NCC 2016 Volume One
Search the National Construction Code editions
Section C Fire Resistance (Verification Methods)
Compliance with CP2(a)(iii) to avoid the spread of fire between buildings on adjoining allotments is verified when it is calculated that—
a building will not cause heat flux in excess of those set out in column 2 of Table CV1 at locations within the boundaries of an adjoining property set out in column 1 of Table CV1 where another building may be constructed; and
when located at the distances from the allotment boundary set out in column 1 of Table CV1, a building is capable of withstanding the heat flux set out in column 2 of Table CV1 without ignition.
Column 1 | Column 2 |
---|---|
Location | Heat Flux (kW/m2) |
On boundary | 80 |
1 m from boundary | 40 |
3 m from boundary | 20 |
6 m from boundary | 10 |
is a means to verify whether or not a building proposal achieves the requirements of in minimising the risk of fire spreading between buildings on adjoining allotments. A fire in one building should not cause the spread of fire to another building, because such fire spread potentially endangers public safety, health and amenity.
It is not compulsory for a designer to use . The designer has the choice of using:
If is used to calculate the level of heat flux, it is important to calculate the level at all the points referred to in . The maximum level is not necessarily at the boundary. The size and shape of the openings will influence the level of heat flux.
Whether a material will ignite from radiant heat depends on the amount of heat and whether an ignition source (such as a spark) is present.
The following values give some typical examples of the amount of radiant heat necessary to ignite common materials used in buildings and their construction. Note, these figures should not be taken to be absolute, and may be subject to a range of variables.
There are three mechanisms for transferring heat:
ConductionConduction is the transfer of heat from one source to the other when they are in contact.
ConvectionTakes place when the flames or fire plume carry the heat to another body. Convection includes the carrying of embers from a burning body that can cause ignition of a second body.
RadiationRadiation is the transfer of heat from one body to another. In essence this involves one body putting out enough heat to heat up another body without any form of contact, either directly or by way of flames or embers.
Radiation is the main mechanism for heat and fire spread between buildings.
By way of techniques developed in the field of physics, it is possible to calculate the amount of heat given off by a burning building. The answer depends on a number of factors, including:
Compliance with CP2(a)(iii) to avoid the spread of fire between buildings on the same allotment is verified when it is calculated that a building—
is capable of withstanding the heat flux set out in column 2 of Table CV2 without ignition; and
will not cause heat flux in excess of those set out in column 2 of Table CV2,
when the distance between the buildings is as set out in column 1 of Table CV2.
Table CV2
Column 1 | Column 2 |
---|---|
Distance between buildings | Heat Flux (kW/m2) |
0 m | 80 |
2 m | 40 |
6 m | 20 |
12 m | 10 |
Compliance with CP2 to avoid the spread of fire via the external wall of a building is verified when—
compliance with CP2(a)(iii) to avoid the spread of fire between buildings, where applicable, is verified in accordance with CV1 or CV2, as appropriate; and
the external wall system—
has been tested for external wall (EW) performance in accordance with AS 5113; and
has achieved the classification EW; and
if containing a cavity, incorporates cavity barriers and these cavity barriers have been included in the test performed under (i) at the perimeter of each floor; and
in a building of Type A construction, the building is protected throughout by a sprinkler system complying with Specification E1.5 and has—
sprinkler protection to balconies, patios and terraces, and where overhead sprinkler coverage is not achieved alongside the external wall, sidewall sprinkler heads are provided at the external wall for the extent of the balcony, patio or terrace where overhead sprinkler coverage is not achieved; and
for a building with an effective height greater than 25 m—
monitored stop valves provided at each floor level arranged to allow the isolation of the floor level containing the stop valve while maintaining protection to the remainder of the building; and
the sprinkler system being capable of providing sufficient flow to serve the design area (assumed area of operation) required by AS 2118.1 for the relevant hazard class on each floor level plus the design area (assumed area of operation) required by AS 2118.1 for the floor level above, except where the former level is—
the floor level below the uppermost roof; or
any floor level that is wholly below ground; and
in a building of Type B construction, the building is—
is protected throughout by a sprinkler system complying with Specification E1.5; or
has any openings in external walls separated by a slab or other horizontal construction complying with C2.6(a)(iv) as if the building were of Type A construction.
External wall of a building
CV3 is a means to verify whether or not a proposed external wall system achieves the requirements of CP2 in minimising the risk of fire spreading in a building and between buildings via the external walls of the subject building.
It is not compulsory for a designer to use CV3. The designer has the choice of using—
If CV3 is used, an external wall system must also be verified against CV1 or CV2, as well as meeting certain other fire safety measures, including ones specific to buildings of Type A and Type B construction.
Other fire safety measures are imposed in recognition that an external wall system tested to AS 5113 may contain combustible elements that still present a risk that needs to be mitigated in order to minimise the risk of fire spread via the external wall of a building.
The external wall system being tested to AS 5113 must reflect what is proposed to be installed, including cavities, cavity barriers, substrates and fixings. However, the external wall system being tested is not intended to include windows and doors.