NCC 2016 Volume Two
Search the National Construction Code editions
Part 3.4.4 Structural Steel Members
Appropriate Performance Requirements
Where an alternative structural steel member system is proposed as a Performance Solution to that described in Part 3.4.4, that proposal must comply with—
The following terms are used in this Part:
Figure 3.4.4.0 EFFECTIVE MEMBER SPACING FOR STRUCTURAL STEEL BEARERS AND STRUTTING BEAMS |
|||
---|---|---|---|
Diagram a. | Single spanning rafter or joist | ||
|
|||
Design member | Member 1 | Member 2 | |
Effective member spacing | 0.5 x Span 1 | 0.5 x (Span 1 + Span 2) | |
Diagram b. | Continuous spanning rafter or joist | ||
|
|||
Design member | Member 1 | Member 2 | Member 3 |
Effective member spacing | 0.4 x Span 1 | 0.6 x (Span 1 + Span 2) | 0.5 x (Span 2) + Span 3 |
Steel member abbreviations are as follows:
P2.1.1 is satisfied for structural steel sections if they are designed and constructed in accordance with one of the following:
Steel structures: AS 4100.
Cold-formed steel structures: AS/NZS 4600.
Design requirements for other materials used in combination with structural steel members are described in Part 3.4.2, 3.4.3 or Part 3.11 — Structural design manuals.
Compliance with this acceptable construction practice satisfies in respect to structural stability, provided—
the building is located in an area with a design wind speed of not more than N3; and
the first dimension of steel sections is installed vertically; and
all loads are uniformly distributed (unless otherwise noted or allowed for); and
the building is one for which Appendix A of AS 1170.4 contains no specific earthquake design requirements; and
There are certain limitations on the application to domestic structures such as Class 1a and 1b buildings in Appendix A of AS 1170.4. These limitations include building height, roof slope, etc. For additional information refer to Appendix A of AS 1170.4.
the structural steel member is not subject to snow loads.
Compliance with 3.4.4.4 satisfies in respect to corrosion protection requirements.
Structural steel members may be used as follows:
Bearers supporting a timber floor or non-loadbearing stud wall — in accordance with Figure 3.4.4.1.
Strutting beams supporting roof and ceiling loads — in accordance with Figure 3.4.4.2.
Lintels supporting roof, ceiling, frame and timber floor — in accordance with Figure 3.4.4.3.
Columns — in accordance with 3.4.4.3.
Structural steel members described in this Part must be protected against corrosion in accordance with 3.4.4.4.
Joists, bearers and lintels must be restrained from lateral movement or twisting along their length by fixing rafters or joists to the top flange of the member so that it prevents that member from moving laterally.
