Filter
Part 2.3 Fire safety
Explanatory information:
Objective
O2.3
The Objective is to—
- safeguard the occupants from illness or injury by alerting them of a fire in the building so that they may safely evacuate; and
- avoid the spread of fire.
Functional Statements
F2.3.1 Protection from the spread of fire
A Class 1 building is to be protected from the spread of fire.
F2.3.2 Fire detection and early warning
A Class 1 building is to be provided with safeguards so that occupants are warned of a fire in the building so that they may safely evacuate.
Performance Requirements
P2.3.1 Spread of fire
A Class 1 building must be protected from the spread of fire from—
another building other than an associated Class 10 building; and
the allotment boundary, other than a boundary adjoining a road or public space.
(see Figure 2.3.1)
A Class 10a building must not significantly increase the risk of fire spread between Class 2 to 9 buildings.
State and Territory Variations
State and Territory Variations
In South Australia after P2.3.1(a)(i) delete P2.3.1(a)(ii) and insert SA P2.3.1(a)(ii) and (iii) as follows:
-
- the allotment boundary, other than a boundary adjoining a road or public space; and
- a Class 10b brush fence.
Note to Figure 2.3.1: This diagram indicates areas of potential fire spread. This situation will differ for corner allotments, etc.
P2.3.2 Automatic warning for occupants
In a Class 1 building, occupants must be provided with automatic warning on the detection of smoke so that they may evacuate in the event of a fire to a place of safety.
Verification Methods
V2.3.1.1 Avoidance of the spread of fire [P2.3.1(a)(i)]
Compliance with P2.3.1(a)(i) to avoid the spread of fire between buildings on the same allotment is verified when—
the external walls and any openings in the external walls of a building, less than 1.8 m from another building, are capable of withstanding 92.6 kW/m2 of heat flux for 60 minutes; and
the external walls extend to the underside of a non-combustible roof covering or non-combustible eaves lining in accordance with 3.7.2.4.
V2.3.1.2 Avoidance of the spread of fire [P2.3.1(a)(ii)]
Compliance with P2.3.1(a)(ii) to avoid the spread of fire from an allotment boundary is verified when—
the external walls and any openings in the external walls of a building, less than 0.9 m from an allotment boundary, are capable of withstanding 92.6 kW/m2 of heat flux for 60 minutes; and
the external walls extend to the underside of a non-combustible roof covering or non-combustible eaves lining in accordance with 3.7.2.4.
V2.3.1.3 Avoidance of the spread of fire [P2.3.1(b)] (adjoining allotment)
Compliance with P2.3.1(b) to avoid the spread of fire between buildings on adjoining allotments is verified when it is calculated that—
a building will not cause heat flux in excess of those set out in column 2 of Table V2.3.1.3 at locations within the boundaries of an adjoining property set out in column 1 of Table V2.3.1.3 where another building may be constructed; and
when located at the distances from the allotment boundary set out in column 1 of Table V2.3.1.3, a building is capable of withstanding the heat flux set out in column 2 of Table V2.3.1.3 without ignition.
Column 1 (Location) |
Column 2 (Heat flux [kW/m 2 ]) |
On boundary |
80 |
1 m from boundary |
40 |
3 m from boundary |
20 |
6 m from boundary |
10 |
V2.3.1.4 Avoidance of the spread of fire [P2.3.1(b)] (same allotment)
Compliance with P2.3.1(b) to avoid the spread of fire between buildings on the same allotment is verified when it is calculated that a building—
is capable of withstanding the heat flux set out in column 2 of Table V2.3.1.4 without ignition; and
will not cause heat flux in excess of those set out in column 2 of Table V2.3.1.4, when the distance between the buildings is as set out in column 1 of Table V2.3.1.4.
Column 1 (Location) |
Column 2 (Heat flux [kW/m 2 ]) |
0 m |
80 |
2 m |
40 |
6 m |
20 |
12 m |
10 |