This video from the 2022 NCC Seminars discusses Part 5.4 Unreinforced single leaf masonry from the NCC 2022 Housing Provisions.
Transcript
0:00
[Music]
0:09
My name is Phil Finnimore, with the Australian Building Codes Board and today I'm going to talk to you about masonry
0:16
construction and the details within Volume Two and the Housing Provisions of NCC 2022.
0:24
H1D5 of Volume Two sets out the Deemed-to-Satisfy pathways shown in this slide. On the right hand
0:31
side is AS 3700 or the 4773.1 and .2 suite of standards. This is known in 2019 as an acceptable
0:41
construction manual simply referenced in the Housing Provisions for 2022 as reference documents.
0:48
If you choose this path they're the relevant standards if you don't choose this path you can go
0:54
to Part 5.4, that's on the left hand side of this slide, which are the Deemed-to-Satisfy requirements
1:01
set out in the Housing Provisions for 2022. So to be clear for masonry there's a choice a complete
1:07
choice between a referenced Australian Standard 3700 or 4773 or Part 5.4 of the Housing Provisions.
1:20
Comparisons between 2019 Volume Two and the Housing Provisions
1:24
which is where the Deemed-to-Satisfy requirements are for masonry construction
1:29
on the left Part 3.3 2019 starts at 3.3.1 go through go through to Part 3.3.6
1:37
unreinforced masonry all the way through to ice isolated masonry repairs.
1:43
What we've changed for NCC 2022 is the addition of cavity masonry Deemed-to-Satisfy requirements
1:51
and unreinforced single leaf masonry requirements. These are in addition to those of 2019 and I'll
1:58
talk about some details of those and how Volume Two connects those to the Housing Provisions
2:05
H1D5 is the relevant Deemed-to-Satisfy provision in Volume Two for Masonry
2:12
and this is the connection between the relevant Australian Standards if you choose those as the
2:17
Deemed-to-Satisfy solution so that's 3700 or 4773 Parts (1) and (2) or if you choose to
2:25
use the Deemed-to-Satisfy requirements of the Housing Provisions it will take it to
2:29
Part 5.2 that's in H1D5(1)(c) and this is where the limitations exist if you use the
2:37
Housing Provisions. Noting the first one there is the maximum wind speed for a design of a
2:42
building using the Housing Provisions is not to be more than N3, a wind speed of N3.
2:50
Other limitations relate to the classification of the site A, S and M that's a site classification
2:59
that's also similar to that for footings and slab construction. So the limitations there
3:04
for wind speed site classification and also a new requirement that speaks to design for
3:12
earthquake if you have a design for earthquake in a house or any residential construction it's
3:20
limited to the extent that you have to go back into the Australian Standards 3700 or 4773 for
3:28
your solution. So in summary if your building requires earthquake design you have
3:33
to go back to the relevant Australian Standard you can't continue to use the Housing Provisions.
3:40
Talking in a bit of detail about Part 5.3 cavity masonry and we're talking about limitations within
3:48
the element of cavity masonry as a type of wall so we've discussed the fact that there
3:53
are limitations set out broadly in Volume Two in H1D5, but if you go to cavity masonry
3:59
in the Housing Provisions because that's the DtS solution that you choose you'll note that
4:04
there are also limitations for that particular element of construction and in this case as
4:09
an example there's limitations on the height, there's requirements for masonry cross walls
4:15
that are subject to wind loads to have support either by a masonry crosswool or steel mullions
4:23
and stating the obvious in subclause (2) there cavity masonry must be constructed with two
4:29
leaves, because that's how we form our cavity, and each of those leaves needs to be a minimum of
4:35
90 millimeters wide. Also talking about cavities is a requirement to have a cavity that has a
4:42
minimum and a maximum dimension, so there's a limitation there or a value of a minimum
4:49
35 millimeters up to 75 millimeters for a cavity. Noting that any services with the exception of
4:55
mullions within that cavity need to be clear and maintain those dimensions. If you do put steel
5:01
mullions into a cavity you need to make sure that there is a moisture barrier on the outside Leaf
5:08
between the inside masonry wall and the external part of that steel mullion that's in 5.3.2(3)(c).
5:20
By looking at unreinforced single leaf masonry it's Part 5.4 of the Housing Provisions 2022
5:27
this particular figure sets out a requirement for external walls to be continuously connected to a
5:33
roof frame. This is not the only Deemed-to-Satisfy solution but it is the only one contained in the
5:39
Housing Provisions if you choose a different method to this that's okay but you would need
5:43
to get that solution from either of the relevant Australian Standards that's 3700 or the 4773 suite.