End supports for joists, bearers and lintels must transfer loads to the footings and have a bearing distance as follows:
For single spans, the bearing distance must not be less than the width of the member.
For continuous spans, internal bearing must be not less than two times the width of the member.
Figure 3.4.4.1 BEARER SUPPORTING A TIMBER FLOOR AND NON-LOADBEARING STUD WALL |
||||||||||
---|---|---|---|---|---|---|---|---|---|---|
|
||||||||||
Table a. — Acceptable bearer spans | ||||||||||
Steel section | SINGLE SPAN | CONTINUOUS SPAN | ||||||||
Effective bearer spacing (m) | Effective bearer spacing (m) | |||||||||
1.8 | 2.4 | 3.0 | 3.6 | 4.2 | 1.8 | 2.4 | 3.0 | 3.6 | 4.2 | |
MAXIMUM SPAN OF BEARER (M) | MAXIMUM SPAN OF BEARER (M) | |||||||||
125TFB | 4.1 | 3.8 | 3.6 | 3.4 | 3.2 | 4.7 | 4.3 | 3.8 | 3.5 | 3.2 |
180UB16.1 | 5.1 | 4.7 | 4.5 | 4.3 | 4.1 | 5.9 | 5.5 | 5.2 | 5.0 | 4.7 |
200UB18.2 | 5.6 | 5.2 | 5.0 | 4.7 | 4.6 | 6.5 | 6.0 | 5.7 | 5.5 | 5.3 |
250UB25.7 | 6.8 | 6.4 | 6.0 | 5.8 | 5.6 | 7.9 | 7.4 | 7.0 | 6.7 | 6.4 |
250x150x9.0 RHS | 7.7 | 7.1 | 6.7 | 6.4 | 6.2 | 8.8 | 8.2 | 7.8 | 7.4 | 7.1 |
250x150x5.0 RHS | 6.8 | 6.3 | 5.9 | 5.7 | 5.5 | 7.8 | 7.2 | 6.8 | 6.5 | 6.3 |
310UB32.0 | 7.9 | 7.3 | 7.0 | 6.7 | 6.4 | 9.1 | 8.5 | 8.1 | 7.7 | 7.4 |
125x75x2.0 RHS | 3.1 | 2.8 | 2.6 | 2.5 | 2.4 | 4.0 | 3.7 | 3.5 | 3.3 | 3.1 |
125x75x3.0 RHS | 3.5 | 3.2 | 3.0 | 2.8 | 2.7 | 4.4 | 4.1 | 3.9 | 3.7 | 3.5 |
150x50x2.0 RHS | 3.4 | 3.1 | 2.8 | 2.7 | 2.5 | 4.2 | 3.9 | 3.7 | 3.5 | 3.4 |
150x50x3.0 RHS | 3.7 | 3.4 | 3.2 | 3.0 | 2.9 | 4.6 | 4.3 | 4.1 | 3.9 | 3.7 |
100TFC | 3.2 | 2.9 | 2.7 | 2.6 | 2.4 | 3.7 | 3.2 | 2.8 | 2.6 | 2.4 |
150PFC | 4.8 | 4.5 | 4.2 | 4.0 | 3.9 | 5.5 | 5.1 | 4.9 | 4.7 | 4.5 |
180PFC | 5.4 | 5.1 | 4.8 | 4.6 | 4.4 | 6.3 | 5.9 | 5.6 | 5.3 | 5.1 |
200PFC | 5.9 | 5.5 | 5.2 | 5.0 | 4.8 | 6.8 | 6.3 | 6.0 | 5.7 | 5.5 |
250PFC | 7.2 | 6.7 | 6.4 | 6.1 | 5.9 | 8.4 | 7.8 | 7.4 | 7.1 | 6.8 |
300PFC | 8.1 | 7.6 | 7.2 | 6.9 | 6.6 | 9.4 | 8.8 | 8.3 | 8.0 | 7.7 |
Notes:
|
Figure 3.4.4.2 STRUTTING BEAM SUPPORTING A ROOF AND CEILING |
||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Strutting beam application | ||||||||||
|
||||||||||
Table a. — Acceptable strutting beam spans | ||||||||||
Steel section | STEEL SHEET ROOF | TILED ROOF | ||||||||
Strutting beam spacing (m) | Strutting beam spacing (m) | |||||||||
1.8 | 2.4 | 3.0 | 3.6 | 4.2 | 1.8 | 2.4 | 3.0 | 3.6 | 4.2 | |
MAXIMUM SPAN OF STRUTTING BEAM (M) | MAXIMUM SPAN OF STRUTTING BEAM (M) | |||||||||
125TFB | 5.7 | 5.4 | 5.1 | 4.9 | 4.6 | 4.9 | 4.6 | 4.4 | 4.2 | 4.1 |
150UB14.0 | 6.4 | 6.0 | 5.7 | 5.4 | 5.1 | 5.5 | 5.2 | 4.9 | 4.7 | 4.5 |
200UB18.2 | 7.9 | 7.4 | 7.1 | 6.8 | 6.5 | 6.9 | 6.4 | 6.1 | 5.8 | 5.6 |
250UB31.4 | 10.0 | 9.4 | 9.0 | 8.7 | 8.4 | 8.8 | 8.2 | 7.8 | 7.5 | 7.2 |
310UB46.2 | 11.9 | 11.3 | 10.8 | 10.5 | 10.1 | 10.6 | 10.0 | 9.5 | 9.1 | 8.8 |
