NCC 2019 Volume Two
Search the National Construction Code editions
Part 3.9.1 Stairway and ramp construction
Appropriate Performance Requirements
Where an alternative stairway or ramp system is proposed as a Performance Solution to that described in Part 3.9.1, that proposal must comply with—
The following figures depict stairway members and associated terminology used to describe them in the Housing Provisions. Some items such as barriers and handrails have been omitted for clarity.
The requirements of this Part are to be read in conjunction with Part 3.10.4 where a building is located in an alpine area and contains an external stairway or ramp.
3.8.2.2 contains the required height for a ceiling above a stairway, ramp or landing, measured vertically above the nosing line of stairway treads or the floor surface of a ramp or landing.
Compliance with this acceptable construction practice satisfies Performance Requirement P2.5.1 for stairway and ramp construction.
A stairway must be designed to take loading forces in accordance with AS/NZS 1170.1 and must have—
Goings (G), risers (R) and a slope relationship quantity (2R + G) in accordance with Table 3.9.1.1, except as permitted by (b) and (c); and
Stair type |
Riser (R) |
Going (G) |
Slope relationship |
|||
(see Figure 3.9.1.4 below) |
(see Figure 3.9.1.4 below) |
(2R+G) |
||||
Max |
Min |
Max |
Min |
Max |
Min |
|
Stairs (other than spiral) |
190 |
115 |
355 |
240 |
700 |
550 |
Spiral |
220 |
140 |
370 |
210 |
680 |
590 |
Note to Table 3.9.1.1: Riser and going dimensions must be measured in accordance with Figure 3.9.1.4.
risers which do not have any openings that would allow a 125 mm sphere to pass through between the treads; and
treads of solid construction (not mesh or other perforated material) if the stairway is more than 10 m high or connects more than 3 storeys.
In the case of a stairway serving only non-habitable rooms, such as attics, storerooms and the like that are not used on a regular or daily basis—
the going (G), riser (R) and slope relationship quantity (2R + G) in accordance with Table 3.9.1.1 may be substituted with those in Table 3.9.1.2; and
need not comply with 3.9.1.2(a)(iv).
Riser (R) |
Going (G) |
Slope relationship |
|||
(2R+G) |
|||||
Max |
Min |
Max |
Min |
Max |
Min |
225 |
130 |
355 |
215 |
700 |
540 |
Note to Table 3.9.1.2: The going (G) must be not more than the tread depth plus a maximum gap of 30 mm between the rear edge of one tread and the nosing of the tread above.
3.9.1.2(a)(i) states that a stairway must have not more than 18 and not less than 2 risers in each flight. Where there are less than 2 risers in a flight, it does not comprise a stairway for the purpose of the BCA. 18 risers is considered to be the maximum reasonable number that an average person can negotiate before requiring a rest. Winders are counted as part of the maximum number of 18 risers. More than 1 riser is considered necessary for a person to observe and adjust to a change in level.
The purpose of 3.9.1.2 is to achieve constant going and riser dimensions deemed safe for people to walk up and down. This minimises the risk of people overstepping during descent on uneven stairs (due to short goings) and tripping on ascent (due to high risers). Table 3.9.1.1 and Table 3.9.1.2 express ratios between going and riser dimensions which are considered safe for use. 3.9.1.2(a)(iii) accounts for conditions such as movement of materials due to atmospheric moisture changes or minor deviations related to variations in materials which affect finished stair dimensions.
Diagram a illustrates adjacent risers within a flight with minor deviations in the materials affecting the finished stair dimensions. The nominated riser height is exceeded by riser A. As a consequence riser height B is less than the nominated riser height. The difference between riser A and riser B cannot exceed 5 mm.
Diagram b illustrates an entire flight with minor deviations in the materials affecting the finished riser dimensions. In addition to the 5 mm difference permitted between adjacent goings or risers, the maximum difference between the smallest and largest going or riser within a flight must not exceed 10 mm.
