Happy Holidays! We wish you a happy and safe holiday season. Please note that the ABCB office will be closed from 24 December 2024 until 2 January 2025.
NCC 2022 Volume Two - Building Code of Australia Class 1 and 10 buildings
Search the National Construction Code editions
Filter
2
Specification 2 Descriptions of elements referred to in Specification 1
Specification 2 Descriptions of elements referred to in Specification 1
Specification 2 provides descriptions of the building elements listed in the tables referenced in Specification 1. This is intended to provide the necessary details to ensure that compliance is achieved.
Masonry units of ashlar, calcium silicate, concrete or fired clay (including terracotta blocks) must be laid in cement mortar or composition mortar complying with the relevant provisions of AS 3700.
Gypsum-sand mortar and gypsum-sand plaster must consist of either—
not more than 3 parts by volume of sand to 1 part by volume of gypsum; or
if lime putty is added, not more than 2.5 parts by volume of sand to 1 part by volume of gypsum and not more than 5% of lime putty by volume of the mixed ingredients.
Gypsum-perlite or gypsum-vermiculite plaster must be applied—
in either one or 2 coats each in the proportions of 1 m3 of perlite or vermiculite to 640 kg of gypsum if the required thickness of the plaster is not more than 25 mm; and
in 2 coats if the required thickness is more than 25 mm, the first in the proportions of 1 m3 of perlite or vermiculite to 800 kg of gypsum and the second in the proportions of 1 m3 of perlite or vermiculite to 530 kg of gypsum.
If plaster used as fire protection on walls is more than 19 mm thick—
it must be reinforced with expanded metal lath that—
has a mass per unit area of not less than 1.84 kg/m2; and
has not fewer than 98 meshes per metre; and
is protected against corrosion by galvanising or other suitable method; or
it must be reinforced with 13 mm x 13 mm x 0.7 mm galvanised steel wire mesh securely fixed at a distance from the face of the wall of not less than ⅓ of the total thickness of the plaster.
For masonry in which the amount of perforation or coring of the units does not exceed 25% by volume (based on the overall rectangular shape of the unit) the thickness of the wall must be calculated from the manufacturing dimensions of the units and the specified thickness of the joints between them as appropriate.
For masonry in which the amount of perforation or coring of the units exceeds 25% by volume (based on the overall rectangular shape of the unit) the thickness of the wall must be calculated from the equivalent thicknesses of the units and the specified thickness of the joints between them as appropriate.
The ratio of height between lateral supports to overall thickness of a wall of ashlar, no-fines concrete, unreinforced concrete, solid gypsum blocks, gypsum-perlite or gypsum-vermiculite plaster on metal lath and channel, must not exceed—
If a wall of ashlar, solid gypsum blocks or concrete is plastered on both sides to an equal thickness, the thickness of the wall for the purposes of Tables S1C2b and S1C2c (but not for the purposes of S2C5) may be increased by the thickness of the plaster on one side.
(1) Where Tables S1C2e, S1C2f, S1C2g, S1C2h, S1C2i and S1C2j indicate that column-protection is to be plastered, the tabulated thicknesses are those of the principal material.
(2) The thicknesses referred to in (1) do not include the thickness of plaster, which must be additional to the listed thickness of the material to which it is applied.
A column incorporated in or in contact on one or more sides with a wall of solid masonry or concrete at least 100 mm thick may be considered to be exposed to fire on no more than 3 sides.
A beam, open-web joist, girder or truss in direct and continuous contact with a concrete slab or a hollow block floor or roof may be considered to be exposed to fire on no more than 3 sides.
(1) The spaces between the fire-protective material and the steel (and any re-entrant parts of the column itself) must be filled solid with a fire-protective material like concrete, gypsum or grout.
(2) The insides of hollow sections, including pipes, need not be filled.
The proportion of cored holes or perforations in a hollow terracotta block (based on the overall rectangular volume of the unit) must not exceed the following:
For blocks up to 75 mm thick — 35%.
For blocks more than 75 mm but not more than 100 mm thick — 40%.
Reinforcing for column and beam protection — masonry
2019: Sch. 5 (Annex): 11.1
Masonry of calcium-silicate, fired clay and concrete for the protection of steel columns must have steel-wire or mesh reinforcement in every second course and lapped at the corners.
Reinforcing for column and beam protection — gypsum blocks and hollow terracotta blocks
2019: Sch. 5 (Annex): 11.2
Gypsum blocks and hollow terracotta blocks for the protection of steel columns must have steel-wire or mesh reinforcement in every course and lapped at corners.
Reinforcing for column and beam protection — structural concrete and poured gypsum
2019: Sch. 5 (Annex): 11.3
If a steel column or a steel beam is to be protected with structural concrete or poured gypsum, the concrete or gypsum must be reinforced with steel-wire mesh or steel-wire binding placed about 20 mm from its outer surface, and—
for concrete or gypsum less than 50 mm thick, the steel wire must be—
at least 3.15 mm in diameter; and
spaced at not more than 100 mm vertically; or
for concrete or gypsum not less than 50 mm thick, the steel wire must be either—
of a diameter and spacing in accordance with (a); or
at least 5 mm in diameter and spaced at not more than 150 mm vertically.
Reinforcing for column and beam protection — gypsum-perlite or gypsum-vermiculite plaster sprayed to contour
2019: Sch. 5 (Annex): 11.4
(1) If a steel column or steel beam is protected with either gypsum-perlite or gypsum-vermiculite plaster sprayed to contour and the construction falls within the limits of Table S2C26a or S2C26b, the plaster must be reinforced with—
(2) The reinforcement must be placed at a distance from the face of the plaster of at least 1/3 of the thickness of the plaster and must be securely fixed to the column or beam at intervals of not more than the relevant listing in Tables S2C26a and S2C26b.
Measurement of thickness of column and beam protection
2019: Sch. 5 (Annex): 12.1
The thickness of the fire protection to steel columns and steel beams (other than fire protection of gypsum-perlite or gypsum-vermiculite plaster sprayed on metal lath or sprayed to contour) is to be measured from the face or edge of the steel, from the face of a splice plate or from the outer part of a rivet or bolt, whichever is the closest to the outside of the fire-protective construction, except that—
if the thickness of the fire protection is 40 mm or more, rivet heads may be disregarded; and
if the thickness of the fire protection is 50 mm or more—
any part of a bolt (other than a high-tensile bolt) may be disregarded; and
a column splice plate within 900 mm of the floor may encroach upon the fire protection by up to a ¼ of the thickness of the fire protection; and
the flange of a column or beam may encroach by up to 12 mm upon the thickness of the fire protection at right angles to the web if—
the column or beam is intended to have an FRL of 240/240/240 or 240/–/–; and
the flange projects 65 mm or more from the web; and
the thickness of the edge of the flange (inclusive of any splice plate) is not more than 40 mm.