100TFC | 4.6 | 4.4 | 4.2 | 3.9 | 3.7 | 4.0 | 3.7 | 3.6 | 3.4 | 3.2 |
150PFC | 6.7 | 6.3 | 6.0 | 5.8 | 5.6 | 5.8 | 5.5 | 5.2 | 5.0 | 4.8 |
200PFC | 8.2 | 7.7 | 7.4 | 7.1 | 6.8 | 7.2 | 6.7 | 6.4 | 6.1 | 5.9 |
250PFC | 10.0 | 9.4 | 9.0 | 8.7 | 8.4 | 8.8 | 8.2 | 7.8 | 7.5 | 7.3 |
300PFC | 11.1 | 10.5 | 10.1 | 9.7 | 9.4 | 9.8 | 9.3 | 8.8 | 8.4 | 8.2 |
Notes:
|
Figure 3.4.4.3 LINTELS SUPPORTING ROOF, FRAMES AND TIMBER FLOORS |
||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Lintels supporting roof and floors | ||||||||||
|
||||||||||
Table a. — Acceptable spans for lintels | ||||||||||
Steel section | STEEL SHEET ROOF | TILED ROOF | ||||||||
Effective load width (m) | Effective load width (m) | |||||||||
1.8 | 2.4 | 3.0 | 3.6 | 4.2 | 1.8 | 2.4 | 3.0 | 3.6 | 4.2 | |
MAXIMUM SPAN OF LINTEL (M) | MAXIMUM SPAN OF LINTEL (M) | |||||||||
125TFB | 3.7 | 3.4 | 3.2 | 3.0 | 2.8 | 3.6 | 3.3 | 3.0 | 2.9 | 2.7 |
150UB14.0 | 4.1 | 3.9 | 3.7 | 3.5 | 3.3 | 4.0 | 3.7 | 3.5 | 3.3 | 3.2 |
200UB25.4 | 5.6 | 5.3 | 5.0 | 4.8 | 4.7 | 5.4 | 5.1 | 4.8 | 4.6 | 4.5 |
250UB31.4 | 6.6 | 6.2 | 5.9 | 5.7 | 5.5 | 6.3 | 6.0 | 5.7 | 5.4 | 5.2 |
100TFC | 2.8 | 2.6 | 2.4 | 2.3 | 2.1 | 2.7 | 2.5 | 2.3 | 2.1 | 2.0 |
150PFC | 4.4 | 4.1 | 3.9 | 3.7 | 3.6 | 4.2 | 3.9 | 3.7 | 3.6 | 3.4 |
200PFC | 5.4 | 5.0 | 4.8 | 4.6 | 4.4 | 5.1 | 4.8 | 4.6 | 4.4 | 4.2 |
250PFC | 6.6 | 6.2 | 5.9 | 5.7 | 5.5 | 6.3 | 6.0 | 5.7 | 5.4 | 5.3 |
75x75x5EA | 1.3 | 1.2 | 1.1 | – | – | 1.3 | 1.1 | – | – | – |
90x90x6EA | 1.9 | 1.6 | 1.5 | 1.3 | 1.2 | 1.7 | 1.5 | 1.4 | 1.3 | 1.2 |
100x100x6EA | 2.0 | 1.8 | 1.6 | 1.5 | 1.4 | 1.9 | 1.7 | 1.5 | 1.4 | 1.3 |
125x75x6UA | 2.3 | 2.0 | 1.8 | 1.7 | 1.5 | 2.2 | 1.9 | 1.7 | 1.6 | 1.4 |
150x100x10UA | 3.9 | 3.6 | 3.2 | 2.9 | 2.7 | 3.7 | 3.3 | 3.0 | 2.8 | 2.6 |
Notes:
|
Columns may support the area provided for in Table 3.4.4.1 provided—
the effective height of the column is determined in accordance with Figure 3.4.4.4; and
the floor area to be supported is determined in accordance with Figure 3.4.4.5; and
the load eccentricity between the centre of the column and the applied vertical loading complies with Figure 3.4.4.6.
Figure 3.4.4.4 DETERMINING EFFECTIVE COLUMN HEIGHT |
|||
---|---|---|---|
Diagram a. | Column height (H) | ||
|
|||
Table a. Column height factor (F1) | |||
BASE DETAIL | BRACING SYSTEM | ||
Fully Braced (1) Construction | Unbraced Construction (cantilever columns) (2) | ||
Cast into footing | 1.00 | 2.60 | |
Fixed by bolts to footing or slab | 1.20 | must not be used | |
Fixed by intermediate floor or bracing in both directions | 1.20 | 2.60 | |
Notes:
|
Figure 3.4.4.5 DETERMINING FLOOR AREA SUPPORTED |
|||
---|---|---|---|
Diagram a. | AREA SUPPORTED BY COLUMNS (Plan view) | Table a. | AREA SUPPORTED BY COLUMNS |
|
COLUMN | TOTAL AREA SUPPORTED | |
