NCC 2016 Volume Two
Search the National Construction Code editions
Part 3.9.2 Barriers And Handrails
Appropriate :
Compliance with this acceptable construction practice satisfies Performance RequirementsP2.5.2 for barriers and P2.5.1(b)(i) for handrails.
A continuous barrier must be provided along the side of—
any roof to which general access is provided; and
any stairway or ramp; and
a floor, corridor, hallway, balcony, deck, verandah, mezzanine, access bridge or the like; and
any delineated path of access to a building,
if the trafficable surface is 1 m or more above the surface beneath (see Figure 3.9.2.3).
The requirements of (a) do not apply to—
a retaining wall unless the retaining wall forms part of, or is directly associated with a delineated path of access to a building from the road, or a delineated path of access between buildings; or
a barrier provided to an openable window covered by 3.9.2.5.
The height of a barrier required by 3.9.2.2 must be in accordance with the following:
The height must not be less than 865 mm above the nosings of the stair treads or the floor of a ramp.
The height must not be less than—
1 m above the floor of any access path, balcony, landing or the like (see Figure 3.9.2.1); or
A transition zone may be incorporated where the barrier height changes from 865 mm on the stair flight or ramp to 1 m at the landing (see Figure 3.9.2.2).
Openings in barriers (including decorative balustrades) must be constructed so that they do not permit a 125 mm sphere to pass through it and for stairs, the opening is measured above the nosing line of the stair treads.
A barrier to a stairway serving a non-habitable room, such as an attic, storeroom or the like that is not used on a regular or daily basis, need not comply with (c) if—
openings are constructed so that they do not permit a 300 mm sphere to pass through; or
where rails are used, the barrier consists of a top rail and an intermediate rail, with the openings between rails not more than 460 mm.
A barrier, except a window serving as a barrier, must be designed to take loading forces in accordance with AS/NZS 1170.1.
A window forming part of a barrier is not required to comply with AS/NZS 1170.1 as it is exempted by 3.9.2.3(e). However, a window serving as a barrier must comply with the glazing assembly provisions of AS 2047 or AS 1288. These provisions consider the wind loading on the glass and human impact requirements.
For floors more than 4 m above the surface beneath, any horizontal elements within the barrier between 150 mm and 760 mm above the floor must not facilitate climbing.
Where a required barrier is constructed of wire it is deemed to meet the requirements of (c) if it is constructed in accordance with the following:
For horizontal wire systems—
when measured with a strain indicator, it must be in accordance with the tension values in Table 3.9.2.1; or
must not exceed the maximum deflections in Table 3.9.2.3.
For non-continuous vertical wire systems, when measured with a strain indicator, must be in accordance with the tension values in Table 3.9.2.1 (see Note 4).
For continuous vertical or continuous near vertical sloped wire systems—
must have wires of no more than 2.5 mm diameter with a lay of 7×7 or 7×19 construction; and
changes in direction at support rails must pass around a pulley block without causing permanent deformation to the wire; and
must have supporting rails, constructed with a spacing of not more than 900 mm, of a material that does not allow deflection that would decrease the tension of the wire under load; and
when the wire tension is measured with a strain indicator, it must be in accordance with the tension values in Table 3.9.2.2 and measured in the furthermost span from the tensioning device.
Table 3.9.2.1 WIRE BARRIER CONSTRUCTION – REQUIRED TENSION FOR STAINLESS STEEL HORIZONTAL WIRES
Clear distance between posts (mm) | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
600 | 800 | 900 | 1000 | 1200 | 1500 | 1800 | 2000 | 2500 | |||
Wire dia. (mm) | Lay | Wire spacing (mm) | Minimum required tension in Newtons (N) | ||||||||
2.5 | 7×7 | 60 | 55 | 190 | 263 | 415 | 478 | 823 | 1080 | 1139 | X |
80 | 382 | 630 | 730 | 824 | 1025 | 1288 | X | X | X | ||
100 | 869 | 1218 | 1368 | X | X | X | X | X | X | ||
2.5 | 1x19 | 60 | 35 | 218 | 310 | 402 | 585 | 810 | 1125 | 1325 | X |
80 | 420 | 630 | 735 | 840 | 1050 | 1400 | 1750 | X | X | ||
100 | 1140 | 1565 | X | X | X | X | X | X | X | ||
3.0 | 7x7 | 60 | 15 | 178 | 270 | 314 | 506 | 660 | 965 | 1168 | 1491 |
80 | 250 | 413 | 500 | 741 | 818 | 1083 | 1370 | 1565 | X | ||
100 | 865 | 1278 | 1390 | 1639 | X | X | X | X | X | ||
3.0 | 1x19 | 60 | 25 | 183 | 261 | 340 | 520 | 790 | 1025 | 1180 | X |
80 | 325 | 555 | 670 | 785 | 1015 | 1330 | 1725 | 1980 | X | ||
100 | 1090 | 1500 | 1705 | 1910 | X | X | X | X | X | ||
4.0 | 7x7 | 60 | 5 | 73 | 97 | 122 | 235 | 440 | 664 | 813 | 1178 |
80 | 196 | 422 | 480 | 524 | 760 | 1100 | 1358 | 1530 | 2130 | ||
100 | 835 | 1182 | 1360 | 1528 | 1837 | 2381 | 2811 | 3098 | X | ||
4.0 | 1x19 | 60 | 5 | 5 | 10 | 15 | 20 | 147 | 593 | 890 | 1280 |
80 | 30 | 192 | 300 | 415 | 593 | 1105 | 1303 | 1435 | 1844 | ||
100 | 853 | 1308 | 1487 | 1610 | 2048 | 2608 | 3094 | 3418 | 3849 | ||
4.0 | 7x19 | 60 | 155 | 290 | 358 | 425 | 599 | 860 | 1080 | 1285 | 1540 |
80 | 155 | 290 | 358 | 425 | 599 | 860 | 1080 | 1285 | 1540 | ||
