NCC 2016 Volume Two
Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

Filter

Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c
Part 3.12.5 Services

Part 3.12.5 Services

3.12.5 Application

This Part applies to—

(a)

a Class 1 building; and

(b)

a Class 10a building; and

(c)

a Class 10b swimming pool associated with a Class 1 or 10a building.

Acceptable construction manual

3.12.5.0

A heated water supply system must be designed and installed in accordance with Part B2 of NCC Volume Three — Plumbing Code of Australia.

Acceptable construction practice

3.12.5.1 Insulation of services

Thermal insulation for central heating water piping and heating and cooling ductwork must—

(a)

be protected against the effects of weather and sunlight; and

(b)

be able to withstand the temperatures within the piping or ductwork; and

(c)

use thermal insulation material in accordance with AS/NZS 4859.1.

Explanatory information

Explanatory information:

The central heating water piping provisions apply to systems designed to heat the building via water, such as a hydronic heating system.

3.12.5.2 Central heating water piping

Central heating water piping that is not within a conditioned space must be thermally insulated to achieve the minimum material R-Value in accordance with Table 3.12.5.1.

Table 3.12.5.1 CENTRAL HEATING WATER PIPING—MINIMUM MATERIAL R-VALUE

to be insulated

Minimum material R-Value for each climate zone

1, 2, 3 and 5 4, 6 and 7 8
1. Internal
  1. All flow and return piping that is—
    1. within an unventilated wall space; or
    2. within an internal floor between storeys; or
    3. between ceiling insulation and a ceiling.
  2. All heated water piping encased within a concrete floor slab (except that which is part of a floor heating system).
0.4 0.4 0.4
2. located within a ventilated wall space, an enclosed building subfloor or a roof space
  1. All flow and return piping.
  2. Cold water supply piping — within 500 mm of the connection to the central water heating system.
  3. Relief valve piping — within 500 mm of the connection to the central water heating system.
0.6 0.9 1.3
3. located outside the building or in an unenclosed building subfloor or roof space
  1. All flow and return piping.
  2. Cold water supply piping — within 500 mm of the connection to the central water heating system.
  3. Relief valve piping — within 500 mm of the connection to the central water heating system.
0.6 1.3 1.3

Explanatory information

Explanatory information:
  1. The insulation levels in the following table are typical examples of materials that can be used to insulate central heating water piping calculated in accordance with AS/NZS 4859.1.
  2. The R-Value is that of the insulation and not the Total R-Value of the pipe, air film and insulation. Where piping has a significant inherent R-Value it may be subtracted from the material R-Value required. However, the inherent R-Value of most piping material is not sufficient to satisfy the requirements in Table 3.12.5.1.
  3. Piping within a timber member, such as that passing through a wall stud, is considered to have sufficient insulation for the purposes of Table 3.12.5.1.
  4. The following table provides examples for the R-Value of the insulation used for smaller diameter piping.
Insulation R-Value
9 mm of closed cell polymer 0.4
13 mm of closed cell polymer 0.6
19 mm of closed cell polymer 0.9
25 mm of closed cell polymer 1.3
25 mm of glasswool 1.3

3.12.5.3 Heating and cooling ductwork

(a)

Heating and cooling ductwork and fittings must—

(i)

achieve the material R-Value in Table 3.12.5.2; and

(ii)

be sealed against air loss—

(A)

by closing all openings in the surface, joints and seams of ductwork with adhesives, mastics, sealants or gaskets in accordance with AS 4254 Parts 1 and 2 for a Class C seal; or

(B)

for flexible ductwork, with a draw band in conjunction with a sealant or adhesive tape.

(b)

Duct insulation must—

(i)

abut adjoining duct insulation to form a continuous barrier; and

(ii)

be installed so that it maintains its position and thickness, other than at flanges and supports; and

(iii)

where located outside the building, under a suspended floor, in an attached Class 10a building or in a roof space—

(A)

be protected by an outer sleeve of protective sheeting to prevent the insulation becoming damp; and

(B)

have the outer protective sleeve sealed with adhesive tape not less than 48 mm wide creating an airtight and waterproof seal.

(c)

The requirements of (a) do not apply to heating and cooling ductwork and fittings located within the insulated building envelope including a service riser within the conditioned space, internal floors between storeys and the like.

Explanatory information

Explanatory information:

Ductwork within a fully insulated building may still benefit from insulation particularly when the system is only operating for short periods.

In some climate zones condensation may create problems with uninsulated ductwork and insulation should still be considered.