C1 | 0.375L1 x 0.375LA | ||
C2 | 0.625(L1 + L2) x 0.375LA | ||
C3 | 0.375L1 x 0.625(LA + LB) | ||
C4 | 0.625(L1 + L2) x 0.625(LA + LB) | ||
C5 | 0.375L1 x (L cant + 0.5LC) | ||
C6 | 0.625(L1 + L2) x (L cant + 0.5LC) | ||
Note: The total area supported depends on the position of the column in the structure as shown in Diagram a. To calculate the correct area supported by a column, match the column’s position with those shown in Diagram a. which shows a plan view of a floor and then calculate the total area supported from Table a. |
Figure 3.4.4.6 ACCEPTABLE LOAD ECCENTRICITY FOR COLUMNS |
---|
|
Table 3.4.4.1 COLUMNS
COLUMNS – SUPPORTING TIMBER FLOOR ONLY | ||||||
---|---|---|---|---|---|---|
COLUMN EFFECTIVE HEIGHT (mm) | FLOOR AREA SUPPORTED (m2) | |||||
5 | 10 | 15 | 20 | 25 | ||
CHS C250 | 600 | 60.3 x 3.6 | 88.9 x 4.0 | 101.6 x 5.0 | 114.3 x 5.4 | 139.7 x 5.0 |
1200 | 60.3 x 4.5 | 88.9 x 4.0 | 101.6 x 5.0 | 114.3 x 5.4 | 139.7 x 5.0 | |
1800 | 60.3 x 4.5 | 88.9 x 4.0 | 101.6 x 5.0 | 114.3 x 5.4 | 139.7 x 5.0 | |
2400 | 60.3 x 4.5 | 88.9 x 4.0 | 101.6 x 5.0 | 114.3 x 5.4 | 139.7 x 5.0 | |
3600 | 76.1 x 3.6 | 101.6 x 4.0 | 114.3 x 4.5 | 139.7 x 5.0 | 139.7 x 5.0 | |
CHS C350 | 600 | 60.3 x 2.9 | 88.9 x 2.6 | 101.6 x 3.2 | 114.3 x 3.6 | 139.7 x 3.5 |
1200 | 60.3 x 2.9 | 88.9 x 2.6 | 101.6 x 3.2 | 114.3 x 3.6 | 139.7 x 3.5 | |
1800 | 60.3 x 2.9 | 101.6 x 2.6 | 114.3 x 3.2 | 114.3 x 3.6 | 139.7 x 3.5 | |
2400 | 76.1 x 2.3 | 101.6 x 2.6 | 114.3 x 3.2 | 139.7 x 3.0 | 139.7 x 3.5 | |
3600 | 88.9 x 2.6 | 101.6 x 2.6 | 114.3 x 3.2 | 139.7 x 3.0 | 165.1 x 3.0 | |
SHS C350 | 600 | 50 x 50 x 2.5 | 75 x 75 x 2.5 | 75 x 75 x 4.0 | 100 x 100 x 4.0 | 100 x 100 x 4.0 |
1200 | 65 x 65 x 2.0 | 75 x 75 x 2.5 | 75 x 75 x 4.0 | 100 x 100 x 4.0 | 100 x 100 x 4.0 | |
1800 | 65 x 65 x 2.0 | 75 x 75 x 3.0 | 100 x 100 x 3.0 | 100 x 100 x 4.0 | 100 x 100 x 4.0 | |
2400 | 65 x 65 x 2.0 | 75 x 75 x 3.0 | 100 x 100 x 3.0 | 100 x 100 x 4.0 | 100 x 100 x 5.0 | |
3600 | 65 x 65 x 2.5 | 75 x 75 x 4.0 | 100 x 100 x 3.0 | 100 x 100 x 4.0 | 100 x 100 x 5.0 | |
SHS C450 | 600 | 50 x 50 x 2.0 | 65 x 65 x 2.5 | 75 x 75 x 3.0 | 100 x 100 x 2.8 | 100 x 100 x 3.3 |
1200 | 50 x 50 x 2.0 | 65 x 65 x 2.5 | 75 x 75 x 3.0 | 100 x 100 x 3.0 | 100 x 100 x 3.3 | |
1800 | 50 x 50 x 2.3 | 75 x 75 x 2.3 | 75 x 75 x 3.3 | 100 x 100 x 3.0 | 100 x 100 x 3.8 | |
2400 | 65 x 65 x 2.0 | 75 x 75 x 2.5 | 75 x 75 x 3.5 | 100 x 100 x 3.0 | 100 x 100 x 3.8 | |
3600 | 65 x 65 x 2.3 | 100 x 100 x 2.0 | 100 x 100 x 2.8 | 100 x 100 x 3.8 | 100 x 100 x 4.0 | |
COLUMNS — SUPPORTING TILE ROOF ONLY | ||||||
CHS C250 | 600 | 60.3 x 3.6 | 60.3 x 3.6 | 76.1 x 3.6 | 76.1 x 4.5 | 88.9 x 4.0 |
1200 | 60.3 x 3.6 | 60.3 x 3.6 | 76.1 x 3.6 | 76.1 x 4.5 | 101.6 x 4.0 | |
1800 | 60.3 x 3.6 | 60.3 x 3.6 | 76.1 x 3.6 | 76.1 x 4.5 | 101.6 x 4.0 | |