100 | 1038 | 1412 | 1598 | 1785 | 2165 | 2735 | X | X | X | ||
Notes:
|
Table 3.9.2.2 CONTINUOUS WIRE BARRIER CONSTRUCTION – REQUIRED TENSION FOR VERTICAL OR NEAR VERTICAL STAINLESS STEEL WIRES
Wire dia. (mm) | Lay | Widest spacing between wires (mm) | Maximum clear spacing between rails (mm) |
---|---|---|---|
900 | |||
Required tension in Newtons (N) | |||
2.5 | 7x19 | 80 | 145 |
100 | 310 | ||
110 | 610 | ||
2.5 | 7x7 | 80 | 130 |
100 | 280 | ||
110 | 500 | ||
Notes:
|
Table 3.9.2.3 WIRE BARRIER CONSTRUCTION – MAXIMUM PERMISSIBLE DEFLECTION FOR STAINLESS STEEL WIRES
Clear distance between posts (mm) | |||||||
---|---|---|---|---|---|---|---|
600 | 900 | 1200 | 1500 | 1800 | 2000 | ||
Wire dia. (mm) | Wire spacing (mm) | Minimum required tension in Newtons (N) | |||||
2.5 | 60 | 17 | 11 | 9 | 8 | 8 | 8 |
80 | 7 | 5 | 5 | 5 | X | X | |
3.0 | 60 | 19 | 13 | 8 | 7 | 7 | 7 |
80 | 8 | 6 | 6 | 5 | 5 | 5 | |
4.0 | 60 | 18 | 12 | 8 | 8 | 7 | 7 |
80 | 8 | 6 | 4 | 4 | 4 | 4 | |
Notes:
|
A glass barrier must comply with AS 1288.
Figure 3.9.2.1 BARRIER CONSTRUCTION |
---|
|
Note: For the purposes of this Figure, a 125 mm sphere must not pass between rails or through the opening when measured above the nosing line. |
Figure 3.9.2.2 TRANSITION ZONES |
---|
|
Figure 3.9.2.3 BARRIERS — WHEN REQUIRED |
---|
|
Handrails to a stairway or ramp must—
be located along at least one side of the flight or ramp; and
be located along the full length of the flight or ramp, except in the case where a handrail is associated with a barrier the handrail may terminate where the barrier terminates; and
have the top surface of the handrail not less than 865 mm vertically above the nosings of the stair treads or the floor surface of the ramp; and
have no obstruction on or above them that will tend to break a handhold, except for newel posts, ball type stanchions, or the like.
The requirements of (a) do not apply to—
a stairway or ramp providing a change in elevation of less than 1 m; or
a landing; or
a winder where a newel post is installed to provide a handhold; or
a stairway or ramp in a Class 10 building.
A window opening must be provided with protection, if the floor below the window in a bedroom is 2 m or more above the surface beneath.
Where the lowest level of the window opening is less than 1.7 m above the floor, a window opening covered by (a) must comply with the following:
The openable portion of the window must be protected with—
a device capable of restricting the window opening; or
a screen with secure fittings.
A device or screen required by (i) must—
not permit a 125 mm sphere to pass through the window opening or screen; and
resist an outward horizontal action of 250 N against the—
window restrained by a device; or
screen protecting the opening; and
have a child resistant release mechanism if the screen or device is able to be removed, unlocked or overridden.
A barrier with a height not less than 865 mm above the floor is required to an openable window—
in addition to window protection, when a child resistant release mechanism is required by (b)(ii)(C); and
where the floor below the window is 4 m or more above the surface beneath if the window is not covered by (a).
A barrier covered by (c) must not—
permit a 125 mm sphere to pass through it; and
have any horizontal or near horizontal elements between 150 mm and 760 mm above the floor that facilitate climbing.
The intent of 3.9.2.5 is to limit the risk of a person (especially a young child) falling through an openable window. Where the floor level below an openable window is less than 2 m there are no specific requirements. For an openable window in a bedroom 2 m or more above the surface beneath, openable windows are required to restrict passage of a 125 mm sphere using any one of the following design solutions:
If the openable part of the window is at least 1.7 m above the floor, no further protection is required.
relates to a screen or window restricting device protecting an openable window in a bedroom. The screen or opening restricting device may be installed in a manner that allows it to be removed, unlocked or overridden in the event of a fire or other emergency to allow safe egress. In these situations the unlocking device must be child resistant.
Child resistance could be achieved by the need to use a tool, key or two hands.
There are a number of hardware options available. Short chain winders and barrier screens will allow windows to comply with this requirement. Sliding window locks may lock a sash so a 125 mm sphere cannot pass through. Where provision is made to fully open the window beyond 125 mm then the child resistant release mechanism is required in addition to the device resisting a 250 N force as required by 3.9.2.5(b)(ii)(B).
in addition prescribes that an 865 mm barrier (sill) would be required. A wall beneath an openable window can be considered as the barrier if the criteria in (d) are met.
relates to the height of a barrier under an openable window in a room that is not a bedroom in a Class 1 building or a window in a Class 10 building.
The term "window" is not italicised in 3.9.2.5 and as such, is not restricted to the definition of "window" in the BCA. The reason for this is to also capture windows that may let in air but not light, e.g. metal louvres. A metal louvre or openable panel would not fit in the BCA definition of window but is subject to the window barrier provisions.