NCC 2019 Volume Two
Search the National Construction Code editions
Part 3.3.5 Masonry veneer
Appropriate Performance Requirements
Where an alternative masonry veneer wall system is proposed as a Performance Solution to that described in Part 3.3.5, that proposal must comply with—
Performance RequirementsP2.1.1, P2.2.2 and P2.2.3 are satisfied for masonry veneer if it is designed and constructed in accordance with one of the following:
AS 3700.
AS 4773.1 and AS 4773.2.
Compliance with this acceptable construction practice satisfies Performance Requirements P2.1.1, P2.2.2 and P2.2.3 for masonry veneer provided—
the building is located in an area with a design wind speed of not more than N3; and
masonry veneer walls are constructed on footings that comply with Part 3.2; and
the building site soil classification is A, S or M; and
the building is not constructed in an alpine area; and
the building is one for which Appendix A of AS 1170.4 contains no specific earthquake design requirements.
Masonry veneer walls must not be greater than 8.5 m in height when measured above the adjacent finished ground level.
Masonry units must have a minimum characteristic unconfined compressive strength of—
3 MPa for solid or cored units; or
10 MPa for hollow units.
Masonry veneer walls must have a minimum veneer thickness of 90 mm.
Subject to (d), masonry units must be—
either clay or calcium silicate brick or concrete brick or block; and
classified and used in the exposure conditions appropriate to their classification as described in Table 3.3.5.1.
Exposure classification |
Masonry application |
Protected (P) |
Suitable for use in locations such as—
|
General purpose (GP) |
Suitable for use in all locations except those where 'Exposure class' is required. |
Exposure class (Exp) |
Suitable for use in all locations including severe local conditions such as—
|
The exposure classification or durability of a masonry unit is a measure of its resistance to attack by soluble salts, either in the ground or in the atmosphere. All masonry products manufactured are classified by their durability. The majority of uses will require either an Exposure class (Exp) product or a General Purpose (GP) product.
Mixing of panels consisting of clay masonry units with panels consisting of concrete or calcium silicate masonry units is not permitted unless—
at vertical junctions, a control joint is installed; and
at horizontal junctions between panels of different materials, a slip joint using a membrane similar to that used for damp-proof courses is installed.
Mortar used for masonry construction must comply with AS 3700 or AS 4773 except that the mortar may be mixed by volume in the proportions stated in Table 3.3.5.2.
Mortar mix by volume Note 1
Cement:lime:sand
Brick exposure classification
General use
Suitable for concrete masonry Note 2
Protected
1:2:9
1:0:5
General purpose
1:1:6
1:0:5
Exposure class
1:0.5:4.5
1:0:4.2
Notes to Table 3.3.5.2 :
Unless otherwise specified, masonry bed and perpend joints must have a nominal thickness of 10 mm.
Where raked joints are used they must not be—
raked deeper than 10 mm; or
used in saline environments or areas subject to heavy industrial airborne pollution.
The clear width of a cavity between the masonry veneer and the exterior face of the supporting frame must be not less than 25 mm wide and where the masonry veneer is constructed on a slab-on-ground, the cavity must be drained to the outside in accordance with 3.3.5.9.
The 25 mm clear width of the cavity needs to be maintained regardless of any wall membranes, sheet bracing or services installed to the supporting frame.
Damp-proof courses and flashings must consist of—
a material that complies with AS/NZS 2904; or
embossed black polyethylene film of high impact resistance and low slip, with a nominal thickness of 0.5 mm prior to embossing, and comply with clause 7.6 of AS/NZS 2904; or
polyethylene coated metal, that has an aluminium core of not less than 0.1 mm thick, is coated both sides with bitumen adhesive enclosed in polyethylene film of not less than 0.1 mm thick on each face, and has a nominal total thickness of not less than 0.5 mm prior to embossing; or
bitumen impregnated materials of not less than 2.5 mm thick, that comply with clause 7.5 of AS/NZS 2904; or
termite sheet materials complying with Part 3.1.4 (with no penetrations) serving the purpose of a damp-proof course and/or flashing that is continuous through the wall or pier.
Damp-proof courses and flashings must be—
located so as to form a continuous damp-proofing barrier—
around the bottom perimeter of walls where constructed on a concrete slab; and
in walls and piers below suspended floors; and
where a masonry wall passes through a roof; and
where a roof abuts an external masonry wall; and
to the bottom and tops of windows and doors and the like in accordance with (c), except a damp-proof course or a flashing need not be provided to the top of a window or door where the opening is protected by an eave of a width more than 3 times the height of the masonry veneer above the opening; and
continuous through the wall or pier and be visible from the outside face of the wall.
The location of a damp-proof course or flashing serving as a damp-proof course, must be not less than—
150 mm above the adjacent ground level; or
75 mm above the finished surface level of adjacent paved, concreted or landscaped areas that slope away from the wall; or
50 mm above finished paved, concreted or landscaped areas complying with 3.1.3.3(b)(ii) and protected from the direct effects of the weather by a carport, verandah or the like; or
in low rainfall intensity areas—
15 mm above finished paved, concreted or landscaped areas; or
0 mm above finished paved, concreted or landscaped areas if the damp-proof course is protected from the direct effects of the weather by a carport, verandah or the like.
Sill and head flashings serving openings must be—
installed so that the flashing extends not less than 150 mm beyond the reveals on each side of the opening; and
located not more than—
one course below the sill brick course; and
300 mm above the opening; and
turned up in the cavity not less than 150 mm above the opening; and
embedded not less than 30 mm into the masonry veneer; and
attached to the window or wall framing.