2400 | 60.3 x 3.6 | 60.3 x 4.5 | 76.1 x 3.6 | 88.9 x 4.0 | 101.6 x 4.0 | |
3600 | 60.3 x 3.6 | 76.1 x 3.6 | 76.1 x 4.5 | 88.9 x 4.0 | 101.6 x 4.0 | |
CHS C350 | 600 | 60.3 x 2.3 | 60.3 x 2.3 | 76.1 x 2.3 | 88.9 x 2.6 | 101.6 x 2.6 |
1200 | 60.3 x 2.3 | 60.3 x 2.9 | 76.1 x 2.3 | 88.9 x 2.6 | 101.6 x 2.6 | |
1800 | 60.3 x 2.3 | 60.3 x 2.9 | 88.9 x 2.6 | 88.9 x 2.6 | 101.6 x 2.6 | |
2400 | 60.3 x 2.3 | 76.1 x 2.3 | 88.9 x 2.6 | 88.9 x 2.6 | 101.6 x 2.6 | |
3600 | 60.3 x 2.3 | 76.1 x 2.3 | 88.9 x 2.6 | 101 x 2.6 | 101.6 x 3.2 | |
SHS C350 | 600 | 50 x 50 x 2.0 | 50 x 50 x 2.5 | 65 x 65 x 2.5 | 75 x 75 x 2.5 | 75 x 75 x 3.0 |
1200 | 50 x 50 x 2.0 | 50 x 50 x 2.5 | 65 x 65 x 2.5 | 75 x 75x 2.5 | 75 x 75 x 3.0 | |
1800 | 50 x 50 x 2.0 | 65 x 65 x 2.0 | 65 x 65 x 2.5 | 75 x 75 x 2.5 | 75 x 75 x 3.0 | |
2400 | 50 x 50 x 2.0 | 65 x 65 x 2.0 | 65 x 65 x 2.5 | 75 x 75 x 2.5 | 75 x 75 x 4.0 | |
3600 | 50 x 50 x 2.5 | 65 x 65 x 2.5 | 75 x 75 x 2.5 | 75 x 75 x 3.0 | 75 x 75 x 4.0 | |
SHS C450 | 600 | 50 x 50 x 1.6 | 50 x 50 x 2.0 | 65 x 65 x 2.0 | 65 x 65 x 2.3 | 65 x 65 x 2.8 |
1200 | 50 x 50 x 1.6 | 50 x 50 x 2.0 | 65 x 65 x 2.0 | 65 x 65 x 2.3 | 65 x 65 x 2.8 | |
1800 | 50 x 50 x 1.6 | 65 x 65 x 1.6 | 65 x 65 x 2.0 | 65 x 65 x 2.5 | 75 x 75 x 2.5 | |
2400 | 50 x 50 x 1.6 | 50 x 50 x 2.5 | 65 x 65 x 2.3 | 75 x 75 x 2.3 | 75 x 75 x 2.8 | |
3600 | 50 x 50 x 2.0 | 65 x 65 x 2.0 | 75 x 75 x 2.3 | 100 x 100 x 2.0 | 100 x 100 x 2.3 | |
Note: Tabulated values are the column sections to be used. |
Structural steel members that are not built into a masonry wall must be protected against corrosion in accordance with Table 3.4.4.2.
Table 3.4.4.2 PROTECTIVE COATINGS FOR STEELWORK
ENVIRONMENT | LOCATION | MINIMUM PROTECTIVE COATING | |
---|---|---|---|
General structural steel members | |||
MODERATE More than 1 km from breaking surf or more than 100 m from salt water not subject to breaking surf or non-heavy industrial areas |
INTERNAL | No protection required in a permanently dry locationNote 6 | |
EXTERNAL | Option 1. | 2 coats alkyd primer | |
Option 2. | 2 coats alkyd gloss | ||
Option 3. | Hot dip galvanise 300 g/m2 min | ||
Option 4. | Hot dip galvanise 100 g/m2 min plus— | ||
(a) 1 coat solvent based vinyl primer; or | |||
(b) 1 coat vinyl gloss or alkyd. | |||
SEVERE Within 1 km from breaking surf or within 100 m of salt water not subject to breaking surf or heavy industrial areas |
INTERNAL | Option 1. | 2 coats alkyd primer |
Option 2. | 2 coats alkyd gloss | ||
EXTERNAL | Option 1. | Inorganic zinc primer plus 2 coats vinyl gloss finishing coats | |
Option 2. | Hot dip galvanise 300 g/m2 | ||
Option 3. | Hot dip galvanise 100 g/m2 min plus— | ||
(a) 2 coats solvent based vinyl primer; or | |||
(b) 2 coats vinyl gloss or alkyd. | |||
Notes:
|