Despite the deviations shown in both Diagram a and Diagram b, the stairs in the flight are deemed constant.
Irrespective of any minor deviations permitted by 3.9.1.2(a)(iii), finished going and riser dimensions must not exceed the limitations stipulated in Table 3.9.1.1.
Minor deviations in a stairway |
|
Diagram a. |
Deviation in adjacent risers |
|
|
Notes: |
|
Diagram b. |
Deviations over a flight |
|
|
Notes: |
3.9.1.2(a)(iv) allows the use of open riser stairs. However, it limits the openings to 125 mm to minimise the risk of a person (especially a young child) falling through the opening created by the open riser.
3.9.1.2(a)(v) specifies a height where solid treads must be used so that people cannot see through them. This minimises the risk of people being affected by vertigo.
In the case of a stairway with winders—
Stairways with winders:
The point of measurement of the going (G) in the slope relationship quantity (2R + G) for tapered treads and treads in spiral stairways as described in Table 3.9.1.1 (see Figure 3.9.1.1a to Figure 3.9.1.1c) must be—
for tapered treads, other than treads in a spiral stairway—
not more than 1 m in width, the middle of the unobstructed width of the stairway (see Figure 3.9.1.1b); and
more than 1 m in width, 400 mm from the unobstructed width of each side of the stairway (see Figure 3.9.1.1c); and
for treads in spiral stairways, the point seven tenths of the unobstructed width from the face of the centre pole or support towards the handrail side (see Figure 3.9.1.2a and Figure 3.9.1.2b).
Figure 3.9.1.1 Measurement of slope relationship—Plan view
Figure 3.9.1.2 Spiral stairs
An external ramp serving an external doorway or a ramp within a building must—
be designed to take loading forces in accordance with AS/NZS 1170.1; and
have a gradient not steeper than 1:8; and
The requirements for slip-resistance treatment to stair treads, ramps and landings are as follows:
Treads must have—
a surface with a slip-resistance classification not less than that listed in Table 3.9.1.3 when tested in accordance with AS 4586; or
a nosing strip with a slip-resistance classification not less than that listed in Table 3.9.1.3 when tested in accordance with AS 4586.
The floor surface of a ramp must have a slip-resistance classification not less than that listed in Table 3.9.1.3 when tested in accordance with AS 4586.
Landings, where the edge leads to the flight below, must have—
a surface with a slip-resistance classification not less than that listed in Table 3.9.1.3 when tested in accordance with AS 4586, for not less than 190 mm from the stair nosing; or
a nosing strip with a slip-resistance classification not less than that listed in Table 3.9.1.3 when tested in accordance with AS 4586.
Application
Dry surface conditions
Wet surface conditions
Ramp not steeper than 1:8
P4 or R10
P5 or R12
Tread surface
P3 or R10
P4 or R11
Nosing or landing edge strip
P3
P4
Landings must—
be not less than 750 mm long and where this involves a change in direction, the length is measured 500 mm from the inside edge of the landing (see Figure 3.9.1.3a); and
have a gradient not steeper than 1:50; and
be provided where the sill of a threshold of a doorway opens onto a stairway or ramp that provides a change in floor level or floor to ground level greater than 3 risers or 570 mm (see Figure 3.9.1.3b); and
extend across the full width of a doorway; and
in the case of a stairway serving only non-habitable rooms, such as attics, storerooms and the like that are not used on a regular or daily basis, the requirements of (a) may be substituted with a minimum length of landing being not less than 600 mm long.
The purpose of a landing is to provide a rest area for people using the stairway or ramp, and to allow the stairway or ramp to change direction if needed.
The minimum length of a landing allows people using a stairway or ramp to rest, and reduces the risk of people falling more than one flight of stairs.
The maximum grade of 1 in 50 required under 3.9.1.5(b) makes sure that the landing is as level as possible, but still allows a slight slope for drainage if necessary.