity (mm/h) (from Table 3.5.2.1) | Ridge to Gutter Length (m) | |||||||
2 | 4 | 6 | 8 | 10 | 12 | 14 | 16 | |
150 | 0.08 | 0.17 | 0.25 | 0.33 | 0.42 | 0.50 | 0.58 | 0.67 |
175 | 0.10 | 0.19 | 0.29 | 0.39 | 0.49 | 0.58 | 0.68 | 0.78 |
200 | 0.11 | 0.22 | 0.33 | 0.44 | 0.56 | 0.67 | 0.78 | 0.89 |
225 | 0.13 | 0.25 | 0.38 | 0.50 | 0.63 | 0.75 | 0.88 | 1.0 |
250 | 0.14 | 0.28 | 0.42 | 0.56 | 0.69 | 0.83 | 0.97 | 1.1 |
275 | 0.15 | 0.31 | 0.46 | 0.61 | 0.76 | 0.92 | 1.1 | 1.2 |
300 | 0.17 | 0.33 | 0.50 | 0.67 | 0.83 | 1.0 | 1.2 | 1.3 |
325 | 0.18 | 0.36 | 0.54 | 0.72 | 0.90 | 1.1 | 1.3 | 1.4 |
350 | 0.19 | 0.39 | 0.58 | 0.78 | 0.97 | 1.2 | 1.4 | 1.6 |
375 | 0.21 | 0.42 | 0.63 | 0.83 | 1.0 | 1.3 | 1.5 | 1.7 |
400 | 0.22 | 0.44 | 0.67 | 0.89 | 1.1 | 1.3 | 1.6 | 1.8 |
Table b. Overflow volume for dedicated measure (L/s) | |||||
---|---|---|---|---|---|
Design 5 minute duration rainfall intensity (mm/h) (from Table 3.5.2.1) | Roof Catchment Area (m2) | ||||
30 | 40 | 50 | 60 | 70 | |
150 | 1.3 | 1.7 | 2.1 | 2.5 | 2.9 |
175 | 1.5 | 1.9 | 2.4 | 2.9 | 3.4 |
200 | 1.7 | 2.2 | 2.8 | 3.3 | 3.9 |
225 | 1.9 | 2.5 | 3.1 | 3.8 | 4.4 |
250 | 2.1 | 2.8 | 3.5 | 4.2 | 4.9 |
275 | 2.3 | 3.1 | 3.8 | 4.6 | 5.3 |
300 | 2.5 | 3.3 | 4.2 | 5.0 | 5.8 |
325 | 2.7 | 3.6 | 4.5 | 5.4 | 6.3 |
350 | 2.9 | 3.9 | 4.9 | 5.8 | 6.8 |
375 | 3.1 | 4.2 | 5.2 | 6.3 | 7.3 |
400 | 3.3 | 4.4 | 5.6 | 6.7 | 7.8 |
Table 3.5.2.4 ACCEPTABLE OVERFLOW MEASURES
Table a. Acceptable continuous overflow measure | ||
---|---|---|
Description | Overflow Capacity (L/s/m) | Construction |
Front face slotted gutter with—
|
0.5 |
|
Controlled back gap with—
|
1.5 |
|
Controlled front bead height with the front bead of the gutter installed a minimum of 10 mm below the top of the fascia. | 1.5 |
|
Table b. Acceptable dedicated overflow measure per downpipe | ||
---|---|---|
Description | Overflow Capacity (L/s/m) | Construction |
End-stop weirNote 1 with—
|
0.5 |
|
Inverted nozzle installed within 500 mm of a gutter high point with—
|
1.2 |
|
Front face weir with—
|
1.0 |
|
Rainhead with—
|
3.5 |
|
Notes:
|
Stormwater drainage systems specified in the Housing Provisions are not designed to remove all water to an appropriate outfall during exceptionally heavy rain, particularly in tropical areas. Specifically, eaves gutter systems are designed to remove water arising from rainfall events with an average recurrence interval of 20 years provided they are not blocked. Accordingly, it is necessary to design and install the system to incorporate overflow measures so that when overflowing occurs, during a rainfall event with an average recurrence interval of up to 100 years, any water is directed away in a manner which ensures it does not pond against, enter or damage the building, even if the stormwater drainage system is blocked.
Insufficient and poorly located downpipes are a frequent cause of poor roof drainage system performance. The installation of downpipes, especially near valley gutters, is designed to ensure rainwater from areas on the roof that have concentrated water flows is adequately removed.
Particular consideration needs to be given to box gutters, valley gutters etc. located above the internal areas of a building.
There are several options available to designers using the requirements of the Housing Provisions. The designer will need to choose an overflow system that will cope with the rainfall intensity for the particular location. Consideration needs to be given to the total capacity of overflow measures on lower level roofs where overflow measures adopted for a higher roof catchment will result in overflow to a lower one. Overflow discharge onto lower roofs may also require consideration of sarking, flashing and other weatherproofing precautions to the lower roof area.
The acceptable overflow measures in Table 3.5.2.3 were calculated using the following formulas:
For continuous slots or rainhead | For front face weir, end stop weir, inverted nozzle, front bead or controlled gap |
Where— A = Area (m2) Cd = Discharge coefficient = 0.61 g = Gravity = 9.81 m/s2 h = Effective head (m) Q = Flow rate (m3/s) |
Where— b = Width (m) Cd = Discharge coefficient = 0.63 g = Gravity = 9.81 m/s2 h = Effective head (m) Q = Flow rate (m3/s) |