Except where excluded by (b), open perpendicular joints (weepholes) must be created in the course immediately above any flashing (including above any damp-proof course acting as a flashing) and be—
a minimum of 50 mm in height, by the width of the vertical mortar joint; and
at not more than 1.2 m centres; and
Veneer wall ties must—
comply with AS/NZS 2699.1 and be—
light duty veneer ties in areas where the design wind speed is not more than N2; and
medium duty ties—
in areas where the design wind speed is more than N2; and
where engaged piers are provided; and
be spaced and fixed in accordance with Table 3.3.5.3a and Table 3.3.5.3b; and
be protected against corrosion in accordance with Table 3.3.5.4.
Maximum spacings
450 mm wall stud spacing
600 mm wall stud spacing
Horizontal
Maximum 450 mm centres
Maximum 600 mm centres
Vertical
Maximum 400 mm
Maximum 400 mm
Location
Placement of wall ties
Unsupported panel sides and edges of openings
Within 300 mm of panel side or edge
Top of veneer panels and top of panels under openings
Within 300 mm or two courses (whichever is the lesser) of the top of veneer
Within 300 mm or two courses (whichever is the lesser) from the bottom of the veneer
Bottom of veneer panel in masonry rebate with membrane damp-proof course
In each of the first two courses
Where articulation joints occur
At both sides of the articulation joint within 300 mm from the joint
Engaged piers
Within 200 mm of the top of the pier
Note to Table 3.3.5.3b: Ties are to be fixed to the supporting frame at all regular stud positions using screws or nails.
Exposure condition
Tie specification - minimum corrosion protection
Areas—
Areas—
All other areas
Wall ties that are suitable for use in a more severe exposure condition are also suitable for use in less severe exposure conditions, i.e. stainless steel and engineered polymer ties are suitable for use in all conditions and 470g/m2 galvanised ties can be used in all exposure conditions except the most severe.
Except where excluded by (b), openings in masonry veneer must be spanned by steel lintels.
Openings in masonry veneer not more than 500 mm wide need not be provided with a steel lintel provided the opening is adequately supported.
Where a lintel is required it must comply with the following:
Steel lintels must comply with this Part or Part 3.4.4.
Steel lintels must—
be sized in accordance with Table 3.3.5.5; and
be installed with the long leg of lintel angle vertical; and
not carry more than a 110 mm thick veneer; and
not carry masonry more than 3 m in height when measured above the opening; and
have a minimum bearing length at each end of the lintel of—
for clear spans not more than 1 m - 100 mm; or
for clear spans more than 1 m - 150 mm (See Figure 3.3.5.2); and
have a minimum of three courses of masonry over openings; and
comply with the corrosion protection requirements of Table 3.3.5.6.
Lintel |
Maximum clear span of lintel (mm): ≤ 600 mm of masonry over opening |
Maximum clear span of lintel (mm) > 600 mm of masonry over opening |
Flat 75 x 8 |
700 |
700 |
Flat 100 x 10 |
900 |
900 |
Angle 90 x 90 x 6EA |
3000 |
2650 |
Angle 90 x 90 x 8EA |
3200 |
2800 |
Angle 100 x 100 x 6EA |
3350 |
2900 |
Angle 100 x 100 x 8EA |
3600 |
3040 |
Angle 150 x 90 x 8UA |
4200 |
3850 |
Note to Table 3.3.5.5: The lintels described in this Table must be not less than grade 300 MPa in accordance with AS 4100.
Durability class of lintel in accordance with AS/NZS 2699.3 Note 1 |
Material or protective requirements in accordance with AS/NZS 2699.3 Note 1 |
R1 R2 |
Hot dip galvanised with a minimum average coating thickness of 300 g/m2; or stainless steel 316L |
R3 |
Hot dip galvanised with a minimum average coating thickness of 600 g/m2; or stainless steel 316L |
R4 |
Stainless steel 316L |
Notes to Table 3.3.5.6 :
Vertical articulation joints must be provided in masonry veneer walls in accordance with (b), except in walls constructed on sites where the soil classification is A or S (see Part 3.2.4).
For the purposes of 3.3.5.13, the vertical articulation joint also performs the function of a contraction or expansion joint.
Articulation joints between masonry elements must have a width of not less than 10 mm and be provided (see Figures 3.3.5.3, 3.3.5.4 and 3.3.5.5)—
in straight, continuous walls having no openings - at not more than 6 m centres and within 4.5 m, but not closer than 470 mm of all corners; and
in straight, continuous walls with openings more than 900 x 900 mm - at not more than 5 m centres and located so that they are not more than 1.2 m away from openings; and
where the height of the wall changes by more than 20% - at the position of change in height; and
where a wall changes in thickness; and
at control or construction joints in footings or slabs; and
at junctions of walls constructed of different masonry materials.
Articulation joints must not be constructed adjacent to arched openings.
Articulation joints must either be filled with—
a compressible foam or polystyrene filler and a flexible sealant; or
a purpose made backer rod and a flexible sealant (see Figure 3.3.5.5).
Note to Figure 3.3.5.5: Joints and sealants may be painted to reduce visual impact.
Where engaged piers are installed to support subfloor framing, they must comply with the provisions of this Part and be constructed as follows:
Footings for piers must comply with Part 3.2.
Engaged piers must not support more than a single storey with a roof framing span of not more than 12 m.
Piers must be spaced at not more than 3 m centres with floor framing complying with—
Part 3.4.2 for steel framing; and
Part 3.4.3 for timber framing; and
Part 3.4.4 for structural steel framing.
Piers must be—
not more than 1.2 m high; and
a minimum thickness of 100 mm inclusive of mortar; and
a width greater than the depth of the timber or steel section which it is supporting (See Figure 3.3.5.6).
Piers must be tied or bonded to the external masonry wall, and where ties are used they must comply with 3.3.5.10.
Piers formed from hollow-core masonry units must be filled with grout.