Table 3.12.5.2 HEATING AND COOLING DUCTWORK AND FITTINGS—MINIMUM MATERIAL R-VALUE

Ductwork element Minimum material for ductwork and fittings in each
Heating-only system or cooling-only system including an evaporative cooling system Combined heating and refrigerated cooling system
1, 2, 3, 4, 5, 6 and 7 8 1, 2, 3, 4, 5, 6 and 7 2 and 5 8
Ductwork 1.0 1.5 1.5 (see note) 1.0 1.5
Fittings 0.4

Note: The minimum material R-Valuerequired for ductwork may be reduced by 0.5 for combined heating and refrigerated cooling systems in climate zones 1, 3, 4, 6, and 7 if the ducts are—

  1. under a suspended floor with an enclosed perimeter; or
  2. in a roof space that has insulation of not less than R0.5 directly beneath the roofing.

Explanatory information

Explanatory information:
  1. For information on an enclosed perimeter, refer to the explanatory information following Table 3.12.1.4.
  2. Insulation for refrigerated cooling ductwork should have a vapour barrier to prevent possible damage by condensation.
  3. The insulation levels in the following table are typical examples of materials that can be used to insulate ductwork and fittings and the R-Values they contribute. Other methods are available for meeting the minimum material R-Valuerequired by Table 3.12.5.2.
Insulation

Fittings

11 mm polyurethane

0.4

Flexible ductwork

45 mm glasswool (11 kg/m3)

70 mm polyester (6.4 kg/m3)

63 mm glasswool (11 kg/m3)

90 mm polyester (8.9 kg/m3)

85 mm glasswool (11 kg/m3)

1.0

1.0

1.5

1.5

2.0

Sheetmetal ductwork — external insulation

38 mm glasswool (22 kg/m3)

50 mm polyester (20 kg/m3)

50 mm glasswool (22 kg/m3)

75 mm polyester (20 kg/m3)

1.0

1.1

1.5

1.7

Sheetmetal ductwork — internal insulation

38 mm glasswool (32 kg/m3)

50 mm polyester (32 kg/m3)

50 mm glasswool (32 kg/m3)

1.0

1.3

1.5

  1. Any flexible ductwork used for the transfer of products, initiating from a heat source that contains a flame, must also have the fire hazard properties required by 3.7.1.9.

3.12.5.4 Electric resistance space heating

An electric resistance space heating system that serves more than one room must have—

(a)

separate isolating switches for each room; and

(b)

a separate temperature controller and time switch for each group of rooms with common heating needs; and

(c)

power loads of not more than 110 W/m2 for living areas, and 150 W/m2 for bathrooms.

3.12.5.5 Artificial lighting

(a)

The lamp power density or illumination power density of artificial lighting, excluding heaters that emit light, must not exceed the allowance of—

(i)

5 W/m2 in a Class 1 building; and

(ii)

4 W/m2 on a verandah, balcony or the like attached to a Class 1 building; and

(iii)

3 W/m2 in a Class 10a building associated with a Class 1 building.

(b)

The illumination power density allowance in (a) may be increased by dividing it by the illumination power density adjustment factor for a control device in Table 3.12.5.3 as applicable.

(c)

When designing the lamp power density or illumination power density, the power of the proposed installation must be used rather than nominal allowances for exposed batten holders or luminaires.

Explanatory information

Explanatory information:
  1. There are two approaches available for achieving compliance with (a) in Class 1 and associated Class 10a buildings. These are through the determination of the lamp power density or the illumination power density.
  2. The first step in achieving compliance is to determine the relevant lamp power density or illumination power density allowance. Generally the lamp power density or illumination power density is the relevant value in (a)(i), (ii) or (iii), however the illumination power density allowance can be increased in accordance with (b) if a control device is used.

    When illumination power density and one or more control devices are used, the adjustment factor is only applied to the space(s) served by the control device. The adjusted allowance for this space is then combined with the allowances for the remaining spaces using an area weighted average, which subsequently increases the allowance provided in (a)(i), (ii) or (iii).

    When no control device is used, the adjustment factor is equal to 1.

    The second step in achieving compliance is to assess the design lamp power density density or design illumination power density.

  3. The design lamp power density is calculated by adding the maximum power ratings of all the permanently wired lamps in a space and dividing this sum by the area of the space.
  4. The design illumination power density is calculated by adding the illumination power load for each space and dividing this sum by the area of the space.

    Control device adjustment factors in (b) are only applied to the illumination power density, not the design illumination power density.