5:52
Also for unreinforced single leaf masonry going to the tables in particular relating to engaged peers
6:00
we've changed the format of the tables for NCC 2022 and they look a bit like this now to meet
6:06
our digital platform we've set them out with the same information they're just in a new look,
6:11
with new table notes that are relevant to the information in the table. These tables also are
6:17
supported by figures which we'll get to in some slides coming up but importantly to note that
6:24
there are limitations within these tables, in this case for engaged peers, the maximum wind speed of
6:29
N3 noting that for a different thickness of wall there are different solutions and spacings for
6:35
the size of engaged peers, depending on what you choose for whatever design your house will take on.
6:44
A table note worth understanding in this particular table is for 140 millimeter and
6:52
190 millimeter thick walls if you read that note it means you don't necessarily have to have engaged
6:57
peers. Noting that table notes are normative and not informative, so if you have a wall with a
7:04
thickness of 140 millimeters up to 190 millimeters you don't need to provide engaged peers.
7:12
These diagrams or this diagram rather shows and supports the information
7:17
in that table and it simply sets out maximum dimensions in terms of height,
7:23
spacings between engaged peers and permissible openings, if any of these dimensions are exceeded
7:29
it would mean you exceed the dimensions in that table and if that's the case
7:33
you would need to go back to the relevant Australian Standard for the design solution.
7:38
So looking at Part 5.4 unreinforced single leaf masonry specifically internal walls now
7:45
note that in 5.4.3(a) there's a minimum thickness for an internal wall to be 75 millimeters that's
7:51
the size of the masonry unit and also there in (b) we're talking about the connection of these
7:57
internal walls into the ceiling diaphragm. Just like we do for timber framing in houses we have a
8:05
solution that will set out for a minimum thickness of wall of either 75 millimeters right up to 190.
8:13
A particular height limitation on the height but importantly those diagrams on the right
8:18
there are different methods of achieving connection to the ceiling diaphragm that
8:23
still allows for differential movement. These are not the only solutions again if you choose
8:29
a different solution to these ones you would have to go back to AS 3700 or 4773 Parts 1 or 2
8:38
supporting that information those particular clauses also in Part 5.4 for internal walls other
8:45
ways of achieving lateral stability is through return walls shown in this figure. Noting that
8:51
there are dimensions for wing walls, maximum spacings of abutting internal walls and also
8:58
maximum sizes of openings including articulation joints.
9:05
Overall for Part 5.6 the comparison between 2019 and 2022, that is 2019 Volume Two and 2022 Housing Provisions
9:16
you'll note that we've added a new Part 5.6 it's dedicated to masonry components
9:21
and accessories and the reason we've done that is to combine all of the accessories
9:27
and components relative to masonry veneer, cavity masonry, single leaf masonry, isolated piers we've put
9:34
them all in one place so that we're not repeating what we're saying in each of those separate parts.
9:42
An important thing to note for masonry components and accessories and this clause 5.6.6 is a new
9:49
clause dealing with fixing straps and tie-down systems. So in summary there are requirements
9:55
for timber door and window frames a budding cavity masonry that's in subclause (1) there.
10:02
There are requirements for roof tie down for external walls that support sheet metal and tile
10:07
roofs that's subclause (2) and in this subclause note the requirement for tie-down straps to be
10:12
at a 1200 millimeter center maximum and also connected to or adjacent to rafters or trusses.
10:22
Subclause (3) we're talking about roof framing supporting tiled roofs on
10:26
single leaf unreinforced masonry and subclause (4) is talking about
10:31
roof framing supporting sheet roofs on single leaf reinforced masonry.
10:37
An important thing to note in the explanatory information in masonry components and accessories
10:42
is Illustrated here, I mentioned a moment ago the 1200 millimeter centers for tie-down straps
10:49
if you have a length of wall and it contains an opening and that opening is greater than
10:54
1200 millimeters wide it still needs to be tied down but the important thing to note is there
11:01
are no Deemed-to-Satisfy solutions. So that 1200 millimeter opening or if it's greater than 1200
11:07
millimeters the solution for tie down across that opening, as noted in that explanatory information,
11:14
you'll need to seek a solution separately because there are no DtS provisions in the
11:19
Housing Provisions nor are there any in either of the relevant Australian Standards 3700 or 4773.
11:29
Because we've added single leaf masonry into the Housing Provisions for 2022 we've
11:35
got a clause dedicated to weatherproofing single-leaf masonry should the building you're
11:40
designing require weatherproofing not necessarily used for carports or garages using single leaf
11:49
masonry but if there's a case where you need to prevent moisture from outside to the inside
11:53
in a residential part of the building 5.7.6 sets out how you achieve that weatherproofing.