NCC 2016 Volume Three
Search the National Construction Code editions
Section B Water Services
Drinking water that is not intentionally heated must be delivered at a temperature of less than 40 degrees Celsius.
A hose tap must be provided in men's public toilets adjacent to the urinals.
A solar water heater system installed in a new Class 1 building must comply with the Plumbing Regulations 2008.
* * * * *
Delete B2.2(a) and insert Vic B2.2(a) as follows:
This Verification Method is deleted.
Delete B2.2(a) and insert Vic B2.2(a) as follows:
The design, construction, installation, replacement, repair, alteration and maintenance of a heated water service must be in accordance with the following:
AS/NZS 3500.4 including the following additions:
Insert after clause 1.9.2:
In this clause 'heated water installation' means either a heated water reticulation heater and a heated water reticulation system or a heated water reticulation system; and
Insert after clause 4.3.2.4:
The provisions of clause 5.2.8 of AS/NZS 3500.1 apply to heated water reticulation; or
For a Class 1a or 10 building only, Section 3 of AS/NZS 3500.5 including the following addition:
Insert at the end of clause 3.2.2:
In this clause 'heated water installation' means either a heated water reticulation heater and a heated water reticulation system or a heated water reticulation system.
The requirements of this Part.
Delete B2.4 and insert Vic B2.4 as follows:
A solar water heater system installed in a new Class 1 building must comply with the Plumbing Regulations 2008.
The design, construction, installation, replacement, repair, alteration and maintenance of a non-drinking water service must be in accordance with—
AS/NZS 3500.1; or
for a Class 1a or Class 10 building only, Section 2 of AS/NZS 3500.5;
and the requirements of this Part, subject to the following:
From AS/NZS 3500.1, substitute the text of clauses 9.3.2.3(b) and (d) as follows:
(b) be of a type that has a removable handle;
(d) they shall have a non-standard inlet connecting thread and a standard hose connection outlet.
From AS/NZS 3500.5, substitute the text of clauses 2.17.5.3(b) and (d) as follows:
(b) be of a type that has a removable handle;
(d) they shall have a non-standard inlet connecting thread and a standard hose connection outlet.
The installation of an automatic fire sprinkler system must be in accordance with—
in the case of a Class 2, 3, 4, 9a or 9c building, substitute for the whole of Clause 5.7.10 in AS 2118.1: 2006, as issued, published or remade from time to time, with the following:
Covered balconies shall be sprinkler protected.