  5. To comply with (a), the design lamp power density or design illumination power density must be less than or equal to the allowance.
  6. Trading of allowances between (a)(i), (ii) and (iii) is not permitted.
  7. (a)(ii) includes outdoor living spaces such as verandahs, balconies, patios, alfresco spaces or the like that are attached to a Class 1 building.
  8. The artificial lighting requirements in 3.12.5.5 are to be read in conjunction with the artificial lighting requirements in 3.8.4.3.
(d)

Halogen lamps must be separately switched from fluorescent lamps.

(e)

Artificial lighting around the perimeter of a building must—

(i)

be controlled by a daylight sensor; or

(ii)

have an average light source efficacy of not less than 40 Lumens/W.

Explanatory information

Explanatory information:

The artificial lighting around the perimeter of a building does not need to comply to a maximum power density as neither the lighting required or the area of the space can be easily defined. Instead, external lights are required to be controlled by daylight sensors or to be efficient.

Table 3.12.5.3 ILLUMINATION POWER DENSITY ADJUSTMENT FACTOR FOR A CONTROL DEVICE

Item Description Illumination power density adjustment factor
Lighting timer For corridor lighting 0.7
Motion detector
  1. Where—
    1. at least 75% of the area of a space is controlled by one or more motion detectors; or
    2. an area of less than 200 m2 is switched as a block by one or more detectors.
0.9
  1. Where up to 6 lights are switched as a block by one or more detectors.
0.7
  1. Where up to 2 lights are switched as a block by one or more detectors.
0.55
Manual dimming system Note 1 Where not less than 75% of the area of a space is controlled by manually operated dimmers. 0.85
Programmable dimming system Note 2 Where not less than 75% of the area of a space is controlled by programmable dimmers. 0.85
Dynamic dimming system Note 3 Automatic compensation for lumen depreciation.

The design lumen depreciation factor of not less than—

  1. for fluorescent lights, 0.9; or
  2. for high pressure discharge lights, 0.8.
Fixed dimming Note 4 Where at least 75% of the area is controlled by fixed dimmers that reduce the overall lighting level and the power consumption of the lighting. % of full power to which the dimmer is set divided by 0.95.
Daylight sensor and dynamic lighting control device – dimmed or stepped switching of lights adjacent windows
  1. Lights within the space adjacent to windows other than roof lights for a distance from the window equal to the depth of the floor to window head height.
0.5 Note 5
  1. Lights within the space adjacent to roof lights.
0.6 Note 5

Notes:

  1. Manual dimming is where lights are controlled by a knob, slider or other mechanism or where there are pre-selected scenes that are manually selected.
  2. Programmed dimming is where pre-selected scenes or levels are automatically selected by the time of day, photoelectric cell or occupancy sensor.
  3. Dynamic dimming is where the lighting level is varied automatically by a photoelectric cell to either proportionally compensate for the availability of daylight or the lumen depreciation of the lamps.
  4. Fixed dimming is where lights are controlled to a level and that level cannot be adjusted by the user.
  5. The illumination power density adjustment factor is only applied to lights controlled by that item. This adjustment factor does not apply to tungsten halogen or other incandescent sources.

3.12.5.6 Water heater in a heated water supply system

A water heater in a heated water supply system must be designed and installed in accordance with Part B2 of NCC Volume Three — Plumbing Code of Australia.

3.12.5.7 Swimming pool heating and pumping

(a)

Heating for a swimming pool must be by—

(i)

a solar heater not boosted by electric resistance heating; or

(ii)

a heater using reclaimed energy; or

(iii)

a gas heater; or

(iv)

a heat pump; or

(v)

a combination of (i) to (iv).

(b)

Where some or all of the heating required by (a) is by a gas heater or a heat pump, the swimming pool must have—

(i)

a cover unless located in a conditioned space; and

(ii)

a time switch to control the operation of the heater.

(c)

A time switch must be provided to control the operation of a circulation pump for a swimming pool.

(d)

For the purposes of 3.12.5.7, a swimming pool does not include a spa pool.

Explanatory information

Explanatory information:

Some jurisdictions may have requirements for a pool cover under the Smart Approved Water Mark Scheme.

3.12.5.8 Spa pool heating and pumping

(a)

Heating for a spa pool that shares a water recirculation system with a swimming pool must be by—

(i)

a solar heater; or

(ii)

a heater using reclaimed energy; or

(iii)

a gas heater; or

(iv)

a heat pump; or

(v)

a combination of (i) to (iv).

(b)

Where some or all of the heating required by (a) is by a gas heater or a heat pump, the spa pool must have—

(i)

a cover; and

(ii)

a push button and a time switch to control the operation of the heater.

(c)

A time switch must be provided to control the operation of a circulation pump for a spa pool having a capacity of 680 L or more.